Plan Review Details - Permit 17031047
Plan Review Stops For Permit 17031047
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 07:39 Rev Time 0.00
Received By shill Date 2017-04-25 Time 14:38 Sent To  
Notes
2017-04-27 07:40:05PROVISO
 COMPLIANCE WITH FBC ACCESSIBILITY FAIR HOUSING REQUIRED
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-20 Cont ID  
Sent By shill Date 2017-04-20 Time 10:26 Rev Time 0.00
Received By shill Date 2017-04-20 Time 10:25 Sent To  
Notes
2017-04-20 10:27:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR,
 MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY
 OTHERS, FBC 109.
  
 2ND REVIEW, PROVIDE A COPY OF THE CONTRACT. A COST
 BREAKDOWN INCLUDING EACH ITEM, SF OR LF AREA, ETC. MAY
 BE REQUIRED.
  
 2. THIS PERMIT WILL BE ISSUED WITH PROVISO; COMPLIANCE
 WITH FAIR HOUSING ACT IS REQUIRED, FBC 5TH EDITION
 ACCESSIBILITY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 11:57 Rev Time 0.00
Received By shill Date 2017-03-30 Time 11:20 Sent To  
Notes
2017-03-30 11:58:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. C1 SITE DATA DECLARES THIS AS R1; SEE FBC B 310.
 THIS BUILDING WAS PERMITTED AS CONDOMINIUMS. IF A
 CHANGE OF OCCUPANCY IS PROPOSED (FROM R2 TO R1), REVISE
 PLAN TO SHOW COMPLIANCE WITH ALL REQUIERMENTS OF FBC EB
 CHAPTER 10, CHANGE OF OCCUPANCY.
  
 2. SPEC SHEET FOR "ISO-STEP FLOOR UNDERLAYMENT" WAS
 SUBMITTED. PROVIDE THE FOLLOWING TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 3. C1, TOP LEFT, PAGE DID NOT PRINT PROPERLY. RE-PRINT
 AND CONFIRM THAT ALL TEXT PRINTS LEGIBLY.
  
 4. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR,
 MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY
 OTHERS, FBC 109.
  
 5. C1, SITE DATA, CONTRUCTION TYPE HAS A SYMBOL WHICH
 IS NOT CLEAR, AND STATES "APARTMENT". THIS IS NOT A
 BUILDING TYPE, SEE FBC CHAPTER 6 AND REVISE.
  
 6. COMPLIANCE WITH FBC A FAIR HOUSING NOT CLEAR.
 CONSTRUCTED IN 2006, THIS IS CONSIDERED A COVERED UNIT.
 REVISE PLAN TO SHOW COMPLIANCE, FBC 107.
  
 YOU MAY FIND THE FOLLOWING WEBSITE HELPFUL, FREQUENTLY
 ASKED QUESTION #8:
  
 HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML
  
 THE DOJ/HUD JOINT STATEMENT, ADDENDUM TO FAIR HOUSING
 ACT, STATES:
  
 "DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF
 PROPERTIES?
 ALTERATIONS, REHABILITATION OR REPAIR OF COVERED
 MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S
 DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW
 CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY
 DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE
 LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT
 WITH THE LAW."
  
 7. DETAIL 1-A1 SHOWS WOOD WALL FRAMING. FBC B 603,
 REVISE PLAN TO SHOW COMPLIANCE. BUILDING TYPE WAS NOT
 PROVIDED, BUT AS A HIGH RISE IT IS LIKELY A NON
 COMBUSTIBLE BUILDING.
  
 8. FBC 107, FBC B 1207, REVISE PLAN TO INCLUDE FLOOR
 SLAB THICKNESS, OR PROVIDE A COPY OF THE PAGE FROM THIS
 BUILDING'S ORIGINAL CONSTRUCTION WHICH SHOWS THIS
 INFORMATION. SPEC SHEETS PROVIDE STC AND IIC
 INFORMATION FOR AN 8" SLAB. SLAB INFORMATION IS
 REQUIRED TO PROPOSE AN UNDERLAYMENT PRODUCT TESTED ON
 AN 8" SLAB. OTHERWISE, TEST REPORTS FOR A 6" SLAB IS
 REQUIRED (MOST CONSERVATIVE CONDITION).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-18 Cont ID  
Sent By jleahy Date 2017-04-18 Time 08:51 Rev Time 0.00
Received By jleahy Date 2017-04-18 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By jleahy Date 2017-04-03 Time 09:18 Rev Time 0.00
Received By jleahy Date 2017-04-03 Time 09:18 Sent To  
Notes
2017-04-03 09:21:05FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 WATER HEATER IS SHOWN AS THREE PHASE, AND PANEL IS ONLY
 SINGLE PHASE.
  
 SUBMIT CUT SHEET(S) FOR WATER HEATER
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By pleduc Date 2017-04-17 Time   Rev Time 0.00
Received By pleduc Date 2017-04-17 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-30 Cont ID  
Sent By pleduc Date 2017-03-30 Time   Rev Time 0.00
Received By pleduc Date 2017-03-30 Time 12:30 Sent To  
Notes
2017-03-30 15:22:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET C 1 - THERE IS NO REFERNENCE TO THE FLORIDA FIRE
 PREVENTION CODE OR ANY OTHER FIRE CODE.
  
 PLEASE PROVIDE A NOTE:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
  
 2)
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 3)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
  
 4)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 07:40 Rev Time 0.00
Received By shill Date 2017-04-24 Time 12:42 Sent To  
Notes
2017-04-24 12:42:34CONTRACT TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-20 Cont ID  
Sent By shill Date 2017-04-20 Time 10:27 Rev Time 0.00
Received By shill Date 2017-04-13 Time 10:57 Sent To  
Notes
2017-04-14 10:57:45B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-06 Cont ID  
Sent By tklarge Date 2017-04-06 Time 15:28 Rev Time 0.00
Received By tklarge Date 2017-03-28 Time 10:29 Sent To  
Notes
2017-03-29 10:29:21B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-04-24 Cont ID  
Sent By shill Date 2017-04-24 Time 12:41 Rev Time 0.00
Received By shill Date 2017-04-24 Time 12:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 11:23 Rev Time 0.00
Received By shill Date 2017-03-30 Time 11:23 Sent To  
Notes
2017-03-30 11:24:56SEE BUILDING COMMENTS
 A CHANGE OF OCCUPANCY REQUIRES IMPACT FEE ASSESSMENT BY
 PALM BEACH COUNTY. IF A CHANGE OF OCCUPANCY OR USE IS
 PROPOSED (TO BE DETERMINED IN NEXT REVIEW CYCLE),
 ADDITIONAL GUIDANCE WILL BE PROVIDED AT THAT TIME
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-04-06 Cont ID  
Sent By tklarge Date 2017-04-06 Time 15:28 Rev Time 0.00
Received By tklarge Date 2017-04-06 Time 15:25 Sent To  
Notes
***NONE***