| 2017-04-04 12:25:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE SUBMITTED CONSTRUCTION PLAN UNDER SCOPE OF WORK, |
| | 1) INDICATES REMOVE (1) ADDRESSIBLE PULL STATION |
| | LOCATED IN OPEN LOBBY. |
| | |
| | THERE IS NOTHING INDICATED ON THE FLOOR PLAN LAYOUT |
| | RELATING TO A PULL STATION. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 2) THE PROPOSED REMOVAL OF A PULL STATION MAY BE A CODE |
| | VIOLATION OF FLORIDA FIRE PREVENTION CODE AND NFPA 72. |
| | |
| | PULL STATIONS ARE REQUIRED WITHIN 5' OF THE EXIT DOOR. |
| | |
| | 17.14.5 MANUAL FIRE ALARM BOXES SHALL BE INSTALLED SO |
| | THAT THEY ARE CONSPICUOUS, UNOBSTRUCTED, AND |
| | ACCESSIBLE. |
| | 17.14.6 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN |
| | 60 IN. (1.52 M) OF THE EXIT DOORWAY OPENING AT EACH |
| | EXIT ON EACH FLOOR. |
| | 17.14.7 MANUAL FIRE ALARM BOXES SHALL BE MOUNTED ON |
| | BOTH SIDES OF GROUPED OPENINGS OVER 40 FT (12.2 M) IN |
| | WIDTH, AND WITHIN 60 IN. (1.52 M) OF EACH SIDE OF THE |
| | OPENING. |
| | 17.14.8* ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE |
| | PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST |
| | FIRE ALARM BOX WILL NOT BE IN EXCESS OF 200 FT (61.0 |
| | M), MEASURED HORIZONTALLY ON THE SAME FLOOR. |
| | |
| | PLEASE PROVIDE THE JUSTIFICATION FOR THE REMOVAL OF THE |
| | PULL STATION AND FIRE CODE REFERENCE ALLOWING IT TO BE |
| | REMOVED. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |