| Plan Review Stops For Permit 17031082 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-05-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-22 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-19 |
Time |
17:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2017-03-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-31 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-31 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2017-03-31 06:53:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | CONTACT MICHAEL ORIO, 561-494-1080, [email protected] FOR | | | ADDRESSING. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-03-06 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-03-06 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-05-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-22 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-19 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2017-05-22 07:59:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | REVIEW #2 (FIRST RESUBMITTAL) | | | | | | 1. THE PERMIT FOR THE SHELL IS NOT ISSUED. THIS PERMIT | | | CANNOT BE ISSUED UNTIL THE SHELL IS ISSUED (17021163). | | | THIS PERMIT WILL BE ISSUED AT RISK; RESPONSIBILITY FOR | | | A CODE COMPLIANT PROJECT IS ON APPLICANTS FOR THE TWO | | | PERMITS AND THEY ARE TO WORK TOGETHER TO RESOLVE ANY | | | ISSUES. | | | | | | 2ND REVIEW, A LETTER OF ACKNOWLEDGEMENT SIGNED BY BOTH | | | CONTRACTORS WILL BE REQUIRED PRIOR TO PERMIT ISSUANCE. | | | SHELL IS NOT YET ISSUED AT THE TIME OF THIS REVIEW. | | | | | | 2. A CURSORY REVIEW OF THE (ENERGY CALC) INPUT DATA | | | REPORT WAS DONE. CLARIFY THE FOLLOWING: | | | WALLS - 3 SHOWN, IT APPEARS THAT THE FOURTH WALL IS NOT | | | IN THE REPORT | | | WALLS OR WINDOWS - SOME WINDOWS ON THE PLAN ARE TO HAVE | | | DRYWALL INSTALLED ON THE INSIDE. CLARIFY HOW THIS IS | | | HANDLED ON THE PLAN; ARE THESE AREAS ACCOUNTED FOR AS | | | WINDOWS? | | | DOORS - NONE SHOWN; ARE ALL EXTERIOR DOORS GLAZED? ARE | | | THEY INCLUDED IN THE WINDOWS OR FENESTRATION NUMBERS? | | | FENESTRATION - 1 PANE SHOWN; CLARIFY WHAT THIS ITEM IS. | | | ROOF - R19 INSULATION SPECIFIED AND TOTAL R VALUE OF | | | 22.6 - SEE NOTE 7 SHEET A4.0 FOR SHELL PERMIT; NOTE | | | SPECIFIES INSULATION TO ACHIEVE R19, PLEASE CORRELATE | | | (EITHER REVISE THE INPUT DATA REPORT AND ENERGY CALC TO | | | SPEC TOTAL R19 FOR ROOF, OR REVISE SHELL PERMIT TO | | | SPECIFY R19 BOARD). | | | | | | 3. REVISE PLAN TO SHOW INFORMATION REGARDING AMOUNT OF | | | RADIATION AND DESIGN OF WALLS TO SHOW COMPLIANCE WITH | | | ALL REQUIREMENTS OF FBC B 465, FAC 64E-5, FS 404 (AS | | | APPLICABLE). NOT ENOUGH INFORMATION PROVIDED TO | | | DETERMINE CODE COMPLIANCE. | | | | | | 2ND REVIEW, INFORMATION FROM DOH WAS PROVIDED. REVISE | | | PLAN TO STATE AMOUNT OF RADIATION PROPOSED ("<200 KVP" | | | IS ACCEPTABLE IF THAT IS THE CASE) AND REVISE PLAN TO | | | PROVIDE A DETAIL FOR THE LEAD LINED WALLS, OR REVISE W3 | | | AND W5 (SHEET A1) TO CLARIFY LEAD INSTALLATION | | | REQUIREMENTS. DETAILS STATE "LEAD @ X-RAY ROOM" BUT | | | DOES NOT SPECIFY LEAD THICKNESS OR HEIGHT. | | | | | | NEW COMMENT: | | | | | | THE PAGES WHICH WERE REVISED TO ADDRESS COMMENTS FROM | | | FIRST REVIEW ARE NOT SEALED BY THE ARCHITECT. DOCUMENTS | | | PREPARED BY AN ARCHITECT AND SUBMITTED FOR PUBLIC | | | RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS FS481. | | | | | | FOR INSTANCE, SEE A2, I2, I3, CHECK ALL. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-03-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-31 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-31 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2017-03-31 09:40:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE PERMIT FOR THE SHELL IS NOT ISSUED. THIS PERMIT | | | CANNOT BE ISSUED UNTIL THE SHELL IS ISSUED (17021163). | | | THIS PERMIT WILL BE ISSUED AT RISK; RESPONSIBILITY FOR | | | A CODE COMPLIANT PROJECT IS ON APPLICANTS FOR THE TWO | | | PERMITS AND THEY ARE TO WORK TOGETHER TO RESOLVE ANY | | | ISSUES. | | | | | | 2. I WAS UNABLE TO LOCATE THE INPUT DATA REPORT FOR THE | | | ENERGY CALCS, FBC 107. PRIOR TO SUBMITTAL, CONFIRM THAT | | | IT IS COMPLETE (WINDOWS, DOORS, ETC.) AND ACCURATE. | | | | | | 3. REVISE PLAN TO SHOW INFORMATION REGARDING AMOUNT OF | | | RADIATION AND DESIGN OF WALLS TO SHOW COMPLIANCE WITH | | | ALL REQUIREMENTS OF FBC B 465, FAC 64E-5, FS 404 (AS | | | APPLICABLE). NOT ENOUGH INFORMATION PROVIDED TO | | | DETERMINE CODE COMPLIANCE. | | | | | | 4. A2 WATER CLOSET MINIMUM DISTANCE TO WALL IS 18"; | | | REVISE TO COMPLY WITH FBC A 402.2, RANGE IS 16"MIN, 18" | | | MAX. MORE THAN ONE NOTE AFFECTED; REVISE ALL. | | | | | | 5. FBC A 603.2 TURNING SPACE (FBC A 304) REQUIRED. | | | RECTANGLES ARE SHOWN; A CIRCLE OR A T TURNING SPACE IS | | | REQUIRED; REVISE ACCORDINGLY. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-05-31 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-05-31 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-04-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-04-03 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-03-31 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2017-03-31 16:14:29 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | NEED FAULT CURRENT CALCULATION AND LAELING AT SERVICE | | | PER 110.24(A,B) | | | | | | WIRE SIZE FROM MAIN DISCONNECT TO THE GUTTER 215.5 | | | | | | PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED PER | | | 517.13 | | | | | | PLEASE INDICATE THE LIGHTING CONTROL PER FBC ENERGY | | | C405.2.2.2 | | | | | | PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY FBC | | | C401.2 AND ASHREA 8.4.2 | | | | | | | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-02-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-02-26 |
Time |
09:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-05-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-19 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-04-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-04-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-04-04 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-03-06 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-22 |
Time |
11:29 |
Sent To |
I |
|
| Notes |
| 2018-02-23 11:29:31 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-05-31 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-05-16 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-10 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-28 |
Time |
09:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-07 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-07 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-05-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-22 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-22 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2017-05-22 08:45:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE HAVE BEEN PAID (IF APPLICABLE) ARE TO BE | | | PROVIDED | | | 561-233-5025 FOR MORE INFORMATION | | | | | | PERMITS 17031082, 17021163 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-23 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-23 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-04-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-04-03 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-03 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2017-04-03 07:07:43 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17031082 | | | 4/3/17 | | | | | | 1) THE INPUT DATA REPORT IS MISSING FROM THE | | | ENERGYGAUGE COMPLIANCE SUBMITTAL- PLEASE PROVIDE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-24 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-24 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-10 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-04-10 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2017-04-10 12:19:40 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. A-2 GRAB BARS SHALL BE INSTALLED IN A | | | HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36 | | | INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 | | | 2. SHT. A-2 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES | | | (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 MM) | | | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES | | | (1370 MM) MINIMUM FROM THE REAR WALL. PER FBC ACC | | | 604.5.1 | | | 3. SHT. A-2 TOILET PAPER DISPENSERS SHALL COMPLY WITH | | | 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 | | | INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET | | | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET | | | OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM | | | AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR | | | AND SHALL NOT BE LOCATED BEHIND GRAB BARS. PER FBC ACC | | | 604.7 | | | 4. SHT. A-2 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE | | | FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 | | | INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE | | | SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED | | | POSITION. PER FBC ACC 604.4 | | | 5. SHT. A-2 THE WATER CLOSET SHALL BE POSITIONED WITH A | | | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE | | | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES (405 | | | MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE | | | WALL OR PARTITION. PER FBC ACC 604.2 | | | 6. SHT. A-2 SHOW CLEAR FLOOR SPACE FOR DRINKING | | | FOUNTAIN AND BREAK ROOM SINK. PER WPB AMEND TO FBC | | | 107.2.1 | | | 7. AT LEAST ONE OF THE PROCEDURE ROOM SINKS SHALL | | | COMPLY WITH FBC ACC 606 PER FBC ACC 212.3 | | | 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | 9. WATER HAMMER ARRESTERS ARE REQUIRED FOR WASHING | | | MACHINE AND ICE MAKER. PER FBC PL 604.9 | | | 10. A BACK FLOW IS REQUIRED FOR REF ICE MACHINE. PER | | | FBC PL 608.3 | | | | | | | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|