Plan Review Details - Permit 17040007
Plan Review Stops For Permit 17040007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-23 Cont ID  
Sent By jwitmer Date 2017-05-23 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-05-23 Time 17:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-04-11 Cont ID  
Sent By jwitmer Date 2017-04-11 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2017-04-11 Time 14:08 Sent To  
Notes
2017-04-11 14:40:34BUILDING PROVISO: SHEET A-4
 2014 FBC-ACCESSIBILITY CODE
 SECTION 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-06 Cont ID  
Sent By rlecky Date 2017-04-06 Time 15:10 Rev Time 0.00
Received By rlecky Date 2017-04-06 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-10 Cont ID  
Sent By scaldero Date 2017-04-10 Time 11:44 Rev Time 0.00
Received By scaldero Date 2017-04-10 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-06-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-12 Time 14:26 Sent To  
Notes
2017-06-13 14:27:57RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 11:33 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 13:24 Sent To  
Notes
2017-05-12 13:24:09C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-02 Cont ID  
Sent By tklarge Date 2017-05-02 Time 06:11 Rev Time 0.00
Received By tklarge Date 2017-04-03 Time 15:14 Sent To  
Notes
2017-04-04 15:18:54C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-04-11 Cont ID  
Sent By jwitmer Date 2017-04-11 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2017-04-11 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-15 Cont ID  
Sent By ccole Date 2017-06-15 Time 12:32 Rev Time 0.00
Received By ccole Date 2017-06-15 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-19 Cont ID  
Sent By ccole Date 2017-05-19 Time 16:23 Rev Time 0.00
Received By ccole Date 2017-05-19 Time 16:23 Sent To  
Notes
2017-05-19 16:34:341ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040007
 5/19/17
  
 1) M0.1: THERE APPEAR TO BE MATHMATICAL ERRORS IN THE
 O/A CALCULATIONS FOR WORK SPACES 1 THRU 6 IN THE
 SCHEDULE, AND ALSO IN THE TOTAL REQUIRED AND PROVIDED
 CFMS OF O/A- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-04-07 Time 15:13 Rev Time 0.00
Received By ccole Date 2017-04-07 Time 15:13 Sent To  
Notes
2017-04-07 15:31:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #1704007
 4/7/17
  
 1) M0.1 & M1.1: SCOPE OF WORK NOTE #1 INDICATES ONE NEW
 VAV BOX, THE PLANS AND O/A CALCULATIONS INDICATE ALL
 EXISTING.
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE VAV BOXES-
 MAKES, MODEL NUMBERS AND CAPACITIES.
  
 3) PLEASE PROVIDE A VAV BOX SUPPORT AND DUCT CONNECTION
 DETAIL.
  
 4) PLACE A NOTE ON THE PLAN INDICATING ABOVE CEILING
 PLENUM SPACE.
  
 5) M1.1: SHOW THE POINT OF CONNECTION OF THE NEW TOILET
 EXHAUST DUCT TO THE EXISTING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 11:33 Rev Time 0.00
Received By gjohnson Date 2017-06-09 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By tklarge Date 2017-05-02 Time 06:11 Rev Time 0.00
Received By tklarge Date 2017-05-02 Time 05:40 Sent To  
Notes
2017-05-02 06:11:171) A SERVICE SINK IS REQUIRED IN THIS SPACE PER 2014
 FBC-PLUMBING TABLE 403.1.
 2) SHT. A-4 - DEATAIL #2 - TRANSFER SHOWER DIMENSIONS
 SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE
 DIMENSIONS. SHOW THIS ON THE DETAIL. FBC-ACCESS.
 SEC.608.2.1.
 3) L-SHAPED SHOWER SEATS SHALL BE LOCATED PER 2014
 FBC-ACCESS SEC.610.3.2.
 4) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWERS SHALL
 BE LOCATED PER 2014 FBC-ACCESS. SEC.608..5.1. SHOW THE
 DIMENSIONS ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  