Plan Review Details - Permit 17040156
Plan Review Stops For Permit 17040156
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-19 Cont ID  
Sent By wjolin Date 2017-06-14 Time 13:48 Rev Time 0.00
Received By jleahy Date 2017-06-06 Time 16:54 Sent To  
Notes
2017-06-06 16:55:22 
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By vperez Date 2017-04-13 Time 10:39 Rev Time 0.00
Received By vperez Date 2017-04-13 Time 10:39 Sent To  
Notes
2017-04-13 10:40:27ADDRESS FIRE COMMENTS FOR AN ELECTRICAL APPROVAL.
  
 V.PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By wjolin Date 2017-06-06 Time 11:30 Rev Time 0.00
Received By wjolin Date 2017-06-06 Time 11:16 Sent To E
Notes
2017-06-06 11:30:232210 NORTH AUSTRALIAN AVENUE
 PERMIT #17040156
 MASTER #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 6/14/17 UPDATE:
 IN REFERENCE TO THE RESPONSES; KNIGHT FIRE AND SECURITY
 PROVIDED (ATTACHED) A ONE PAGE DOCUMENT WITH RESPONSES
 TO THE INITIAL REVIEW NOTES DATED 2017 04/12 ON OUR
 REVISED SUBMITTAL TO ANSWER THE REVIEW NOTES. I HAVE
 ATTACHED THIS DOCUMENT FOR YOUR REVIEW. IF WE NEED TO
 RESUBMIT THIS FORMALLY AS A RESPONSE TO THE FIRST AND
 SECOND REVIEW PLEASE LET ME KNOW.
  
 IN REGARDS TO THE PLANS WITH CLOUDED AREAS AND DELTAS
 WE FELT THAT THERE WERE SO MANY CHANGES WE WOULD HAVE
 TO CLOUD EACH AND EVERY PAGE. AFTER RECEIPT OF THE 1ST
 REVIEW WE REVISITED THE OWNERS ORIGINAL ENGINEER OF
 RECORDS DESIGN AND DETERMINED WE NEEDED A MORE IN DEPTH
 LOOK AT THE SITE CONDITIONS AS IT RELATED TO THE DESIGN
 AND COMPLIANCE. DURING THIS PERIOD WE DISCOVERED
 SEVERAL AREAS THAT WERE NOT COVERED ON OUR PLANS AS IT
 RELATED TO THIS SYSTEM. BELOW I HAVE LISTED SOME OF THE
 CHANGES WE ADDED TO OUR PLANS AND RESUBMITTAL:
  
 MULTIPLE LOCATIONS WHERE FIRE SPRINKLER TIE INS WERE
 NOT INDICATED WERE ADDED (RISER, FLOW AND TAMPERS)
 INCORRECT ROOM NUMBERS ON THE PLANS THAT WOULD BECOME
 CONFUSING IN THE PROGRAMMING PHASE OF THE PROJECT HAVE
 BEEN CHANGED TO REFLECT THE CORRECT ROOM NUMBER
 FANS NOT INDICATED (3)
 MODULES TO PROVIDE TWO SEPARATE TWO SMOKE COMPARTMENTS
 PER FLOOR FOR THE SLEEPING AREAS HAVE BEEN ADDED?
 CHANGE OF OCCUPANT NOTIFICATION WITHIN EACH TENANT ROOM
 (NOW ALL SOUNDERS IN EACH ROOM ARE LOW FREQUENCY
 SOUNDER BASES)
 PLAN OF SEQUENCE CHANGE AND ADDED TO PLANS
 ADDITIONAL MODULES TO ALLOW FOR 'STAND AND DEFEND" THUS
 PROVIDING A MINIMUM OF TWO SMOKE COMPARTMENTS PER FLOOR
 MODULES TO SEPARATE NOTIFICATION DEVICES FOR THE
 COMPARTMENT OF RELOCATION
 SLC CIRCUIT CHANGES
 SLC DEVICE ADDRESS CHANGES ON ALL FLOORS
 NOTIFICATION DEVICE CHANGES AS WELL AS ADDRESS (CIRCUIT
 NUMBER / DEVICE NUMBER)
  
 HUGH BLAIR
 KNIGHT FIRE AND SECURITY
 (561) 414-0420
  
  
 2ND REVIEW:
 NO RESPONSES TO ORIGINAL REVIEW COMMENTS SUBMITTED AND
 DRAWINGS DO NOT INDICATE ANY REVISION CLOUDS WITH
 DELTAS SHOWING WHAT HAS BEEN CHANGED.
  
 1ST REVIEW:
 PLAN INDICATES EXISTING FIREFIGHTER PHONE JACKS ARE TO
 BE REMOVED. HOW WILL FIRE DEPARTMENT COMMUNICATIONS BE
 ACHIEVED? IS THE BUILDING BEING UPGRADED WITH A DAS/BDA
 RADIO SYSTEM?
  
 THE FIRST FLOOR ALF SLEEPING AREAS ARE NOT DIVIDED INTO
 TWO SMOKE COMPARTMENTS.
  
 DESIGN INDICATES THREE ENTIRE FLOORS WILL BE EVACUATED
 DURING GENERAL FIRE ALARM. THIS EVACUATION CONCEPT IS
 NOT SUPPORTED BY THE LIFE SAFETY CODE. THE CODE
 REQUIRES ASSISTED LIVING FACILITIES TO BE PROVIDED WITH
 AT LEAST TWO SMOKE COMPARTMENTS PER FLOOR TO ALLOW
 "DEFEND IN PLACE" WHEREBY RESIDENTS ARE RELOCATED TO AN
 ADJACENT SMOKE COMPARTMENT ON THE SAME FLOOR DURING A
 FIRE ALARM. FIRE ALARM DEVICES SHOULD ONLY BE ACTIVATED
 IN THE COMPARTMENT OF INCIDENCE AND THE COMPARTMENT
 ABOVE THE FLOOR OF INCIDENCE. FIRE ALARM NOTIFICATION
 DEVICES IN THE COMPARTMENT OF RELOCATION SHOULD NOT BE
 ACTIVATED.
  
 5TH FLOOR EAST WING CORRIDOR NOTIFICATION DEVICES ALL
 HAVE THE SAME ADDRESS.
  
 ALL DEVICES ON THE 6TH FLOOR HAVE THE SAME ADDRESSES AS
 THE 5TH FLOOR DEVICES.
  
 PLAN SEQUENCE OF OPERATION INDICATES ACTIVATION OF ANY
 SMOKE DETECTOR WILL RESULT IN A GENERAL BUILDING FIRE
 ALARM. SMOKE ALARMS/DETECTORS WITHIN THE INDIVIDUAL
 DWELLING UNITS SHALL RESULT IN A LOCAL ALARM ONLY
 (SINGLE DWELLING UNIT).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By wjolin Date 2017-04-12 Time 16:15 Rev Time 0.00
Received By wjolin Date 2017-04-12 Time 15:39 Sent To E
Notes
2017-04-12 16:15:292210 NORTH AUSTRALIAN AVENUE
 PERMIT #17040156
 MASTER #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN INDICATES EXISTING FIREFIGHTER PHONE JACKS ARE TO
 BE REMOVED. HOW WILL FIRE DEPARTMENT COMMUNICATIONS BE
 ACHIEVED? IS THE BUILDING BEING UPGRADED WITH A DAS/BDA
 RADIO SYSTEM?
  
 THE FIRST FLOOR ALF SLEEPING AREAS ARE NOT DIVIDED INTO
 TWO SMOKE COMPARTMENTS.
  
 DESIGN INDICATES THREE ENTIRE FLOORS WILL BE EVACUATED
 DURING GENERAL FIRE ALARM. THIS EVACUATION CONCEPT IS
 NOT SUPPORTED BY THE LIFE SAFETY CODE. THE CODE
 REQUIRES ASSISTED LIVING FACILITIES TO BE PROVIDED WITH
 AT LEAST TWO SMOKE COMPARTMENTS PER FLOOR TO ALLOW
 "DEFEND IN PLACE" WHEREBY RESIDENTS ARE RELOCATED TO AN
 ADJACENT SMOKE COMPARTMENT ON THE SAME FLOOR DURING A
 FIRE ALARM. FIRE ALARM DEVICES SHOULD ONLY BE ACTIVATED
 IN THE COMPARTMENT OF INCIDENCE AND THE COMPARTMENT
 ABOVE THE FLOOR OF INCIDENCE. FIRE ALARM NOTIFICATION
 DEVICES IN THE COMPARTMENT OF RELOCATION SHOULD NOT BE
 ACTIVATED.
  
 5TH FLOOR EAST WING CORRIDOR NOTIFICATION DEVICES ALL
 HAVE THE SAME ADDRESS.
  
 ALL DEVICES ON THE 6TH FLOOR HAVE THE SAME ADDRESSES AS
 THE 5TH FLOOR DEVICES.
  
 PLAN SEQUENCE OF OPERATION INDICATES ACTIVATION OF ANY
 SMOKE DETECTOR WILL RESULT IN A GENERAL BUILDING FIRE
 ALARM. SMOKE ALARMS/DETECTORS WITHIN THE INDIVIDUAL
 DWELLING UNITS SHALL RESULT IN A LOCAL ALARM ONLY
 (SINGLE DWELLING UNIT).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-06 Time 17:12 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 12:07 Sent To  
Notes
2017-05-18 12:07:30RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-13 Cont ID  
Sent By vperez Date 2017-04-13 Time 10:40 Rev Time 0.00
Received By vperez Date 2017-04-13 Time 10:40 Sent To  
Notes
2017-04-06 14:11:08ROUTED TO FIRE INBOX