| 2017-03-30 11:58:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. C1 SITE DATA DECLARES THIS AS R1; SEE FBC B 310. |
| | THIS BUILDING WAS PERMITTED AS CONDOMINIUMS. IF A |
| | CHANGE OF OCCUPANCY IS PROPOSED (FROM R2 TO R1), REVISE |
| | PLAN TO SHOW COMPLIANCE WITH ALL REQUIERMENTS OF FBC EB |
| | CHAPTER 10, CHANGE OF OCCUPANCY. |
| | |
| | 2. SPEC SHEET FOR "ISO-STEP FLOOR UNDERLAYMENT" WAS |
| | SUBMITTED. PROVIDE THE FOLLOWING TEST REPORTS: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 3. C1, TOP LEFT, PAGE DID NOT PRINT PROPERLY. RE-PRINT |
| | AND CONFIRM THAT ALL TEXT PRINTS LEGIBLY. |
| | |
| | 4. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR, |
| | MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY |
| | OTHERS, FBC 109. |
| | |
| | 5. C1, SITE DATA, CONTRUCTION TYPE HAS A SYMBOL WHICH |
| | IS NOT CLEAR, AND STATES "APARTMENT". THIS IS NOT A |
| | BUILDING TYPE, SEE FBC CHAPTER 6 AND REVISE. |
| | |
| | 6. COMPLIANCE WITH FBC A FAIR HOUSING NOT CLEAR. |
| | CONSTRUCTED IN 2006, THIS IS CONSIDERED A COVERED UNIT. |
| | REVISE PLAN TO SHOW COMPLIANCE, FBC 107. |
| | |
| | YOU MAY FIND THE FOLLOWING WEBSITE HELPFUL, FREQUENTLY |
| | ASKED QUESTION #8: |
| | |
| | HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML |
| | |
| | THE DOJ/HUD JOINT STATEMENT, ADDENDUM TO FAIR HOUSING |
| | ACT, STATES: |
| | |
| | "DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION |
| | REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF |
| | PROPERTIES? |
| | ALTERATIONS, REHABILITATION OR REPAIR OF COVERED |
| | MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S |
| | DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW |
| | CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY |
| | AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY |
| | DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE |
| | LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT |
| | WITH THE LAW." |
| | |
| | 7. DETAIL 1-A1 SHOWS WOOD WALL FRAMING. FBC B 603, |
| | REVISE PLAN TO SHOW COMPLIANCE. BUILDING TYPE WAS NOT |
| | PROVIDED, BUT AS A HIGH RISE IT IS LIKELY A NON |
| | COMBUSTIBLE BUILDING. |
| | |
| | 8. FBC 107, FBC B 1207, REVISE PLAN TO INCLUDE FLOOR |
| | SLAB THICKNESS, OR PROVIDE A COPY OF THE PAGE FROM THIS |
| | BUILDING'S ORIGINAL CONSTRUCTION WHICH SHOWS THIS |
| | INFORMATION. SPEC SHEETS PROVIDE STC AND IIC |
| | INFORMATION FOR AN 8" SLAB. SLAB INFORMATION IS |
| | REQUIRED TO PROPOSE AN UNDERLAYMENT PRODUCT TESTED ON |
| | AN 8" SLAB. OTHERWISE, TEST REPORTS FOR A 6" SLAB IS |
| | REQUIRED (MOST CONSERVATIVE CONDITION). |
| | |