Plan Review Details - Permit 17031134
Plan Review Stops For Permit 17031134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-06 Cont ID  
Sent By jwitmer Date 2017-05-06 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2017-05-06 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By jwitmer Date 2017-04-05 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2017-04-05 Time 07:30 Sent To  
Notes
2017-04-05 08:08:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17031134
 ADD: 529 S. FLAGLER DR. SUITE # 6F
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 05/ 2017
 ACTION: DENIED
  
 1) ALBRIGHT LETTER FOR THE SCOPE OF WORK ON PAGE NUMBER
 2 UNDER THE HEADING GENERAL LIST THE REPLACEMENT OF
 EXTERIOR WINDOWS AND DOORS. THE COVER SHEET PROVIDES
 THE WIND DESIGN CRITERIA AND SHEET # 1 SHOWS THE
 OPENINGS IDENTIFIED AS OPENINGS 1-5. THE COVER SHEET
 UNDER THE HEADING WIND DESIGN DATA STATES THAT THE WIND
 PRESSURES ARE TO BE CALCULATED BY DANIEL J. MOSS P. E.
 SIGNED & SEALED LETTER TO BE STAPLED TO PLAN SETS. IN
 THIS SUBMITTAL NO SUCH LETTER WAS SUBMITTED IN THE
 PERMIT PACKAGE DOCUMENTS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) COMPONENTS & CLADDING. 2010/ 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS.
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) THE PLANS SHEET # 1 INDICATES THE USE OF SUPER SAM
 125 FLOOR UNDERLAYMENT/ INSULATION. THE DOCUMENT
 SUBMITTED IS A SALES BROCHURE NOT THE ACTUAL TEST DATA.
 NOTE THE TEST SHOULD SHOW IT IS FOR A 6 INCH CONCRETE
 SLAB AND NO DROP CEILING. THE SOUND TEST ALSO NEEDS TO
 DECLARE IF THE FINISH FLOOR MATERIAL IS MARBLE, TILE
 AND OR WOOD, OR WOOD LAMINATE, MUST BE SPECIFIC TO THE
 FINISH FLOOR MATERIAL.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By rlecky Date 2017-04-04 Time 14:49 Rev Time 0.00
Received By rlecky Date 2017-04-04 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 09:17 Sent To  
Notes
2017-04-28 12:49:142ND REVIEW
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1)
 SHEET 00 - THERE IS NO INDICATION OF A FIRE CODE
 REFERENCE AND/OR COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 2)
 SHEET 1 - THERE ARE INDICATIONS OF WALLS THAT ARE BEING
 REMOVED AND NEW WALLS INSTALLED.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE WITH:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-04 Cont ID  
Sent By pleduc Date 2017-04-04 Time   Rev Time 0.00
Received By pleduc Date 2017-04-03 Time 11:30 Sent To  
Notes
2017-04-04 10:51:09PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1)
 SHEET 00 - THERE IS NO INDICATION OF A FIRE CODE
 REFERENCE AND/OR COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 2)
 SHEET 1 - THERE ARE INDICATIONS OF WALLS THAT ARE BEING
 REMOVED AND NEW WALLS INSTALLED.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE WITH:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-08 Cont ID  
Sent By gjohnson Date 2017-05-08 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2017-04-25 Time 14:27 Sent To  
Notes
2017-04-26 14:27:17B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 14:09 Rev Time 0.00
Received By gjohnson Date 2017-03-29 Time 10:27 Sent To  
Notes
2017-03-31 10:27:28B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-04-05 Cont ID  
Sent By jwitmer Date 2017-04-05 Time 07:36 Rev Time  
Received By jwitmer Date 2017-04-05 Time 07:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By gjohnson Date 2017-05-08 Time 13:26 Rev Time 0.00
Received By gjohnson Date 2017-05-08 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2017-04-21 Time 12:17 Sent To  
Notes
***NONE***