Plan Review Details - Permit 17030946
Plan Review Stops For Permit 17030946
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By hmoser Date 2017-04-04 Time 15:55 Rev Time 0.00
Received By pleduc Date 2017-04-04 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-28 Cont ID  
Sent By pleduc Date 2017-03-28 Time   Rev Time 0.00
Received By hmoser Date 2017-04-03 Time 10:35 Sent To M
Notes
2017-03-28 11:20:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET FP 1 OF 1 - A CLOUDED NOTE INDICATES THAT "NO
 PRESSURE TEST IS REQUIRED". THERE IS NO CODE REFERENCE
 THAT INDICATES THE PROPOSED INSTALLATION SHALL NOT BE
 PRESSURE TESTED. (THIS WAS NOTED ON THE PROVISO
 COMMNETS ON THE MASTER #16120833)
  
 PER NFPA 13, 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4
 BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A
 PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
 24.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE OR VISUAL LEAKAGE.
 24.2.1.8* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR
 PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER
 ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI
 (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES.
 SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED
 SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  
 A PRESSURE TEST OF THE WORKING PRESSURE IS REQUIRED FOR
 2 HOURS PER NFPA 13. IF AN EXISTING FIRE PUMP IS
 INSTALLED PLEASE ENSURE THAT THE WEEKLY TEST/CHURN TEST
 IS CALCULATED.
  
 PLEASE REMOVE OR CORRECT THE NOTE OR JUSTIFY YOUR
 POSITION.
  
  
  
  
 2)
 SHEET FP 1 OF 1 - THERE ARE INCORRECT CODE REFERENCES
 INDICATED IN THE DESIGN NOTES SECTION; NFPA 13,
 16.2.1.4 & 16.2.1.6 . THE CORRECT CODE REFERENCES ARE
 NOTED ABOVE.
  
 PLEASE REMOVE OR CORRECT THE CODE REFENCES OR JUSTIFY
 YOUR POSITION.
  
  
  
  
 3)
 THE APPLICATION FORM INDICATES "REMOVE ADDITIONAL
 HEADS" THERE ARE NO INDICATIONS, CLOUDS, OR OTHER TYPE
 OF CALL-OUT SHOWING WHICH HEADS ARE REMOVED OR CHANGED.
  
 PLEASE INDICATE WHAT HEADS ARE AFFECTED AND THEIR
 LOCATIONS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-04 Cont ID  
Sent By hmoser Date 2017-04-04 Time 15:55 Rev Time 0.00
Received By hmoser Date 2017-04-03 Time 10:57 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-03 Cont ID  
Sent By hmoser Date 2017-04-03 Time 10:36 Rev Time 0.00
Received By hmoser Date 2017-03-23 Time 11:18 Sent To  
Notes
2017-03-24 11:18:32REVISION ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By hmoser Date 2017-04-04 Time 15:55 Rev Time 0.00
Received By hmoser Date 2017-04-04 Time 15:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By hmoser Date 2017-04-03 Time 10:35 Rev Time 0.00
Received By hmoser Date 2017-04-03 Time 10:35 Sent To  
Notes
2017-04-03 10:36:19PLAN DENIED SEE FIRE COMMENTS HM.