Plan Review Details - Permit 17040262
Plan Review Stops For Permit 17040262
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-15 Cont ID  
Sent By cthroop Date 2017-09-15 Time 11:13 Rev Time 0.00
Received By cthroop Date 2017-09-15 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-11 Cont ID  
Sent By cthroop Date 2017-08-11 Time 13:00 Rev Time 0.00
Received By cthroop Date 2017-08-11 Time 08:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By cthroop Date 2017-05-10 Time 11:28 Rev Time 0.00
Received By cthroop Date 2017-05-10 Time 08:45 Sent To  
Notes
2017-05-10 11:31:35BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
 2. PALM BEACH COUNTY IMPACT FEES MAY APPLY.
 3. REF. PLAN SHEET 1 OF 4 - DEMO PLAN NOTE IS TO REMOVE
 WINDOW AND INSTALL SLIDING GLASS DOOR (SGD). PROPOSED
 PLAN NOTE IS TO INSTALL FRENCH DOORS. PLEASE CLARIFY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-03 Cont ID  
Sent By jpearson Date 2017-08-03 Time 08:50 Rev Time 0.00
Received By jpearson Date 2017-08-03 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By vperez Date 2017-04-21 Time 11:30 Rev Time 0.00
Received By vperez Date 2017-04-21 Time 11:30 Sent To  
Notes
2017-04-21 11:30:39INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 2. SHOW EXTERIOR RECEPTACLE AT FRONT/BACK ENTRANCE TO
 MAIN HOUSE PROTECTED BY GFCI DEVICE. FBC RES E3902.3
 3. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS
 PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE
 IN WIDTH. SEE BEDROOM #5.
 4. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET/
 MAIN HOUSE
 5. RECEPTACLE AT THE LAUNDRY ROOM 6FT OF SINK TO BE
 LABELED AS GFCI PROTECTED. FBC RES E3902.7
 6. THERE NEEDS TO BE 3FT. CLEARANCE IN FRONT OF PANELS
 A AND B. DOESN?T APPEAR TO BE.
 7. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION
 PER FBC RES E3903.4
 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-09-01 Cont ID  
Sent By destabro Date 2017-09-01 Time 10:31 Rev Time 0.00
Received By destabro Date 2017-09-01 Time 10:31 Sent To B
Notes
2017-09-01 10:32:319/1/2017 - APPLICANT COMPLIED WITH REVISED WINDOW
 SCHEDULE. DLE

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-08-01 Cont ID  
Sent By destabro Date 2017-08-01 Time 15:19 Rev Time 0.00
Received By destabro Date 2017-08-01 Time 15:19 Sent To B
Notes
2017-08-01 15:22:098/1/2017 - REVISED PLANS SUBSTANTIALLY CHANGE EXTERIOR
 FENESTRATION PATTERN. SUBSTANTIAL LOSS OF WINDOW
 OPENINGS ON THE SIDE AND REAR ELEVATIONS. REDUCED
 WINDOW OPENINGS REQUIRE COA/LEVEL 2 APPROVAL. PLEASE
 DIRECT QUESTIONS TO FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT 561.822.1428.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By destabro Date 2017-05-11 Time 13:46 Rev Time 0.00
Received By destabro Date 2017-05-11 Time 13:46 Sent To B
Notes
2017-05-11 13:48:305/11/2017 - THIS IS A NONCONTRIBUTING PROPERTY TO THE
 BELAIR HISTORIC DISTRICT. DESPITE THE DISCREPANCIES IN
 THE PLAN SHEETS, THE PRODUCT APPROVALS AND PROPOSED
 DESIGN MEET GUIDELINES FOR HISTORIC DISTRICT. DLE
2017-05-11 10:24:41ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-19 Cont ID  
Sent By gjohnson Date 2017-09-19 Time 08:59 Rev Time 0.00
Received By gjohnson Date 2017-08-28 Time 15:18 Sent To  
Notes
2017-08-29 15:18:42R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-20 Time 13:51 Sent To  
Notes
2017-07-21 13:51:39R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-12 Cont ID  
Sent By lmarchan Date 2017-05-12 Time 13:26 Rev Time 0.00
Received By lmarchan Date 2017-04-06 Time 14:11 Sent To  
Notes
2017-04-07 14:11:35R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-08-11 Cont ID  
Sent By cthroop Date 2017-08-11 Time 12:54 Rev Time 0.00
Received By cthroop Date 2017-08-11 Time 08:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By cthroop Date 2017-05-10 Time 11:27 Rev Time 0.00
Received By cthroop Date 2017-05-10 Time 10:18 Sent To  
Notes
2017-05-10 11:28:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By ccole Date 2017-08-17 Time 14:51 Rev Time 0.00
Received By ccole Date 2017-08-17 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 14:16 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 14:16 Sent To  
Notes
2017-05-10 14:59:001ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17040262
 5/10/17
  
 RESULTS: DENIED
  
 1) THE PLAN SHOWS A 16" MAIN RETURN DUCT PENETRATING
 INTO THE AIR HANDLER CLOSET, HOWEVER THE AIR HANDLER
 CLOSET DETAIL DOES NOT SHOW THE DUCT. PLEASE CLARIFY
 HOW THE RETURN AIR SYSTEM IS FUNCTIONING.
  
 2) SHOW THE REQUIRED CLEARANCES FOR THE AIR HANDLER IN
 THE CLOSET- 3" ALONG THE SIDES, BACK AND TOP, WITH THE
 TOTAL WIDTH OF THE CLOSET AT LEAST 12" WIDER THAT THE
 AIR HANDLER- SECTION M1305.1.1.
  
 3) PROVIDE THE BEDROOM TRANSFER DUCT SIZES- SEE SECTION
 M1602.4.
  
 4) PROVIDE KITCHEN EXHAUST AT A RATE OF 100 CFM
 INTERMITTENT OR 25 CFM CONTINUOUS- TABLE 1507.4.
  
 5) THE BATH EXHAUST FAN CAPACITIY SHALL BE MINIMUM 50
 CFM INTERMITTENT OR 20 CFM CONTINUOUS- TABLE 1507.4.
  
 6) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGY
 CONSERVATION FORM R405-2014.
  
 7) SHOW THE TYPE AND SIZE OF DRYER EXHAUST DUCT AND
 TERMINATION LOCATION- SECTION M1502.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-19 Cont ID  
Sent By gjohnson Date 2017-09-19 Time 08:59 Rev Time 0.00
Received By gjohnson Date 2017-09-19 Time 08:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By gjohnson Date 2017-08-17 Time 09:00 Rev Time 0.00
Received By gjohnson Date 2017-08-17 Time 09:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 12:40 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 12:40 Sent To  
Notes
2017-04-27 12:55:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE CLARIFY IS ENTIRE SANITARY SYSTEM BEING
 REPLACED THE THE RISER DOES NOT INDICATE EXISTING OR
 NEW ONLY THE NEW PIPING IS REQUIRED TO BE ON THE PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 2. IS THIS UNIT ABOVE GROUND LEVEL IF IT IS GROUND
 LEVEL PLEASE SHOW THE FIXTURE CONNECTED TO THE
 HORIZONTAL DRAIN AND NOT THE VERTICAL STACK. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE LAUNDRY TRAY AND WASHING MACHINE CAB NOT BE
 VENTED TOGETHER WITH THE TOILET. THE TOILET SHOULD BE
 INDIVIDUALLY VENTED OR CONNECT TO THE BATHROOM GROUP.
 PER FBC PL 912.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-09-01 Cont ID  
Sent By destabro Date 2017-09-01 Time 10:35 Rev Time 0.00
Received By destabro Date 2017-09-01 Time 10:35 Sent To B
Notes
2017-09-01 10:35:489/1/2017 - LANDSCAPE PERMIT SUBMITTED FOR REVIEW
 (#17081352). DLE

Review Stop Z ZONING
Rev No 2 Status F Date 2017-08-01 Cont ID  
Sent By destabro Date 2017-08-01 Time 15:05 Rev Time 0.00
Received By destabro Date 2017-08-01 Time 15:05 Sent To B
Notes
2017-08-01 15:05:298/1/2017 - VALUE OF IMPROVEMENTS EXCEEDS HALF OF
 EXISTING HOUSE VALUE. SEPARATE LANDSCAPE PERMIT IS
 REQUIRED PER ORDINANCE 4689-16. THIS HOLD WILL BE
 RELEASED ONCE THE LANDSCAPE PERMIT APPLICATION IS
 SUBMITTED. QUESTIONS MAY BE DIRECTED TO RAY CARANCI,
 LANDSCAPE PLANNER AT 561-822-1462.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By fmittner Date 2017-05-11 Time 16:44 Rev Time 0.00
Received By fmittner Date 2017-05-11 Time 16:44 Sent To  
Notes
2017-05-11 16:46:20VALUE OF IMPROVEMENTS EXCEEDS HALF OF EXISITNG HOUSE
 VALUE. SEPERATE LANDSCAPE PERMIT IS REQUIRED PER
 ORDINANCE 4689-16, QUESTIONS CONTACT RAY CARANCI,
 LANDSCAPE PLANNER AT 822-1462.