Plan Review Details - Permit 17031196
Plan Review Stops For Permit 17031196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-05 Cont ID  
Sent By jwitmer Date 2017-05-05 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2017-05-05 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-04 Cont ID  
Sent By jwitmer Date 2017-04-04 Time 10:02 Rev Time 0.00
Received By jwitmer Date 2017-04-04 Time 07:15 Sent To  
Notes
2017-04-04 10:02:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17031196
 ADD: 101 N. CLEMATIS ST. SUITE # 510
 CONT: COUNIHAN CONSTRUCTION LLC
 TEL: 561-722-6266
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 04/2017
 ACTION: DENIED
  
 1) THE PLANS SHEET A-1 SHOW TWO UNITS BEING UNIFIED.
 PLEASE NOTE THIS BUILDING IS A CONDOMINIUM AND WILL
 NEED TO HAVE A UNITY OF TITLE FOR THE TWO UNITS.
  
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
 2) THE SHEET A-1 DOES NOT DECLARE THE MINIMUM BUILDING
 TYPE FOR THE 5 STORY MIXED USE BUILDING. PLEASE DECLARE
 THE MINIMUM BUILDING TYPE OF CONSTRUCTION TYPE FOR THIS
 BUILDING, IT WILL AFFECT THE COMMENTS IN THIS REVIEW.
 2014 FBC-B TABLE 503.
  
 3) SHEET A1 SHOWS THE REMOVAL OF THE STAIRS ON THE LEFT
 SIDE OF THE TENANT SPACE THAT LEAD TO THE MEZZANINE AND
 RELOCATING A COLUMN. SHEET A2 SECTION 1 AND PARTIAL
 FRAMING PLAN @ STAIR INFILL BOTH INDICATE STEEL COLUMNS
 THE REMOVAL AND RELOCATING OF (2) STEEL COLUMNS BUT
 THERE IS NO MENTION OF WHERE THESE COLUMNS ARE GOING TO
 BE RE-INSTALLED, NOR WAS THE FLOOR LOADING FOR THE NEW
 CONCENTRATED LOADS FIGURED INTO THE EXISTING FLOOR
 BENEATH THE MEZZANINE? 2014 FBC-B TABLE 1607.1 & 1607.4
 CONCENTRATED LIVE LOADS.
  
 4) SHEET A2 SECTION -1 SHOWS COLUMNS AND CONNECTIONS TO
 STEEL BOX BEAMS, THERE IS NO DETAIL AS TO HOW THE STEEL
 BOX BEAM WILL BE SECURED TO THE COLUMN BELOW? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6) SHEET A-2 SHOWS A SECTION OR ELEVATION OF THE
 INTERIOR OF THE UNIT, PLEASE PROVIDE THE VERTICAL
 DIMENSION FROM FINISH FLOOR TO THE CEILING FOR BOTH THE
 FIRST FLOOR LEVEL AND THE MEZZANINE LEVEL? SHOW
 COMPLIANCE WITH FBC-B 1208.2 MINIMUM CEILING HEIGHTS.
  
 7) THE SUBMITTED PRODUCT APPROVALS FOR THE FLOOR
 INSULATION CANNOT BE REVIEWED UNTIL THE MINIMUM
 BUILDING TYPE HAS BEEN DECLARED. FBC-B-2014 720.2
 CONCEALED INSTALLATION.
  
 8) SHEET A-2 SECTION-1 SHOWS THE USE OF ? INCH PLYWOOD
 AS A SUBFLOORING. CODE COMPLIANCE CANNOT BE DETERMINED
 UNTIL THE MINIMUM BUILDING TYPE HAS BEEN DECLARED.
 FBC-B 603.1 ALLOWABLE COMBUSTIBLE MATERIALS.
  
 9) SHEET A2 SECTION-1 SHOWS THE USE OF GALVANIZED METAL
 FORM DECK AND STRUCTURAL STEEL METAL JOIST BELOW, BUT
 THERE IS NO INFORMATION AS TO HOW THE METAL DECK IS TO
 BE ANCHORED TO THE METAL STEEL JOIST. FBC-B 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) SHEET A2 SECTION-1 INDICATES THE USE OF (3) # 12 X
 1 INCH TEC SCREWS AT CONNECTIONS, IS THIS FOR THE FLOOR
 JOIST AND OR THE STEEL TS6X31/4 COLUMN? FBC-B 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11A) SHEET A2 THE BUILDING SECTION THAT SHOWS THE NEW
 GUARDRAIL SYSTEM DOES NOT PROVIDE ANY INFORMATION IN
 COMPLYING WITH FBC-B 2407.1, 2407.1.1 NOR 2407.1.2.
  
 11B) SHEET A2 THE BUILDING SECTION DOES NOT INDICATE
 HOW THE NEW GUARDRAIL SYSTEM IS TO BE ANCHORED TO THE
 MEZZANINE SLAB/ FRAMING MEMBERS? SHOW COMPLIANCE WITH :
  
 11B(1) FBC-B 1 607.8.1 HANDRAILS AND GUARDS. HANDRAILS
 AND GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF
 50 POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES AND
 GUARDS SHALL ALSO COMPLY WITH SECTION 2407.
  
 11B)(2) 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND
 GUARDS SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED
 LOAD OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF
 ASCE 7.
  
 11C) TO BE DETERMINED BY THE BUILDING OFFICIAL FOR
 FINAL CODE INTERPRETATION. SHEET A2 SHOWS THE GUARDRAIL
 HEIGHT TO BE 36 INCHES IN HEIGHT.
 THE 2014 FBC-B 1013.3 HEIGHT.
 REQUIRED GUARDS SHALL NOT BE LESS THAN 42 INCHES (1067
 MM) HIGH, MEASURED VERTICALLY AS FOLLOWS:
 EXCEPTIONS:
  
 1. FOR OCCUPANCIES IN GROUP R-3 NOT MORE THAN THREE
 STORIES ABOVE GRADE IN HEIGHT AND WITHIN INDIVIDUAL
 DWELLING UNITS IN OCCUPANCIES IN GROUP R-2 NOT MORE
 THAN THREE STORIES ABOVE GRADE IN HEIGHT WITH SEPARATE
 MEANS OF EGRESS, REQUIRED GUARDS SHALL NOT BE LESS THAN
 36 INCHES (914 MM) IN HEIGHT MEASURED VERTICALLY ABOVE
 THE ADJACENT WALKING SURFACES OR ADJACENT FIXED
 SEATING.
  
 11D) SHEET A2 THE BUILDING SECTION INDICATES THE
 INSTALLATION OF A NEW GUARDRAIL ON THE MEZZANINE LEVEL
 BUT THE PLANS ARE SILENT AS TO IF THE GUARDRAIL/
 HANDRAIL SYSTEM ON THE STAIRS WILL ALSO BE REPLACED?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 12) SHEET A1 INDICATES ON THE LOFT CEILING PLAN THE USE
 OF 1 I/2 INCH HIGH HAT CHANNELS @ 48 INCHES MAX ON
 CENTER. PLEASE PROVIDE COMPLIANCE WITH EITHER GA-216 OR
 ASTM C 840 GYPSUM BOARD INSULATION WHERE EITHER OF
 THESE STANDARDS ALLOWS CEILING FRAMING MEMBER @ 48
 INCHES ON CENTER FOR ? INCH GYPSUM. FBC-B 2508.1 &
 TABLE 2508.1.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By jleahy Date 2017-05-08 Time 14:37 Rev Time 0.00
Received By jleahy Date 2017-05-08 Time 14:34 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By rlecky Date 2017-04-04 Time 13:38 Rev Time 0.00
Received By rlecky Date 2017-04-04 Time 13:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By scaldero Date 2017-04-27 Time 11:04 Rev Time 0.00
Received By scaldero Date 2017-04-27 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By scaldero Date 2017-04-04 Time 10:36 Rev Time 0.00
Received By scaldero Date 2017-04-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-08 Cont ID  
Sent By jleahy Date 2017-05-08 Time 14:45 Rev Time 0.00
Received By jleahy Date 2017-04-24 Time 10:13 Sent To  
Notes
2017-04-25 10:13:33B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 11:45 Rev Time 0.00
Received By tklarge Date 2017-03-30 Time 16:04 Sent To  
Notes
2017-03-31 16:04:28B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-04-04 Cont ID  
Sent By jwitmer Date 2017-04-04 Time 10:02 Rev Time 0.00
Received By jwitmer Date 2017-04-04 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-01 Cont ID  
Sent By ccole Date 2017-05-01 Time 14:31 Rev Time 0.00
Received By ccole Date 2017-05-01 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-04-07 Time 10:46 Rev Time 0.00
Received By ccole Date 2017-04-07 Time 10:43 Sent To  
Notes
2017-04-07 10:56:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031196
 4/7/17
  
 1) SHEET A-1: THE SCOPE OF WORK #6 INDICATES AC GRILLES
 TO BE DROPPED. PLEASE SHOW THE LOCATIONS OF THE GRILLS
 ON THE PLAN AND INDICATE IF DUCT EXTENSIONS OR
 RELOCATIONS WILL BE REQUIRED.
  
 2) IT APPEARS NEW BATH EXHAUST FANS ARE TO BE
 INSTALLED. PLEASE INCLUDE THE FANS IN THE SCOPE OF WORK
 AND PROVIDE EQUIPMENT SCHEDULES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By gjohnson Date 2017-05-08 Time 09:19 Rev Time 0.00
Received By gjohnson Date 2017-05-08 Time 08:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 11:44 Rev Time 0.00
Received By tklarge Date 2017-04-21 Time 11:33 Sent To  
Notes
***NONE***