Plan Review Details - Permit 17031256
Plan Review Stops For Permit 17031256
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-12-08 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 17:24 Rev Time 0.00
Received By jwitmer Date 2017-12-07 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2017-11-13 Time 07:29 Sent To  
Notes
2017-11-13 08:20:02BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. NOV. 13/2017
 ACTION: DENIED
  
 1-3A) COMPLIED.
  
 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO
 BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST
 CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST.
 THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS
 FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL
 ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE
 ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3C) 4TH REQUEST. PLEASE NOTE SHEET S-1 SHOWS A COLUMN
 SCHEDULE. THE SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO
 BE 6 X 6 INCH STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH
 STEEL COLUMNS NOWHERE IN THE STEEL COLUMN SCHEDULE HAS
 IT BEEN UPDATED TO WOOD COLUMNS. UPDATE PLANS
 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 3D) SHEET S-2 SEMI COMPLIED. THERE IS ONLY ONE SET OF
 SUBMITTED PLANS WITH A UPDATED (10-19-17). THE OTHER
 SET HAS (2) S-5 SHEETS DATED (10-19-17).
  
 3D) PLEASE BE AWARE, THE DESIGN GIVEN THE 6X6 WOOD POST
 HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR
 DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL
 WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD
 FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) COMPLIED.
  
 5) COLLATE PLANS INTO COMPLETE SETS OF DOCUMENTS.
 SUBMITTED 2 DIFFERENT PRODUCT APPROVALS VOID OUT THE
 ONE NOT BEING USED> WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-31 Cont ID  
Sent By jwitmer Date 2017-08-31 Time   Rev Time 0.00
Received By jwitmer Date 2017-08-31 Time 09:55 Sent To  
Notes
2017-08-31 14:14:28BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. AUGUST 31/2017
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SHOP DRAWING OF APPROVAL ON THE
 PRODUCT APPROVAL. NEITHER THE CONTRACTOR NOR THE
 DESIGNER OF RECORD HAS COMPLIED WITH REQUIREMENT # 3
 IDENTIFYING THE SYSTEM IN THE PRODUCT APPROVAL. WHICH
 CONFIGURATION OF PANELS, TRACK SYSTEMS, AND ASSOCIATED
 HARDWARE. SHEETS 11-14 OF THE TECHNICAL SHEETS ARE FOR
 WOOD STRUCTURES.
  
  
 2ND ROUND OF COMMENTS. IF THE CONTRACTOR (BEELINE
 BUILDING CORP) IS LOOKING FOR COMPLETING OF ENCLOSURE
 OF THE COOLER AND FREEZERS WITH THE USE OF HURRICANE
 PANELS THE DESIGNER OF RECORD WILL NEED TO APPLY THEIR
 SHOP DRAWING STAMP OF APPROVAL ON THE PRODUCT APPROVAL.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) COMPLIED. FLORIDA APPROVAL FL1968-R3
  
 3) PLEASE NOTE THE CONTRACTOR STATES THE STORM PANELS
 ARE GOING TO BE PLACED HORIZONTALLY BUT NOWHERE IS
 THERE AN INSTALLATION SCHEDULE REPEAT FROM THE LAST
 REVIEW!!!!!
  
 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO
 BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST
 CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST.
 THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS
 FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL
 ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE
 ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3C) PLEASE NOTE SHEET S-1 SHOWS A COLUMN SCHEDULE. THE
 SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO BE 6 X 6 INCH
 STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH STEEL COLUMNS
 NOWHERE IN THE STEEL COLUMN SCHEDULE HAS IT BEEN
 UPDATED TO WOOD COLUMNS. UPDATE PLANS DISCREPANCY IN
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
  
 3D) SHEET S-2 DOES NOT PROVIDE WHAT THE CENTER TO
 CENTER LAYOUT OF THE 6 X 6 INCH WOOD POST ARE CENTERED,
 NOR DOES THE PLAN OR STORM SHUTTER SCHEDULE INDICATE
 THE PRESSURES GIVEN ARE LIMITED TO NINE FEET. THE
 STRUCTURAL SHEET S-2 NEEDS TO BE UPDATED. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 3D) PLEASE BEWARE, THE DESIGN GIVEN THE 6X6 WOOD POST
 HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR
 DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL
 WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD
 FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2ND ROUND COMMENT. WITHIN THE PRODUCT APPROVAL
 SUBMITTED THERE IS DETAILS FOR ANCHORING TO CONCRETE
 FOR BOTH THE TOP AND BOTTOM TRACKS, AND FOR WOOD. THE
 SUBMITTED STRUCTURAL SHEETS SHOWS A CONCRETE SLAB AND A
 STEEL HORIZONTAL BEAM WITH METAL SCREED BENT PLATE
 1/4X4X3 INCH WELDED TO THE BEAM. WITHIN THIS PRODUCT
 APPROVAL THERE IS NO DETAILS NOR TABLE FOR ANCHOR
 SPACING. PLEASE PROVIDE : A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, UNIT
 MARK NUMBERS, UNIT SPANS/WIDTHS, IF STORM BAR
 REINFORCING REQUIREMENTS ARE REQUIRED, WALL PRESSURE
 ZONES, SLAT TYPES, GAUGE OF PANELS, ETC.
  
 4)3RD REQUEST. NOT ADDRESSED. COMMENT FROM THE LAST
 REVIEW IS NOT ADDRESSED. WITH THE STORM PANELS IN
 PLACE, HOW WILL THE CONDENSING UNITS DISSIPATE THE HEAT
 IF WITHIN THE ENCLOSED ROOM? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 16:24 Rev Time 0.00
Received By jwitmer Date 2017-07-20 Time 15:49 Sent To  
Notes
2017-07-20 16:24:34BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JULY 20/2017
 ACTION: DENIED
  
 1) IF THE CONTRACTOR (BEELINE BUILDING CORP) IS LOOKING
 FOR COMPLETING OF ENCLOSURE OF THE COOLER AND FREEZERS
 WITH THE USE OF HURRICANE PANELS THE DESIGNER OF RECORD
 WILL NEED TO APPLY THEIR SHOP DRAWING STAMP OF APPROVAL
 ON THE PRODUCT APPROVAL.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) THE 2ND ISSUE WITH THE SUBMITTED EASTERN METAL
 BERTHA ALUMINUM STORM PANELS, THERE IS NO COVER SHEET
 INDICATING IF THE SUBMITTED APPROVAL IS A MIAMI-DADE
 NOA OR A FLORIDA APPROVAL. PLEASE IDENTIFY SO
 COMPLIANCE CAN BE VERIFIED. 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (E) SHUTTERS.
  
 3) WITHIN THE PRODUCT APPROVAL SUBMITTED THERE IS
 DETAILS FOR ANCHORING TO CONCRETE FOR BOTH THE TOP AND
 BOTTOM TRACKS, AND FOR WOOD. THE SUBMITTED STRUCTURAL
 SHEETS SHOWS A CONCRETE SLAB AND A STEEL HORIZONTAL
 BEAM WITH METAL SCREED BENT PLATE 1/4X4X3 INCH WELDED
 TO THE BEAM. WITHIN THIS PRODUCT APPROVAL THERE IS NO
 DETAILS NOR TABLE FOR ANCHOR SPACING. PLEASE PROVIDE :
 A COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, IF STORM BAR REINFORCING REQUIREMENTS ARE
 REQUIRED, WALL PRESSURE ZONES, SLAT TYPES, GAUGE OF
 PANELS, ETC.
  
 4) COMMENT FROM THE LAST REVIEW IS NOT ADDRESSED. WITH
 THE STORM PANELS IN PLACE, HOW WILL THE CONDENSING
 UNITS DISSIPATE THE HEAT IF WITHIN THE ENCLOSED ROOM?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 11:11 Sent To  
Notes
2017-06-22 13:18:42BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 22/2016
 ACTION: DENIED
  
 1) THE SUBMITTED COOLER/ FREEZER PLANS DO NOT HAVE
 APPROVAL FOR THE EXTERIOR OF THE BUILDING. IF SO PLEASE
 SUBMIT STATE APPROVAL. THIS HAS BEEN VERIFIED BY THE
 MECHANICAL PLAN REVIEWER THIS MANUFACTURER HAS NO STATE
 APPROVAL FOR THE COOLER/ FREEZER UNITS FOR EXTERNAL
 USE. PLEASE NOTE THE S2 & S3 SHEETS DO NOT PROVIDE
 ENOUGH DETAILS. SHEET S2 HAS A CUT SECTION 9/S3 SHOWN
 FOR BOTH THE EAST AND WEST ELEVATIONS SHOWING THE WALLS
 ENCLOSED AND BENEATH THE ROOF STRUCTURE, AND 2 LAYERS
 OF BOARD ON BOARD SCREEN WALL.
 IT WOULD APPEAR THERE ARE NO OPENINGS TO ENTER THIS
 MECHANICAL ROOM. I?VE GONE TO THE APPROVE PLANS FOR
 VERIFICATION OF WHAT WAS APPROVED. SHEET A001.1 SHOWS
 THE WEST FACE OF THE STRUCTURE IS TO BE 5 FT. -1 IN.
 FROM THE PROPERTY LINE. SHEET A008 SHOWS THE EAST,
 NORTH AND WEST ELEVATIONS OF THIS AREA. THE EAST WALL
 DOES SHOW AN OPENING AS LARGE AS A GARAGE DOOR. THE
 NORTH WALL NO OPENINGS, AND THE WEST WALL AS OPEN. THIS
 IS A CODE VIOLATION; THE PLANS SHOULD NOT HAVE BEEN
 ISSUED WITH THE WEST FACE OPEN. SINCE THE STRUCTURE IS
 5 FT. 1 INCH FROM THE PROPERTY LINE THIS WALL SHOULD BE
 1 HOUR RATED. THIS IS PROTECT THIS PROPERTY AS WELL AS
 THE NEIGHBORING PROPERTY FROM FIRE, SEE 2014 FBC-B
 TABLE 602 FOR ALL BUILDING TYPES AND OCCUPANCIES.
  
 THE OTHER ISSUE THAT WOULD NEED TO BE ADDRESSED SINCE
 THE PLANS DO NOT STATE IF THIS STRUCTURE IS DESIGNED AS
 AN ENCLOSED OR PARTIALLY ENCLOSED STRUCTURE. SHEET S1
 INDICATES THE MAIN BUILDING TO BE DESIGNED AS AN
 ENCLOSED STRUCTURE. 2014 FBC-B 1603.1.4 WIND DESIGN
 DATA. (4). APPLICABLE PRESSURE COEFFICIENT. PLEASE NOTE
 IF THE ENCLOSURE IS OPEN OR PARTIALLY OPEN THEN THE
 COOLER/ FREEZERS WILL HAVE TO HAVE BEEN TESTED FOR
 THESE CONDITIONS!!!!!
  
 IF THE DESIGNER ELECTS TO ENCLOSE THE STRUCTURE WITH A
 DOOR SYSTEM THEN AS STATED BY THE MECHANICAL REVIEWER
 AIR CIRCULATION AND VENTING MAYBE A CONCERN IF THE
 CONDENSERS ARE LOCATED WITHIN THIS ENCLOSED SPACE,
 LOUVERS AND NEED TO BE CONSIDERED AND PRODUCT APPROVALS
 . 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: ( C ) WALL LOVERS.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-16 Cont ID  
Sent By pleduc Date 2017-06-16 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 09:59 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-12-07 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 17:25 Rev Time 0.00
Received By jwitmer Date 2017-12-01 Time 13:15 Sent To  
Notes
2017-12-04 13:15:21RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-11-13 Cont ID  
Sent By cpuell Date 2017-11-13 Time 10:05 Rev Time 0.00
Received By cpuell Date 2017-10-30 Time 12:54 Sent To  
Notes
2017-10-31 12:54:58RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-09-01 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-24 Time 13:45 Sent To  
Notes
2017-08-25 13:45:52RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-17 Time 09:16 Sent To  
Notes
2017-07-19 09:16:22RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2017-06-09 Time 12:54 Sent To  
Notes
2017-06-15 06:29:046/15 TO FIRE BOX
  
2017-06-12 12:54:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-28 Cont ID  
Sent By ccole Date 2017-04-28 Time 07:18 Rev Time 0.00
Received By ccole Date 2017-03-31 Time 10:00 Sent To  
Notes
2017-04-04 10:00:32ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-12-06 Cont ID  
Sent By ccole Date 2017-12-06 Time 09:51 Rev Time 0.00
Received By ccole Date 2017-12-06 Time 09:51 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 09:41 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 17:15 Sent To  
Notes
2017-11-13 09:48:265TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 11/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLAN APPROVAL IS CONTINGENT ON THE
 BUILDING PLAN APPROVAL WHICH HAS FAILED DUE TO THE
 DEFICIENCIES CITED IN THE BUILDING PLAN REVIEW
 COMMENTS. PLEASE COMPLY FOR FINAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-09-01 Cont ID  
Sent By ccole Date 2017-09-01 Time 07:50 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 07:49 Sent To  
Notes
2017-09-01 07:55:594TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 9/1/2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 3RD REVIEW COMMENTS STILL EXIST. I HAVE REPRINTED
 THEM BELOW. NO CHANGES HAVE BEEN MADE TO THE PREVIOUSLY
 REVIEWED PLANS.
  
 3RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 7/20/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS STATED IN THE NARRATIVE RESPONSE FROM THE
 CONTRACTOR BEELINE BUILDING CORP. PLEASE REVISE THE
 PLANS TO SHOW THE LOCATIONS OF THE TWO NEW WALL FANS IN
 THE WALKIN COOLER ENCLOSURE, AND SUBMIT THE MIAMI-DADE
 NOA FOR THE FANS WITH SHOP DRAWING APPROVAL STAMP BY
 THE ENGINEER OF RECORD. PLEASE NOTE THAT THE FANS WILL
 REQUIRE MAKEUP AIR OPENING(S) OTHER THAN THE 10'X10'
 OPENING THAT WILL BE SHUTTERED DURING STORMS. REVISE
 THE PLANS TO SHOW THE REQUIRED OPENINGS AND HOW THEY
 WILL BE PROTECTED.
  
 2) PROVIDE FAN EQUIPMENT SCHEDULES ON THE PLAN, AND
 REVISE THE ELECTRICAL PLANS.
  
 3) PLEASE NOTE THAT MECHANICAL APPROVAL IS CONTINGENT
 ON BUILDING APPROVAL OF THE ENCLOSURE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-20 Cont ID  
Sent By ccole Date 2017-07-20 Time 16:46 Rev Time 0.00
Received By ccole Date 2017-07-20 Time 16:45 Sent To  
Notes
2017-07-20 17:02:593RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 7/20/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS STATED IN THE NARRATIVE RESPONSE FROM THE
 CONTRACTOR BEELINE BUILDING CORP. PLEASE REVISE THE
 PLANS TO SHOW THE LOCATIONS OF THE TWO NEW WALL FANS IN
 THE WALKIN COOLER ENCLOSURE, AND SUBMIT THE MIAMI-DADE
 NOA FOR THE FANS WITH SHOP DRAWING APPROVAL STAMP BY
 THE ENGINEER OF RECORD. PLEASE NOTE THAT THE FANS WILL
 REQUIRE MAKEUP AIR OPENING(S) OTHER THAN THE 10'X10'
 OPENING THAT WILL BE SHUTTERED DURING STORMS. REVISE
 THE PLANS TO SHOW THE REQUIRED OPENINGS AND HOW THEY
 WILL BE PROTECTED.
  
 2) PROVIDE FAN EQUIPMENT SCHEDULES ON THE PLAN, AND
 REVISE THE ELECTRICAL PLANS.
  
 3) PLEASE NOTE THAT MECHANICAL APPROVAL IS CONTINGENT
 ON BUILDING APPROVAL OF THE ENCLOSURE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-13 Cont ID  
Sent By ccole Date 2017-06-13 Time 13:46 Rev Time 0.00
Received By ccole Date 2017-06-13 Time 13:46 Sent To  
Notes
2017-06-13 14:00:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 6/13/17
  
 1) THE NEW REMOTE "OUTDOOR CONDENSING UNITS" CANNOT BE
 INSTALLED IN AN ENCLOSED BUILDING UNLESS THE
 MANUFACTURER'S CERTIFIES THE INSTALLATION WITH
 SPECIFICATIONS AND INSTRUCTIONS. AT A MINIMUM
 VENTILATION IN SOME MANNER WOULD HAVE TO BE PROVIDED,
 HOWEVER NO VENTILATION SYSTEMS ARE SHOWN ON THE PLANS.
 LOOKING AT THE STRUCTURAL DRAWINGS, IT APPEARS TO BE
 COMPLETELY ENCLOSED
 WITH NO OPENINGS, INCLUDING NO ENTRY DOOR WHICH IS ALSO
 PUZZLING.
  
 2) ME-2, NOTE #06: CONDENSATE SHALL NOT DRAIN INTO THE
 CITY SANITARY SYSTEM PER SECTION 90-126 WPB CODE OF
 ORDINANCES. CLARIFY IF THE HUB DRAIN IS CONNECTED TO A
 STORM DRAIN OR THE SANITARY.
  
 3) TWO STRUCTURAL PLAN SHEETS HAVE BEEN SUBMITTED FOR
 THE NEW BUILDING ADDITION- SHEETS S2 & S3. IS THERE AN
 S1 COVER SHEET THAT WAS NOT SUBMITTED? THERE IS NO CODE
 DATA OR WIND LOAD DESIGN CRITERIA PROVIDED ON THE TWO
 SUBMITTED SHEETS.
  
 4) SHEET S2: THE PLAN APPEARS TO SHOW THE WALK-IN BOXES
 VIRTUALLY FLUSH WITH THE ADDITION WALLS. HOW WILL
 ACCESS BE PROVIDED FOR CLEANING AND MAINTENANCE?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-28 Cont ID  
Sent By ccole Date 2017-04-28 Time 07:18 Rev Time 0.00
Received By ccole Date 2017-04-27 Time 17:16 Sent To  
Notes
2017-04-28 07:51:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 4/28/17
  
 1) THE PERMIT APPLICATION INDICATES INSTALLATION OF 3
 WALK-IN COOLERS ON THE INTERIOR AND 1 EXTERIOR WALK-IN
 COOLER/FREEZER COMBO UNIT, HOWEVER THERE ARE ONLY SPECS
 SUBMITTED FOR 1 INTERIOR AND 1 EXTERIOR UNIT- PLEASE
 PROVIDE A COMPLETE SUBMITTAL PACKAGE THAT INCLUDES
 SPECS FOR ALL THE WALK-IN BOXES.
  
 2) SUBMIT A FLORIDA PRODUCT APPROVAL FOR THE
 AMERIKOOLER EXTERIOR WALK-IN BOX, OR PROVIDE
 DOCUMENTATION INDICATING THAT THE UNIT HAS FLORIDA
 APPROVAL AS A MANUFACTURED BUILDING- SEE FAC RULE 9N-B.
 IN LIEU OF ANY DOCUMENTATION OF APPROVAL BY EITHER
 FLORIDA AGENCY, COMPLETE ENGINEERING CERIFICATION BY A
 THIRD-PARTY AGENCY WILL HAVE TO PROVIDED.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR WALK-IN BOX- SECTION 301.15.
  
 4) PROVIDE REFRIGERATION PLANS FOR THE WALK-IN BOXES
 INCLUDING EQUIPMENT SCHEDULES THAT INDICATE MAKES AND
 MODELS OF CONDENSERS AND EVAPORATORS, PIPING DETAILS
 AND PIPING RUNS, AND LOCATIONS OF EQUIPMENT. PLEASE
 NOTE THAT WIND LOAD ENGINEERING IS REQUIRED FOR
 INSTALLATION OF EXTERIOR CONDENSERS- SECTION 301.15.
  
 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE
 EVAPORATORS THAT INCLUDES THE TRYPES AND SIZES OF
 CONDENSATE PIPING, PIPING RUNS AND DISCHARGE LOCATIONS-
 SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-04-19 Cont ID  
Sent By   Date 2017-04-19 Time   Rev Time 0.00
Received By kmartin Date 2017-04-19 Time 11:46 Sent To M
Notes
2017-04-06 14:07:32ROUTED TO KEVIN MARTIN