Plan Review Details - Permit 17030730
Plan Review Stops For Permit 17030730
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By cthroop Date 2017-05-03 Time 16:52 Rev Time 0.00
Received By cthroop Date 2017-05-03 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-28 Cont ID  
Sent By cthroop Date 2017-03-28 Time 08:20 Rev Time 0.00
Received By cthroop Date 2017-03-28 Time 08:17 Sent To  
Notes
2017-03-28 08:26:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
  
 1. DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
 2. PROVIDE SITE PLAN IDENTIFYING FOOT PRINT OF BUILDING
 AND AREA OF WORK.
 3. PROVIDE DETAIL OF NEW WALL - TYPE OF
 CONSTRUCTION/MATERIALS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By jleahy Date 2017-05-03 Time 16:13 Rev Time 0.00
Received By jleahy Date 2017-05-03 Time 16:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-21 Cont ID  
Sent By rlecky Date 2017-03-21 Time 12:02 Rev Time 0.00
Received By rlecky Date 2017-03-21 Time 11:09 Sent To  
Notes
2017-03-21 12:03:09PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE PLAN DOES NOT INDICATE THE SIZE OR WIRING METHOD
 FOR THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR
 THE COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20
 AMPERE BRANCH CIRCUITS. THE CIRCUIT SIZE FOR THE
 REFRIGERATOR AND MICRO WAS NOT SPECIFIED. FBC E3901.3,
 E3901.4
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. A BUILDING WITH GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE IS
 REQUIRED TO HAVE A CARBON MONOXIDE DETECTOR WITHIN TEN
 FEET OF EACH ROOM USED FOR SLEEPING. FBC R314, 315
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By gjohnson Date 2017-05-03 Time 15:58 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 15:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By gjohnson Date 2017-03-27 Time 16:04 Rev Time 0.00
Received By gjohnson Date 2017-03-27 Time 16:04 Sent To  
Notes
2017-03-27 16:10:481ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 NEW CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. SHOW BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(37).
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-03 Cont ID  
Sent By cthroop Date 2017-05-03 Time 16:52 Rev Time 0.00
Received By cthroop Date 2017-04-27 Time 12:33 Sent To  
Notes
2017-04-28 12:33:32R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-28 Cont ID  
Sent By cthroop Date 2017-03-28 Time 08:19 Rev Time 0.00
Received By cthroop Date 2017-03-17 Time 08:41 Sent To  
Notes
2017-03-20 08:42:33R07

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By gjohnson Date 2017-05-03 Time 15:59 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By gjohnson Date 2017-03-27 Time 16:03 Rev Time 0.00
Received By gjohnson Date 2017-03-27 Time 11:46 Sent To  
Notes
2017-03-27 16:03:531ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  