| 2017-03-22 07:48:36 | W. P. B. BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17030831 |
| | ADD: 735 HANSEN ST. |
| | CONT: ROOFING SYSTEMS OF FLORIDA, INC. |
| | TEL: 561-308-3000 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 22/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION DOES NOT INDICATE THE TYPE OF |
| | ROOFS TO BE REROOFED. THE COUNTYWIDE GIS SYSTEM SHOWS |
| | THE PROPERTY OF 735 HANSEN TO HAVE A GABLE ROOF WITH |
| | SHINGLES AND A FLAT SECTION OF ROOF AS WELL. IT IS |
| | ASSUMED THAT BOTH THE GABLED SHINGLE SECTION OF ROOF |
| | AND THE FLAT ROOF BOTH ARE TO BE REROOFED. WITH THAT |
| | BEING SAID THE PRODUCT APPROVAL SUBMITTED FOR THE FLAT |
| | ROOF A CERTAIN TEED MODIFIED BITUMEN ROOFING SYSTEM, |
| | NOA 14-0529.02 PAGE 27 SHOWS SYSTEM TYPE E7 A BASE |
| | SHEET MECHANICALLY FASTENED WITH A MAXIMUM DESIGN |
| | PRESSURE OF -60 PSF AND GENERAL LIMITATION # 7. FOR A |
| | EXPOSURE C AT 15 FEET IN ZONE # 2 THE NEGATIVE PRESSURE |
| | IS -63.6 AND ZONE # 3 THE PRESSURE IS -95.7. LIMITATION |
| | # 7 IS IN AFFECT. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. FBC-R 301.2(3). |
| | |
| | 2) PLEASE ALSO PROVIDE THE SLOPE OF THE ROOF FOR THE |
| | SHINGLE PORTION OF THE ROOF. ROOFING ASPHALT SHINGLES |
| | 2014< 4/12 PITCH. R905.2.7 UNDERLAYMENT APPLICATION. |
| | UNDERLAYMENT SHALL BE INSTALLED USING ONE OF THE |
| | FOLLOWING METHODS: |
| | FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (17-PERCENT SLOPE), AND LESS THAN FOUR UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | UNDERLAYMENT SHALL COMPLY WITH ASTM D 226, TYPE I OR |
| | TYPE II OR ASTM D 4869, TYPE II OR TYPE IV OR ASTM D |
| | 6757 AND SHALL BE TWO LAYERS APPLIED IN THE FOLLOWING |
| | MANNER. APPLY A 19-INCH (483 MM) STRIP OF UNDERLAYMENT |
| | FELT PARALLEL TO AND STARTING AT THE EAVES, FASTENED |
| | SUFFICIENTLY TO HOLD IN PLACE. STARTING AT THE EAVE, |
| | APPLY |
| | 36-INCH-WIDE (914 MM) SHEETS OF UNDERLAYMENT, |
| | OVERLAPPING SUCCESSIVE SHEETS 19 INCHES. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |