Plan Review Details - Permit 17031136
Plan Review Stops For Permit 17031136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 12:38 Rev Time 0.00
Received By shill Date 2017-05-15 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By shill Date 2017-04-04 Time 14:48 Rev Time 0.00
Received By shill Date 2017-04-04 Time 14:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 11:21 Rev Time 0.00
Received By jleahy Date 2017-05-18 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-19 Cont ID  
Sent By vperez Date 2017-04-19 Time 10:58 Rev Time 0.00
Received By vperez Date 2017-04-19 Time 10:58 Sent To  
Notes
2017-04-19 10:58:52PLEASE ADDRESS MECHANICAL FOR AN ELECTRICAL APPROVAL.
 FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-05 Cont ID  
Sent By pleduc Date 2017-05-05 Time   Rev Time 0.00
Received By pleduc Date 2017-05-05 Time 12:42 Sent To  
Notes
2017-05-05 13:10:212ND REVIEW COMMENTS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1)
 SHEET 1.1 - THERE IS NO INDICATION OF A FIRE CODE
 REFERENCE AND/OR COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 2)
 SHEET 1.1 - THERE ARE INDICATIONS OF WALLS THAT ARE
 BEING REMOVED AND NEW WALLS INSTALLED (OR A RAISED
 CEILING).
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE WITH:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By pleduc Date 2017-04-04 Time   Rev Time 0.00
Received By pleduc Date 2017-04-03 Time 11:29 Sent To  
Notes
2017-04-04 11:12:46PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1)
 SHEET 1.1 - THERE IS NO INDICATION OF A FIRE CODE
 REFERENCE AND/OR COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 2)
 SHEET 1.1 - THERE ARE INDICATIONS OF WALLS THAT ARE
 BEING REMOVED AND NEW WALLS INSTALLED (OR A RAISED
 CEILING).
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE WITH:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 11:22 Rev Time 0.00
Received By jleahy Date 2017-05-04 Time 16:03 Sent To  
Notes
2017-05-04 16:03:45B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 12:54 Rev Time 0.00
Received By gjohnson Date 2017-03-29 Time 10:21 Sent To  
Notes
2017-03-31 10:21:32B15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 17:33 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 17:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-04-07 Time 10:09 Rev Time 0.00
Received By ccole Date 2017-04-07 Time 10:09 Sent To  
Notes
2017-04-07 10:23:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031136
 4/7/17
  
 1) SHEET 2.1: THE LEGEND INDICATES A 50 CFM KITCHEN
 EXHAUST FAN THAT IS NOT SHOWN ON THE PLAN. PLEASE NOTE
 THAT A MINIMUM 100 CFMS IS REQUIRED PER TABLE 403.3 IF
 THE EXHAUST IS OPERATED INTERMITTENTLY.
  
 2) SHOW THE LOCATIONS OF THE COOKTOP EXHAUST FAN AND
 EXHAUST DUCT AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SEE SECTION 505.2.
  
 3) PROVIDE THE CFMS AT EACH NEW SUPPLY DIFFUSER.
  
 4) PROVIDE EXHAUST FOR THE NEW DRYER. SHOW THE TYPE AND
 SIZE OF EXHAUST DUCT, THE DUCT RUN AND TERMINATION
 LOCATION, OR THE POINT OF CONNECTION TO THE EXISTING
 EXHAUST RISER. ADVISORY: EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR RUN THROUGH PLENUMS- SECTION 504.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-12 Cont ID  
Sent By gjohnson Date 2017-05-12 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2017-05-12 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 12:31 Rev Time 0.00
Received By gjohnson Date 2017-04-21 Time 12:18 Sent To  
Notes
2017-04-21 12:53:111ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE RISER DIAGRAM FOR NEW WASHING MACHINE . PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. WASHING MACHINE BRANCH DRAIN SHALL BE MIN OF 3" PER
 FBC PL 406.2
  
 3. THE WASHING MACHINE DRAIN SHALL NOT TIE INTO THE WET
 VENT OF THE BATHROOM GROUP, IT SHALL TIE IN DOWN STREAM
 OF BATHROOM GROUP. PER FBC PL 912.1
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  