Plan Review Details - Permit 17031014
Plan Review Stops For Permit 17031014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-22 Cont ID  
Sent By cthroop Date 2017-05-22 Time 08:14 Rev Time 0.00
Received By cthroop Date 2017-05-19 Time 11:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By cthroop Date 2017-04-21 Time 09:26 Rev Time 0.00
Received By cthroop Date 2017-04-21 Time 07:19 Sent To  
Notes
2017-04-21 09:44:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER OF RECORD TO REVIEW AND APPROVE PLAN SHEETS
 5.1 & 6.1.
 2. ROOFING PERMIT REQUIRED.
 3. GENERAL WALL LEGEND ON PG. 1.1 SPECIFIES EXT. WALL
 INSULATION TO BE R-11. ENERGY SUBMITTAL FORM 405
 SPECIFIES R-19. PLEASE CLARIFY.
 4. SPECIFY WHICH DOOR ASSEMBLY WILL BE INSTALLED FROM
 PRODUCT APPROVAL FL14752.R5. DESIGNER TO REVIEW AND
 APPROVE.
 5. LANDINGS REQUIRED AT EXTERIOR DOORS.
 6. PROVIDE ATTIC ACCESS.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-30 Cont ID  
Sent By jpearson Date 2017-05-30 Time 08:38 Rev Time 0.00
Received By jpearson Date 2017-05-30 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-06 Cont ID  
Sent By vperez Date 2017-04-06 Time 16:38 Rev Time 0.00
Received By vperez Date 2017-04-06 Time 16:38 Sent To  
Notes
2017-04-06 16:39:46PLEASE HAVE DESIGNER OF RECORD SIGN AND SEAL ELECTRICAL
 SHEET. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop HIST HISTORICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ajones Date 2017-10-23 Time 16:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-05-16 Cont ID  
Sent By fmittner Date 2017-05-16 Time 15:36 Rev Time 0.00
Received By fmittner Date 2017-05-16 Time 15:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-04-07 Cont ID  
Sent By fmittner Date 2017-04-07 Time 09:58 Rev Time 0.00
Received By fmittner Date 2017-04-07 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-07 Time   Rev Time 0.00
Received By cpuell Date 2017-05-05 Time 14:45 Sent To  
Notes
2017-05-08 14:45:30R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By cthroop Date 2017-04-21 Time 09:26 Rev Time 0.00
Received By cthroop Date 2017-03-27 Time 13:54 Sent To  
Notes
2017-03-28 13:54:15R07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-07 Cont ID  
Sent By ccole Date 2017-06-07 Time 15:47 Rev Time 0.00
Received By ccole Date 2017-06-07 Time 15:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By skennedy Date 2017-04-21 Time 08:45 Rev Time 0.00
Received By skennedy Date 2017-04-21 Time 08:45 Sent To  
Notes
2017-04-21 09:31:541ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 FAILED - PLEASE DEMONSTRATE INTENT OF COMPLIANCE FOR
 THE BELOW SECTIONS:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By gjohnson Date 2017-04-18 Time 11:35 Rev Time 0.00
Received By gjohnson Date 2017-04-18 Time 10:54 Sent To  
Notes
2017-04-18 11:42:391ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WASHING MACHINE NOT SHOWN ON PLUMBING RISER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW LOCATION OF WATER HEATER. PER WPB AMEND
 TO FBC 107.2.1
  
 3. PLANS SHALL BE SIGNED AND SEALED BY PERSON TAKING
 RESPONSIBILITY FOR DESIGN. PER WPB AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-05-22 Cont ID  
Sent By cthroop Date 2017-05-22 Time 08:14 Rev Time 0.00
Received By cthroop Date 2017-05-19 Time 11:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-04-21 Cont ID  
Sent By cthroop Date 2017-04-21 Time 08:00 Rev Time 0.00
Received By cthroop Date 2017-04-21 Time 07:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-16 Cont ID  
Sent By fmittner Date 2017-05-16 Time 15:36 Rev Time 0.00
Received By fmittner Date 2017-05-16 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-04-07 Cont ID  
Sent By fmittner Date 2017-04-07 Time 10:00 Rev Time 0.00
Received By fmittner Date 2017-04-07 Time 10:00 Sent To  
Notes
***NONE***