| 2017-04-13 12:24:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040336 |
| | ADD: 901 N. FLAGLER DR. SUITE # 5 |
| | CONT: GEN-X CONSTRUCTION INC. |
| | TEL: 561-963-4490 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. APRIL 13/ 2017 |
| | ACTION: DENIED |
| | |
| | 1A) THE SUBMITTED PLANS ARE NOT DRAFTSMAN QUALITY SET |
| | OF PLANS. THERE IS NO EXISTING PLAN AND PROPOSED SCOPE |
| | OF WORK FLOOR PLAN SHOWING WORK TO SCALE TO DETERMINE |
| | CODE COMPLIANCE IN MANY INSTANCES. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | 1B) THE FLOOR PLAN NO-ONE HAS TAKEN RESPONSIBILITY FOR |
| | THE DRAFTING UP THE PLAN. THE QUALIFIER OF GEN-X |
| | CONSTRUCTION MUST TAKE RESPONSIBILITY FOR THE DRAWING |
| | (FLOOR PLAN FOR BUILDING REVIEW) AND MUST PRINT HIS |
| | NAME, SIGN HIS NAME AND LICENSE NUMBER AS THE AUTHOR OF |
| | THIS DOCUMENT. 2014 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | 1C) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| | FIRE SPRINKLERS BUILDING FIRE SPRINKLERED OR NOT? |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: OCCUPANT LOAD AND |
| | EGRESS CAPACITIES |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | DOOR SIZES |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | ACCESSIBLE ROUTE |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 1D) A HAND WRITTEN SCOPE OF WORK OVER ? OF IT IS |
| | ILLEGIBLE. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | PLAN REVIEWS CANNOT BE PREFORMED WHEN THE SCOPE OF WORK |
| | COULD NOT BE RED. |
| | |
| | 2) THE LAST PERMIT ISSUED FOR THIS TENANT SPACE (UNIT # |
| | 5) IS 09110083. SINCE THEN THIS CONTRACTOR TAKES ON ANY |
| | CHANGES TO THE LATEST REVISION ( 10050688), RATED |
| | TENANT SEPARATION WALLS HAVE BEEN MOVED IN THE |
| | RECEPTION AREA OF SUITE # 5. EXAM ROOM WALLS HAVE BEEN |
| | MOVED AS WELL AS THE RESTROOM LOCATION & SIZES. |
| | 2014 FBC-B 708.3 FIRE-RESISTANCE RATING. FIRE |
| | PARTITIONS SHALL HAVE A FIRE RESISTANCE RATING OF NOT |
| | LESS THAN 1 HOUR. |
| | 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. IN COMBUSTIBLE |
| | CONSTRUCTION WHERE THE FIRE PARTITIONS ARE NOT REQUIRED |
| | TO BE CONTINUOUS TO THE SHEATHING, DECK OR SLAB, THE |
| | SPACE BETWEEN THE CEILING AND THE SHEATHING, DECK OR |
| | SLAB ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN |
| | ACCORDANCE WITH SECTIONS 718.2 AND 718.3 AT THE |
| | PARTITION LINE. |
| | |
| | 3A) SHOW COMPLIANCE WITH 2014 ACCESSIBILITY CODE |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS |
| | NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED |
| | AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST |
| | OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE |
| | MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE |
| | ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN |
| | CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY |
| | SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE |
| | GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN |
| | ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM |
| | FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV) |
| | ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING |
| | FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 3B) 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4) THE VALUE FOR THE SCOPE OF WORK, AND ACTUAL DEPICTED |
| | SCOPE OF WORK INDICATED IN THE SUBMITTED PLAN VERSES |
| | THE LAST KNOWN PERMIT DRAWNINGS WILL INCREASE THE VALUE |
| | FROM THE STATED VALUE. 108.3* BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |