Plan Review Details - Permit 17031088
Plan Review Stops For Permit 17031088
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-03 Cont ID  
Sent By cthroop Date 2017-07-03 Time 08:12 Rev Time 0.00
Received By cthroop Date 2017-07-03 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By cthroop Date 2017-04-12 Time 17:00 Rev Time 0.00
Received By cthroop Date 2017-04-12 Time 16:36 Sent To  
Notes
2017-04-12 17:08:07BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE SITE PLAN WITH THE FOLLOWING: LOCATION OF
 EXISTING POLE TO BE RE-LOCATED. LOCATION OF RE-LOCATED
 POLES. LOCATION OF NEW POLOES.
 2. PROVIDE SHOP DRAWINGS/SPECIFICATIONS OF POLES.
 3. PROVIDE FOUNDATION DETAIL FOR EACH TYPE OF POLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By jleahy Date 2017-06-27 Time 15:42 Rev Time 0.00
Received By jleahy Date 2017-06-27 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-04 Cont ID  
Sent By jleahy Date 2017-04-04 Time 08:13 Rev Time 0.00
Received By jleahy Date 2017-04-04 Time 08:13 Sent To  
Notes
2017-04-04 08:30:41FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 C405.6 EXTERIOR LIGHTING (MANDATORY). WHERE THE POWER
 FOR EXTERIOR LIGHTING IS SUPPLIED THROUGH THE ENERGY
 SERVICE TO THE BUILDING, ALL EXTERIOR LIGHTING, OTHER
 THAN LOW-VOLTAGE LANDSCAPE LIGHTING, SHALL COMPLY WITH
 SECTIONS C405.6.1 AND C405.6.2.
  
 C405.6.2 EXTERIOR BUILDING LIGHTING POWER. THE TOTAL
 EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL EXTERIOR
 BUILDING APPLICATIONS IS THE SUM OF THE BASE SITE
 ALLOWANCE PLUS THE INDIVIDUAL ALLOWANCES FOR AREAS THAT
 ARE TO BE ILLUMINATED AND ARE PERMITTED IN TABLE
 C405.6.2(2) FOR THE APPLICABLE LIGHTING ZONE. TRADEOFFS
 ARE ALLOWED ONLY AMONG EXTERIOR LIGHTING APPLICATIONS
 LISTED IN TABLE C405.6.2(2), TRADABLE SURFACES SECTION.
 THE LIGHTING ZONE FOR THE BUILDING EXTERIOR IS
 DETERMINED FROM TABLE C405.6.2(1) UNLESS OTHERWISE
 SPECIFIED BY THE LOCAL JURISDICTION. EXTERIOR LIGHTING
 FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN THE
 EXCEPTIONS TO SECTION C405.6.2) SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION C405.6.1.
  
 PROVIDE CUT SHEETS FOR POLES AND FIXTURES, TIME CLOCK
 AND/OR PHOTOCELL.
  
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-03 Cont ID  
Sent By cthroop Date 2017-07-03 Time 08:11 Rev Time 0.00
Received By cthroop Date 2017-06-22 Time 12:49 Sent To  
Notes
2017-06-23 12:49:29RESUB ROUTED TO LLOUIE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By cthroop Date 2017-04-12 Time 17:00 Rev Time 0.00
Received By cthroop Date 2017-03-29 Time 09:52 Sent To  
Notes
2017-03-30 09:52:40ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-06-27 Cont ID  
Sent By llouie Date 2017-06-27 Time 10:24 Rev Time 0.00
Received By llouie Date 2017-06-27 Time 10:24 Sent To  
Notes
2017-06-27 10:24:47SPOKE TO AVANN. PER AVANN, MINOR PD AMENDMENT NOT
 REQUIRED.

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-26 Cont ID  
Sent By llouie Date 2017-06-26 Time   Rev Time 0.00
Received By llouie Date 2017-06-26 Time   Sent To  
Notes
2017-06-26 08:25:02** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY SHOWING THE LOCATION OF
 THE EXISTING FIXTURES. [REPEAT COMMENT FROM 4/3/17]
  
 2.) SCOPE SEEMS TO INDICATE THE ADDITION AND RELOCATION
 OF EXISTING FIXTURES. ANY MODIFICATION TO THE APPROVED
 SITE PLAN REQUIRES AN APPLICATION FOR A MINOR PLANNED
 DEVELOPMENT (PD) AMENDMENT THROUGH THE PLANNING
 DIVISION PRIOR TO BUILDING PERMIT. [REPEAT COMMENT FROM
 4/3/17]
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By llouie Date 2017-04-03 Time   Rev Time 0.00
Received By llouie Date 2017-03-31 Time 09:35 Sent To  
Notes
2017-04-03 08:25:01** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY SHOWING THE LOCATION OF
 THE EXISTING FIXTURES.
  
 2.) HOW TALL ARE THE LIGHT FIXTURES? PROVIDE A DETAIL.
  
 3.) SCOPE SEEMS TO INDICATE THE ADDITION AND RELOCATION
 OF EXISTING FIXTURES. ANY MODIFICATION TO THE APPROVED
 SITE PLAN REQUIRES AN APPLICATION FOR A MINOR PLANNED
 DEVELOPMENT (PD) AMENDMENT THROUGH THE PLANNING
 DIVISION PRIOR TO BUILDING PERMIT.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  
  
  
  
  
2017-03-31 15:05:11ROUTED TO LINDA LOUIE