| 2017-03-29 05:28:47 | 1) SUBMIT AN OVERALL FLOOR PLAN THAT CLEARLY SHOWS THE |
| | LOCATION OF THE WORK TO BE DONE.WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. THE PLAN SUBMITTED IS UNACCEPTABLE AS IT |
| | DOES NOT REFLECT THE ENTIRE SCOPE OF WORK. |
| | 2) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE |
| | NEW WATER AND SANITARY LINES TO BE INSTALLED. SHOW ALL |
| | PIPE SIZES, TYPE OF PIPE MATERIAL, CONNECTION TO THE |
| | EXISTING SYSTEM, ETC.WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.3. |
| | 3) IS THIS RESTROOM A HANDICAPPED ACCESSIBLE RESTROOM? |
| | IF SO, IT SHALL COMPLY WITH THE FBC- ACCESSIBILITY FOR |
| | FIXTURE CLEARANCES. |
| | 4) THE PROPOSAL REFERS TO A NEW TOILET YET ONE IS NOT |
| | SHOWN ON THE DRAWING. CLARIFY. |
| | 5) THE EXISTING BATHROOM DOES NOT SHOW A SHOWER YET THE |
| | PROPOSED ONE DOES. IS THIS SHOWER TO BE ADDED OR IS IT |
| | EXISTING? CLARIFY. |
| | 6) TWO COPIES OF A FLOOR PLAN SHALL BE SUBMITTED FOR |
| | THE WORK TO BE DONE. ONLY ONE HAS BEEN SUBMITTED. WPB |
| | AMEND. TO FBC SEC. 107.1. |
| | 7) IF THE SHOWER IS NEW, SHOW THE LENGTH AND WIDTH |
| | DIMENSIONS OF THE SHOWER. IT WILL HAVE TO COMPLY WITH |
| | THE FBC-ACCESSIBILITY CODE IF THE BATHROOM IS AN |
| | ACCESSIBLE BATHROOM. CLEARLY IDENTIFY THIS ON THE |
| | PLANS. FBC-ACCESS. SEC. 213.3.6. |
| | 8) THE FLOOR PLAN DOES NOT IDENTIFY THE TYPE OF |
| | FIXTURE(S) BEING ROUGHED IN. CLEARLY LABEL THE FIXTURES |
| | ON THE FLOOR PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) THERE WERE WALLS AND DRYWALL REMOVED IN THIS UNIT |
| | WITHOUT PERMITS. A FLOOR PLAN AND BUILDING PERMIT |
| | APPLICATION SHALL BE SUBMITTED THAT CLEARLY REFLECTS |
| | THE ENTIRE SCOPE OF WORK TO BE DONE INCLUDING ANY |
| | ELECTRIC WORK.WPB AMEND. TO FBC SEC.107.2.1. |
| | |
| | NOTE: THE SUBMITTED PLAN WAS SO VAGUE AND DEFICIENT IN |
| | THE MINIMUM PLAN REVIEW CRITERIA AS REQUIRED IN THE WPB |
| | AMEND. TO THE FBC THAT A CCOMPREHENSIVE PLAN REVIEW |
| | COULD NOT BE PERFORMED. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED UPON THE RE-REVIEW OF THESE DOCUMENTS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |