Plan Review Details - Permit 17031143
Plan Review Stops For Permit 17031143
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-21 Cont ID  
Sent By wjolin Date 2017-06-21 Time 14:21 Rev Time 0.00
Received By wjolin Date 2017-06-21 Time 14:21 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By wjolin Date 2017-05-11 Time 09:37 Rev Time 0.00
Received By wjolin Date 2017-05-11 Time 09:27 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By wjolin Date 2017-04-12 Time 15:10 Rev Time 0.00
Received By wjolin Date 2017-04-06 Time 11:26 Sent To M
Notes
2017-04-06 11:28:43410 DATURA STREET
 PERMIT #17031143
 MASTER #16020194
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IF ED SNIDER (PE #71374) IS TO BE THE SUCCESSOR FIRE
 PROTECTION ENGINEER OF RECORD THEN THE FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FROM THE MASTER PERMIT
 (#16020194) NEED TO REFLECT THIS CHANGE IN LIEU OF
 ATTEMPTING THIS CHANGE ON THE FIRE SPRINKLER SUB-PERMIT
 SHOP DRAWINGS (#17031143).
  
 SHEET FP1.0: PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 SHEET FP3.0: THE SCHEDULE INDICATES THE FIRE PUMP
 HORSEPOWER TO BE 40 HP; HOWEVER, THE SPECIFICATIONS
 INDICATE 25 HP. PLEASE INDICATE THE CORRECT HP.
  
 SHEET FP6.6: NO SPRINKLER PROTECTION FOR PARKING GARAGE
 TENANT STORAGE.
  
 SHEET FP7.1B: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.1C: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.2A: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE THIRD FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.5D: HYDRAULIC DESIGN D (UNIT TYPE A1)
 SPRINKLER LAYOUT DOES NOT MATCH THE SPRINKLER LAYOUT
 FOR UNIT TYPE A1 AS SHOWN ON SHEET FP5.0.
  
 SHEET FP7.5D: DESIGN AREA D HYDRAULICALLY CALCULATES
 SPRINKLERS CLOSEST TO THE CROSSMAIN IN LIEU OF
 CALCULATING SPRINKLERS THAT ARE MORE REMOTE OR MORE
 HYDRAULICALLY DEMANDING. FOR EXAMPLE, RECESSED PENDENT
 (SIN R3516) IS INDICATED AS PROTECTING 20'X20' AND THE
 LISTING REQUIRES 20 GPM; HOWEVER, THE GREATEST FLOW IN
 THE CALCULATION IS ONLY 18 GPM. IF 4 SPRINKLERS ON THE
 REMOTE PORTION OF THE BRANCHLINE ARE CALCULATED, DOES
 THIS RESULT IN A GREATER PRESSURE DEMAND DUE TO THE
 FRICTION LOSS ASSOCIATED WITH THE 28 FEET OF 3/4"
 PIPING PLUS FITTINGS?
  
 SHEET FP8.0: STANDARD SPRAY SPRINKLERS IN THE LOUNGE
 ARE LOCATED MORE THAN 15 FEET APART.
  
 SHEET FP8.1 & 8.2: THE DRAWING SCALE IS INDICATED AS
 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE IS 1/4"=1'-0".
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-06-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-15 Time 14:34 Sent To  
Notes
2017-06-16 14:35:00RESUB ROUTED TO FIRE DESK AREA - WOULDN'T FIT IN FIRE
 BIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-12 Cont ID  
Sent By ccole Date 2017-05-12 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-05-09 Time 10:06 Sent To  
Notes
2017-05-10 10:07:13RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By ccole Date 2017-04-12 Time 17:20 Rev Time 0.00
Received By ccole Date 2017-03-29 Time 13:26 Sent To  
Notes
2017-03-30 13:26:24ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-22 Cont ID  
Sent By ccole Date 2017-06-22 Time 15:49 Rev Time 0.00
Received By ccole Date 2017-06-22 Time 15:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-23 Cont ID  
Sent By ccole Date 2017-05-12 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-05-12 Time 08:46 Sent To  
Notes
2017-05-23 08:05:362ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17031143
 5/23/17
  
 RESULTS: DENIED.
  
 1) SHEET FP8.3 WAS NOT RESUBMITTED WITH THE CORRECTED
 PLAN SETS- PLEASE PROVIDE THE SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By ccole Date 2017-04-12 Time 17:09 Rev Time 0.00
Received By ccole Date 2017-04-12 Time 16:40 Sent To  
Notes
2017-04-12 17:18:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031143
 4/12/17
  
 1) SUBMITTAL DOCUMENTS INCLUDING HYDRAULIC CALCULATIONS
 AND FIRE SPRINKLER PRODUCT SPECIFICATIONS SHALL BE
 SUBMITTED IN TWO OR MORE SETS IN ACCORDANCE WITH
 SECTION 107.1 WPB AMENDMENTS TO THE FBC. THREE SETS OF
 PLANS AND CONSTRUCTION DOCUMENTS ARE REQUIRED FOR
 THRESHOLD BUILDINGS.
  
 2) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 BACKFLOW PREVENTER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  