Plan Review Details - Permit 17031290
Plan Review Stops For Permit 17031290
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 08:05 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 14:13 Sent To  
Notes
2017-05-09 14:13:58RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-13 Cont ID  
Sent By ccole Date 2017-04-13 Time 15:30 Rev Time 0.00
Received By ccole Date 2017-03-31 Time 09:53 Sent To  
Notes
2017-04-04 09:54:11ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 08:05 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 07:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By ccole Date 2017-04-13 Time 15:31 Rev Time 0.00
Received By ccole Date 2017-04-13 Time 15:31 Sent To  
Notes
2017-04-13 15:53:101ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031290
 4/13/17
  
 1) THE WORK DESCRIPTION ON THE APPLICATION READS
 "INSTALL 4 FANS & DUCTWORK". THE SUBMITTED PLANS AND
 FAN SCHEDULE SHOW 20 FANS. I AM ASSUMING THE FANS TO BE
 INSTALLED ARE FOR THE KITCHEN HOODS, HOWEVER THERE ARE
 ONLY TWO GREASE EXHAUST FANS- ( EF-16 & 18) AND ONE
 DISHWASHER EXHAUST FAN- (EF-15) SHOWN ON THE PLANS AND
 THE SCHEDULE. PLEASE PROVIDE MORE SPECIFIC
  
 INFORMATION ON THE APPLICATION AND ON THE PLANS.
  
 2) CLARIFY IF THE GREASE EXHAUST DUCTS WILL BE
 INSTALLED 18" CLEAR OF COMBUSTIBLES OR IF DUCTWRAPPING
 WILL BE INSTALLED. PROVIDE NOTES ON THE PLAN AND SUBMIT
 A PRODUCT DATA SHEET FOR THE WRAP IF APPLICABLE TO THE
 PROJECT.
  
 3) PROVIDE A ROOF PLAN THAT SHOWS CLEARANCE DISTANCE
 MEASUREMENTS FROM THE GREASE EXHAUST TERMINATIONS TO
 MECHANICAL OR GRAVITY AIR INTAKES- SEE SECTION
 506.3.13.3.
  
 4) PROVIDE A DETAIL THAT SHOWS THE CLEARANCE DISTANCE
 HEIGHT FROM THE THE ROOF SURFACE TO THE EXHAUST OUTLET-
 SECTION 506.3.13.1.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE FANS
 AND FAN CURBS TO THE ROOF STRUCTURE- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  