Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-02 Cont ID  
Sent By jgomez Date 2017-05-02 Time 13:25 Rev Time 0.00
Received By jgomez Date 2017-05-02 Time 13:25 Sent To  
Notes
2017-05-02 13:32:05RESIDENTIAL (R3) SUBMITTAL, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- TREMCO BUILT UP ROOFING SYSTEM OVER CONCRETE DECK
 NOA 16-092.16 SUBMITTED:
 A) CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: NEED ASSEMBLY THAT IS DESIGNED TO RECEIVE STONE
 AS SHOWN ON PLANS. ALSO, IF THE DESIGN PRESSURES OF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES OF
 ALL ROOF DECK ZONES, THEN IT CAN NOT BE USED BECAUSE
 ALL THE SYSTEMS IN THIS NOA ARE LIMITED BY GENERAL
 LIMITATION # 9. THIS LIMITATION STATES THAT LISTED
 DESIGN PRESSURES IS APPLICABLE TO ALL ROOF ZONES. IT
 DOESN'T ALLOW FOR RATIONAL ANALYSIS OR EXTRAPOLATION
 FOR ENHANCED FASTENING. SEE GENERAL LIMITATION #9 ON
 LAST PAGE OF NOA SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By jgomez Date 2017-04-13 Time 09:51 Rev Time 0.00
Received By jgomez Date 2017-04-13 Time 07:55 Sent To  
Notes
2017-04-13 09:37:53RESIDENTIAL (R3) SUBMITTAL, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- TREMCO BUILT UP ROOFING SYSTEM OVER CONCRETE DECK
 NOA 16-092.16 SUBMITTED:
 A) CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: NEED ASSEMBLY THAT IS DESIGNED TO RECEIVE STONE
 AS SHOWN ON PLANS. ALSO, IF THE DESIGN PRESSURES OF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES OF
 ALL ROOF DECK ZONES, THEN IT CAN NOT BE USED BECAUSE
 ALL THE SYSTEMS IN THIS NOA ARE LIMITED BY GENERAL
 LIMITATION # 9. THIS LIMITATION STATES THAT LISTED
 DESIGN PRESSURES IS APPLICABLE TO ALL ROOF ZONES. IT
 DOESN'T ALLOW FOR RATIONAL ANALYSIS OR EXTRAPOLATION
 FOR ENHANCED FASTENING. SEE GENERAL LIMITATION #9 ON
 LAST PAGE OF NOA SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-02 Cont ID  
Sent By jgomez Date 2017-05-02 Time 13:36 Rev Time 0.00
Received By jgomez Date 2017-04-19 Time 14:39 Sent To  
Notes
2017-04-20 14:39:52RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-13 Cont ID  
Sent By jgomez Date 2017-04-13 Time 15:22 Rev Time 0.00
Received By jgomez Date 2017-04-06 Time 13:22 Sent To  
Notes
2017-04-07 13:23:06SUBMITTAL ROUTED TO JGOMEZ