Plan Review Details - Permit 17040006
Plan Review Stops For Permit 17040006
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-10-13 Cont ID  
Sent By cthroop Date 2017-10-13 Time 11:04 Rev Time 0.00
Received By cthroop Date 2017-10-13 Time 10:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-08-23 Cont ID  
Sent By cthroop Date 2017-08-23 Time 07:34 Rev Time 0.00
Received By cthroop Date 2017-08-21 Time 16:37 Sent To M
Notes
2017-08-23 07:36:55BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 4TH REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. ONE SET OF PLANS NOT SIGNED.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-27 Time 07:37 Rev Time 0.00
Received By cthroop Date 2017-07-05 Time 09:40 Sent To  
Notes
2017-07-05 16:08:00BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE EXISTING FLOOR PLAN.
 2. VALUE CANNOT BE DETERMINED AT THIS TIME.
  
 PLEASE REVIEW COMMENTS FROM PREVIOUS REVIEWS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By cthroop Date 2017-06-05 Time 14:30 Rev Time 0.00
Received By cthroop Date 2017-06-05 Time 14:18 Sent To  
Notes
2017-06-05 14:34:41BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CHANGED WORK DESCRIPTION FROM BATHROOM REMODEL TO
 BATHROOM ADDITION.
 2. CANNOT DETERMINE VALUE.
 3. SUBMIT ALL DOCUMENTS IN DUPLICATE.
 4. PROVIDE MECHANICAL PLAN.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By cthroop Date 2017-04-05 Time 10:22 Rev Time 0.00
Received By cthroop Date 2017-04-05 Time 10:19 Sent To E
Notes
2017-04-05 10:35:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONFLICT BETWEEN WORK DESCRIPTION (SOW) ON
 APPLICATION (BATHROOM REMODEL) AND PLANS (BATHROOM
 ADDITION). PLEASE CLARIFY.
 2. PROVIDE FLOOR PLAN WITH EXISTING LAYOUT/USE AND
 PROPOSED WORK.
 3. VALUE CANNOT BE DETERMINED UNTIL SOW IS CLARIFIED.
 4. PROVIDE VENTILATION PER R303.4.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 12:16 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 08:14 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 08:14 Sent To  
Notes
2017-08-15 08:14:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY.
 ONE PLAN WAS NOT SIGNED, 1 PLAN WAS SIGNED BY "CHARLES
 JACKSON", WHO IS NOT A LICENSED DESIGN PROFESSIONAL PER
 FDBPR WEBSITE. PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, 481; FBC 107.2.1
 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 PROVIDE SWITCHED LIGHT AT EXTERIOR DOOR OF BATHROOM PER
 PREVIOUS COMMENT. NEC 210.70(A)(2)(B), FBC RE3903.3
 3. PREVIOUS COMMENT #5 NOT ADDRESSED SATISFACTORILY.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 OUTLETS ARE NOT SHOWN IN AREA ADJACENT TO THE PROPESED
 WORK AREA. SHOW AS EITHER EXISTIG OF NEW. PROVIDE
 CORRECTION. NEC 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2017-07-05 Cont ID  
Sent By cthroop Date 2017-07-05 Time 15:59 Rev Time 0.00
Received By cthroop Date 2017-07-05 Time 15:59 Sent To  
Notes
2017-07-05 16:00:12ADDED 4TH E STOP BY MISTAKE. 3RD E STOP RESULTS REMAIN
 IN EFFECT. CT

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-06-26 Cont ID  
Sent By jpearson Date 2017-06-26 Time 07:41 Rev Time 0.00
Received By jpearson Date 2017-06-26 Time 07:41 Sent To  
Notes
2017-06-26 07:57:42CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL OR ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.025; 471.003(2)(H)
 2. PROVIDE LIGHT AT EXTERIOR DOOR. "FOR DWELLING UNITS,
 ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC
 POWER, AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE OF
 OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS".
 NEC 210.70(A)(2)(B), FBC RE3903.3
 3. PROVIDE FLOOR PLAN OF HOUSE SHOWING LOCATIONS OF
 EXISTING SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO
 CODE, SHOW AS NEW INSTALLATIONS. FBC R314, R315; FBC
 107.2.1
 4. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED
 CIRCUITS, INCLUDE WIRE AND BREAKER SIZE AND TYPE. NEC
 408.4; FBC RE3706.2; FBC 107.2.1
 5. PROVIDE FLOOR PLAN OF AREA WHERE WORK IS PROPOSED
 INDICATING ANY EXISTING, RELOCATED, OR NEW POWER AND
 LIGHTING OUTLETS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-27 Cont ID  
Sent By jleahy Date 2017-06-01 Time 12:35 Rev Time 0.00
Received By jpearson Date 2017-06-01 Time 12:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By vperez Date 2017-04-05 Time 11:04 Rev Time 0.00
Received By vperez Date 2017-04-05 Time 11:04 Sent To M
Notes
2017-04-05 11:05:32PLEASE CLARIFY ELECTRICAL SCOPE OF WORK. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-10-13 Cont ID  
Sent By cthroop Date 2017-10-13 Time 11:04 Rev Time 0.00
Received By cthroop Date 2017-09-18 Time 10:49 Sent To  
Notes
2017-09-19 10:49:50R06

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-23 Cont ID  
Sent By hmoser Date 2017-08-23 Time 11:43 Rev Time 0.00
Received By hmoser Date 2017-08-10 Time 15:57 Sent To  
Notes
2017-08-14 15:58:31R42

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-05 Cont ID  
Sent By cthroop Date 2017-07-05 Time 16:05 Rev Time 0.00
Received By cthroop Date 2017-06-20 Time 11:36 Sent To  
Notes
2017-06-21 11:37:05R01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-05 Cont ID  
Sent By cthroop Date 2017-06-05 Time 14:30 Rev Time 0.00
Received By cthroop Date 2017-05-15 Time 10:10 Sent To  
Notes
2017-05-16 10:14:25R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-11 Cont ID  
Sent By hmoser Date 2017-04-11 Time 09:04 Rev Time 0.00
Received By hmoser Date 2017-04-03 Time 11:20 Sent To  
Notes
2017-04-04 11:21:07ROUTED TO PLUMBING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2017-08-23 Cont ID  
Sent By hmoser Date 2017-08-23 Time 11:41 Rev Time 0.00
Received By hmoser Date 2017-08-23 Time 11:36 Sent To  
Notes
2017-08-23 11:43:03EXHAUST DUCT AND FAN TO BE INSPECTED BY BUILDING HM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-07-05 Cont ID  
Sent By cthroop Date 2017-07-05 Time 16:04 Rev Time 0.00
Received By cthroop Date 2017-07-05 Time 16:04 Sent To  
Notes
2017-07-05 16:04:57NO MECHANICAL WORK. EXHAUST FAN WILL BE REVIEWED BY
 ELCTRICAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-05-17 Cont ID  
Sent By hmoser Date 2017-05-17 Time 14:03 Rev Time 0.00
Received By hmoser Date 2017-05-17 Time 13:41 Sent To  
Notes
2017-05-17 14:05:09NO MECHANICAL OR A/C WORK AT THIS TIME HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-11 Cont ID  
Sent By hmoser Date 2017-04-11 Time 09:03 Rev Time 0.00
Received By hmoser Date 2017-04-11 Time 09:02 Sent To  
Notes
2017-04-11 09:04:29NO AIR CONDITIONING PLAN SUBMITTED HM.

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-09-29 Cont ID  
Sent By thunt Date 2017-09-29 Time 15:53 Rev Time 0.00
Received By thunt Date 2017-09-29 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-08-21 Cont ID  
Sent By thunt Date 2017-08-21 Time 16:16 Rev Time 0.00
Received By thunt Date 2017-08-21 Time 15:45 Sent To  
Notes
2017-08-21 16:15:024TH REVIEW
  
 PREVIOUS COMMENTS HAVE STILL NOT BEEN ADDRESSED. THE
 TOTAL VALUATION OF THE ENTIRE JOB APPEARS LOW, PLEASE
 PROVIDE A DETAILED, QUANTITY ESTIMATES, AND OR BONA
 FIDE SIGNED CONTRACTS TO MEET WPB AMEND TO FBC 109.3
  
 NEW COMMENTS
 1) SHOW NEW LOCATION OF WATER HEATER
 2) 1 OF THE PLANS IS NOT SIGED
  
 AT THIS TIME A THOROUGH REVIEW CANNOT BE COMPLETED AT
 THIS TIME.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-06-26 Cont ID  
Sent By gjohnson Date 2017-06-26 Time 16:56 Rev Time 0.00
Received By gjohnson Date 2017-06-26 Time 16:25 Sent To  
Notes
2017-06-26 16:57:542ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS 3RD REQUEST
  
  
  
 NOT COMPLIED 2. THE TOTAL VALUATION OF THE JOB APPEARS
 LOW PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES,
 AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND
 VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC
 109.3
  
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By gjohnson Date 2017-06-05 Time 10:38 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 08:48 Sent To  
Notes
2017-06-05 11:00:202ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS
  
 NOT COMPLIED 1. PLEASE CLARIFY THE PLAN STATES BATHROOM
 ADDITION THE APPLICATION STATES BATHROOM REMODEL
 CLARIFY ON THE PLAN IF ITS A REMODEL OF EXISTING
 BATHROOM OR CHANGE APPLICATION IF ITS A ADDITION OF NEW
 BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 NOT COMPLIED 2. THE TOTAL VALUATION OF THE JOB APPEARS
 LOW PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES,
 AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND
 VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC
 109.3
  
 NEW PLUMBING COMMENTS:
  
 1. PROVIDE TWO PLAN SHEETS FOR THE NEW BATHROOM
 ADDTION. PER WPB AMEND TO FBC 107.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-04 Cont ID  
Sent By gjohnson Date 2017-04-04 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2017-04-04 Time 16:33 Sent To  
Notes
2017-04-04 16:51:471ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE CLARIFY THE PLAN STATES BATHROOM ADDITION THE
 APPLICATION STATES BATHROOM REMODEL CLARIFY ON THE PLAN
 IF ITS A REMODEL OF EXISTING BATHROOM OR CHANGE
 APPLICATION IF ITS A ADDITION OF NEW BATHROOM. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE TOTAL VALUATION OF THE JOB APPEARS LOW PLEASE
 PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR BONA
 FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET
 THE
 APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC
 109.3
  
 3. PROVIDE EXISTING FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  