| 2017-03-23 14:29:20 | THE BACKFLOW DEVICE IS REQUIRED TO BE LEAD FREE PER THE |
| | CITY OF WPB CROSS -CONNECTION CONTROL MANUAL & 2014 |
| | FBC-PLUMBING SEC. 605.2.1. THE SUBMITTED DOCUMENTS DO |
| | NOT SHOW THAT THE DEVICE IS LEAD FREE. |
| | |
| | 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE |
| | DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK |
| | SECTION ON THE PERMIT APPLICATION. |
| | |
| | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. |
| | |
| | 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| | SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. |
| | 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO |
| | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE |
| | CITY?S REQUIREMENTS. |
| | 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| | IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| | DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| | PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| | ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| | DEVICE. |
| | NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS |
| | SHALL BE ON THE JOBSITE FOR INSPECTION. |
| | THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL CAN BE FOUND AT : |
| | HTTP://WPB.ORG/UTILITIES/BACKFLOW |
| | UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: |
| | WWW.USC.EDU/DEPT/FCCCHR |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |