Plan Review Details - Permit 17040259
Plan Review Stops For Permit 17040259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By jwitmer Date 2017-06-06 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2017-06-06 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By jwitmer Date 2017-04-12 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2017-04-12 Time 11:49 Sent To  
Notes
2017-04-12 15:00:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040259
 ADD: 500 N. CONGRESS AVE.
 CONT: PRO LINE BUILDERS
 TEL: 954-448-0298
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 12/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET, ARCHITECTURAL SHEETS AND SHEET S1
 ALL INDICATE THE VULT WIND ZONE IS 160 MPH FOR A
 BUILDING WITH A RISK CATEGORY II. PLEASE NOTE THE 2014
 FBC-B FIGURE 1609A PLACES US IN THE 170 MPH VULT WIND
 ZONE. NOTE # 2 DOES ALLOW FOR LINEAR INTERPOLATION
 BETWEEN CONTOURS IS PERMITTED. PLEASE ALSO NOTE THE
 PRESSURES ON SHEET S-1 WILL INCREASE FOR ALL ZONES.
  
 2) THE PRODUCT APPROVALS THAT ARE INCORPORATED IN THE
 PLANS:
 PGT 1-4 FL331.3 FRENCH DOORS FD-555
 TT 1-2 FL10537.1 THERMA TRU SINGLE IMPACT DOORS
 YKK 1-4 FL16314.2 FIXED WINDOWS YOW225 TUH
 NONE OF THESE APPROVALS IDENTIFY GLAZING, MULLIONS.
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014
 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL
 BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) SHEET A-1 SHOWS THE NEW ELEVATOR SHAFT WALLS AND AN
 EXISTING STAIRWELL ADJACENT TO THE ELEVATOR. THE
 STAIRWELL SHOWS A NEW ROOM WITHIN THE STAIRWELL. FBC-B
 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND RAMP
 OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR EXIT
 STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
  
 4) SHEET A1 SHOWS THE NEW LULA-ELEVATOR PLEASE PROVIDE
 THE MANUFACTURERS SPECIFICATION FOR COMPLIANCE WITH:
 WITH 408.1-4.8 ACCESSIBILITY CODE AND WITH ASME A17.1.
  
 5) BUILDING PROVISO: SHEET A11 SHOWS WELDED CONNECTIONS
 BETWEEN THE STEEL POST AND OVERHEAD STEEL BEAMS W12X35
 PLEASE SHOW COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-23 Cont ID  
Sent By jleahy Date 2017-06-23 Time 16:52 Rev Time 0.00
Received By jleahy Date 2017-06-23 Time 15:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By jleahy Date 2017-05-11 Time 11:29 Rev Time 0.00
Received By jleahy Date 2017-05-11 Time 11:29 Sent To  
Notes
2017-05-11 11:29:55JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
  
 FBC-EC 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF
  
 FBC-EC 505.2.4 - PROVIDE A TIME CLOCK OR ASTRONOMICAL
 SWITCH TO TURN OFF DURING DAYLIGHT HOURS.
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE SIZES
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By pleduc Date 2017-06-05 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By pleduc Date 2017-04-13 Time   Rev Time 0.00
Received By pleduc Date 2017-04-13 Time 09:34 Sent To  
Notes
2017-04-13 10:41:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CS 1 - MULTIPLE OCCUPANCIES ARE INDICATED;
 HOWEVER, THE OCCUPANCY CLASSIFICATION IS NOT.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES.
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE
 COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2,
 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE
 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING SEPARATIONS.
  
  
 PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND ENSURE
 COMPLIANCE WITH SEPARATION REQUIRERMENTS.
  
  
  
  
 2) SHEET A 1 - AN ELEVATOR ROOM IS INDICATED WITHIN THE
 STAIRWELL. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
  
 7.1.3.2.3* AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY
 PURPOSE THAT HAS THE POTENTIAL TO INTERFERE WITH ITS
 USE AS AN EXIT AND, IF SO DESIGNATED, AS AN AREA OF
 REFUGE. (SEE ALSO 7.2.2.5.3.)
  
 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN
 EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER
 STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2.
 7.2.2.5.3.1 OPEN SPACE WITHIN THE EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE THAT HAS THE POTENTIAL TO
 INTERFERE WITH EGRESS.
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT
 ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE,
 OR OTHERWISE HAZARDOUS MATERIALS.
  
 THE DESIGN DOES NOT MEET THE CODE REQUIREMENTS. THERE
 IS NO RATING INDICATED FOR THE CEILING. THE ENTRANCE
 DOOR IS WITHIN THE ENCLOSURE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) SHEET LS 1 - THERE IS A LIGHTWEIGHT ROOF SIGN
 INDICATED; HOWEVER, A ROOF AND FLOOR (R/F) IS REQUIRED.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 4) SHEETS LS 1 & 2 - THERE IS A NOTE INDICATING THE
 EGRESS CAPACITY AT THE 2ND FLOOR STAIWELL DOORS 36" AT
 .2 = 180; HOWEVER, PER NFPA 101 CHAPTER 7, .3 SHALL BE
 USED FOR STAIRWELLS. THOUGH NO DIMESION IS INDICATED,
 FOR REFERENCE PURPOSES; 36" AT .3 = 120. THE EGRESS
 CAPACITY IS THE LESSER OF THE TWO CALCULATIONS.
  
 7.3.3* EGRESS CAPACITY.
 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF
 MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS
 SHOWN IN TABLE
 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 .
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 5) SHEET A 1 - A NEW ELEVATOR IS INDICATED. PER NFPA 1
 & 101,
  
 11.3.1 FIRE FIGHTERS? EMERGENCY OPERATIONS.
 11.3.1.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS. [101:9.4.3.1]
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINCE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-03 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-28 Time 14:34 Sent To  
Notes
2017-06-29 14:34:30RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-26 Cont ID  
Sent By gjohnson Date 2017-06-26 Time 15:26 Rev Time 0.00
Received By gjohnson Date 2017-05-31 Time 10:12 Sent To  
Notes
2017-06-01 10:12:27B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-11 Cont ID  
Sent By jleahy Date 2017-05-11 Time 11:32 Rev Time 0.00
Received By jleahy Date 2017-04-06 Time 14:52 Sent To  
Notes
2017-04-07 14:52:54B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By jwitmer Date 2017-04-12 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2017-04-12 Time 11:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-03 Cont ID  
Sent By ccole Date 2017-07-03 Time 12:38 Rev Time 0.00
Received By ccole Date 2017-07-03 Time 12:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-12 Cont ID  
Sent By ccole Date 2017-06-12 Time 11:58 Rev Time 0.00
Received By ccole Date 2017-06-12 Time 11:58 Sent To  
Notes
2017-06-12 12:21:582ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 AND EXISTING BUILDING CODES
 PERMIT #17040259
 6/12/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGYGAUGE COMPLIANCE REPORT AND AC
 CALCULATIONS APPEAR TO BE FOR ONLY THE FIRST FLOOR
 OCCUPANCY. PLEASE INCLUDE THE ENERGY COMPLIANCE DATA
 AND AC CALCULATIONS FOR THE SECOND FLOOR IN THE
 SUBMITTAL.
  
 2) CORRECT THE CLASSIFICATION OF "NEW FINISHED
 BUILDING" IN THE ENERGYGAUGE PROJECT SUMMARY ON PAGE 2.
 THIS IS A RENOVATION AND CHANGE OF OCCUPANCY.
  
 3) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 NEW AND EXISTING SYSTEMS. INCLDE THE MAKES AND MODELS,
 COOLING AND HEATING CAPACITIES, HEATING KW'S, AND
 EFFICIENCY RATINGS.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-11 Cont ID  
Sent By ccole Date 2017-04-11 Time 14:26 Rev Time 0.00
Received By ccole Date 2017-04-11 Time 14:26 Sent To  
Notes
2017-04-11 14:55:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040259
 4/11/17
  
 1) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION
 AND PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS.
  
 2) ENERGYGAUGE COMPLIANCE FORM: PLEASE PROVIDE SYSTEM
 IDENTIFICATION NUMBERS THAT MATCH THE IDENTIFICATION
 NUMBERS ON THE PLANS.
  
 3) SHEET M-2: PROVIDE A DUCT SMOKE DETECTOR IN THE
 RETURN AIR SYSTEM OF AHU-1- SECTION 606.2.1 FBC-14
 MECHANICAL. PLEASE NOTE THAT A TYPICAL 5-TON AC SYSTEM
 WILL EXCEED 2000 CFMS SUPPLY AIR.
  
 4) M-2: PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE O/A
 DUCTS SERVING AHU-1 & 2- SECTION 403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 5) M-4: PROVIDE MANUFACTURER'S SPECIFICATIONS (CUT
 SHEET) FOR THE FASSON #9150 STRAPPING TAPE THAT
 INDICATES COMPLIANCE WITH SMACNA STANDARDS.
  
 6) M-4: THE CONDENSER ANCHORING DETAIL HAS A COPIED,
 OUTDATED ENGINEER'S SEAL, AND IS BASED ON AN OUTDATED
 WIND SPEED. PLEASE SEE SECTION 1609 FBC-14 BUIILDING
 AND PROVIDE CURRENT CODE COMPLIANT ENGINEERING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-26 Cont ID  
Sent By gjohnson Date 2017-06-26 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2017-06-26 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By gjohnson Date 2017-05-08 Time 07:50 Rev Time 0.00
Received By gjohnson Date 2017-05-05 Time 13:35 Sent To  
Notes
2017-05-08 07:58:031ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PVC PIPE IS PROHIBITED IN USE FOR WATER DISTRIBUTION
 PIPING INSIDE THE BUILDING THE TABLE PROVIDED ON SHT.
 P-8 IS FOR WATER SERVICE PIPE WHICH IS THE PIPING FROM
 THE METER TO THE STRUCTURE OUTSIDE THE BUILDING, WATER
 DISTRIBUTION PIPE SHALL COMPLY WITH FBC PL TABLE 605.4
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-06-21 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-21 Time 13:40 Sent To  
Notes
2017-06-21 14:36:40PAUL GREILICH, SENIOR PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-04-21 Time   Rev Time 0.00
Received By pgreilic Date 2017-04-21 Time 14:02 Sent To  
Notes
2017-04-21 14:03:34PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy