Plan Review Details - Permit 17030708
Plan Review Stops For Permit 17030708
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 12:12 Rev Time 0.00
Received By shill Date 2017-05-15 Time 12:01 Sent To  
Notes
2017-05-15 12:13:01PROVISO
 WINDOWS: U = .30
 SHGC = .25
  
 PER ENERGY CALCS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-27 Cont ID  
Sent By shill Date 2017-03-27 Time 15:07 Rev Time 0.00
Received By shill Date 2017-03-27 Time 14:49 Sent To  
Notes
2017-03-27 15:11:22PROVISO
 WINDOWS: U = .30
 SHGC = .25
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 12:18 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 12:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By rlecky Date 2017-03-23 Time 14:28 Rev Time 0.00
Received By rlecky Date 2017-03-23 Time 11:29 Sent To  
Notes
2017-03-23 14:33:03 
 17030708
 801 DOBBINS STREET
 APARTMENT REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE PLANS AS SUBMITTED ARE DEFICIENT OR MISSING
 INFORMATION IN THE FOLLOWING AREAS.
  
 LOCATION OF PANEL BOARDS, AIR CONDITIONING EQUIPMENT,
 DISCONNECTS, TAMPER RESISTANT RECEPTACLES, MISSING
 RECEPTACLES, INTERCONNECTION OF SMOKE DETECTORS, ARC
 FAULT RECEPTACLES ARE REQUIRED THROUGHOUT, REQUIRED
 LAUNDRY CIRCUITS, SPECIFICATIONS FOR CEILING FIXTURES,
 ENERGY EFFICIENCY SPECS FOR LAMPS, HOUSE PANEL
 DIRECTORY, SERVICE LOCATION, SERVICE RISER HEIGHT,
 SERVICE DROP HEIGHT, WIRE SIZES FOR SERVICE, WIRE SIZES
 FOR WATER HEATERS, WIRE SIZES FOR PANELS, MAIN
 DISCONNECTS, INTERSYSTEM GROUNDING BAR, SERVICE FAULT
 CURRENT CALCULATIONS, PANEL BOARD FAULT CURRENT
 CALCULATIONS, ARC FAULT SAFETY LABELING, APARTMENT LOAD
 CALCULATION.
  
 NOTE THAT AIR CONDITIONING, HEATING, LAUNDRY, RANGE AND
 DRYER LOADS WERE NOT INCLUDED IN THE LOAD CALCULATIONS
 AND NEED TO BE ADDED IF THEY WILL BE PART OF THIS
 SUBMITTAL.
  
 NEC CODE SECTIONS: 210.12, 110.9, 110.10, 406.11,
 250.94, 210.52 (F), 410.116, 110.26,
  
 FBC CODE SECTIONS: E3902.12, E3609, E3703.3, ER404.1,
 E4004.8
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 12:18 Rev Time 0.00
Received By jleahy Date 2017-05-02 Time 08:19 Sent To  
Notes
2017-05-03 08:20:43B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-29 Cont ID  
Sent By gjohnson Date 2017-03-29 Time 16:30 Rev Time 0.00
Received By gjohnson Date 2017-03-16 Time 12:53 Sent To  
Notes
2017-03-17 12:54:06R18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 17:04 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-28 Cont ID  
Sent By ccole Date 2017-03-28 Time 08:40 Rev Time 0.00
Received By ccole Date 2017-03-28 Time 08:40 Sent To  
Notes
2017-03-28 08:50:421ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030708
 3/28/17
  
 1) SHEET 3.0: PLEASE IDENTIFY ALL ROOMS AND SPACES ON
 THE FLOOR PLANS- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC.
  
 2) ENERGYGAUGE FORM R405-2014:
  
 A) THE IDENTIFICATIONS OF THE APARTMENTS ON THE FORMS
 (A, B ETC.) DO NOT MATCH THE PLANS WHICH LISTS THE
 UNITS NUMERICALLY. PLEASE CORRELATE THE PLANS AND
 CALCULATIONS SO THEY MATCH.
  
 B) THE FORMS ARE LACKING COMPLETE PROJECT INFORMATION
 AND DATA AT THE TOP OF THE FORM AND ARE NOT SIGNED BY
 THE OWNER/AGENT.
  
 C) THE FORMS ARE INDICATING A "WORST CASE" COMPLIANCE
 WHICH IS ONLY PERMITTED FOR MODEL HOME COMPLIANCE- SEE
 SECTION R405.4.2 EXCEPTION.
  
 D) THE CHECKLISTS HAVE NOT BEEN COMPLETED.
  
 4) SHEET 3.0: PROVIDE THE EQUIPMENT SCHEDULES FOR AHU'S
 # 2 & 3. PLEASE NOTE ENERGYGAUGE FORM R405 AND THE AC
 CALCULATIONS EACH LIST THE SYSTEMS AS 16 SEER.
  
 5) 3.0, 1ST FLOOR APT:
  
 A) PROVIDE THE SIZE OF THE BEDROOM/HALLWAY TRANSFER
 DUCT.
  
 B) CLARIFY IF AHU-3 HAS AN OPEN RETURN BECAUSE THE
 D/600 RETURN GRILL IS UNDERSIZED.
  
 6) 3.0: 2ND FLOOR:
  
 A) PROVIDE THE FLEX DUCT SIZES,
  
 B) THE BEDOOM TRANSFERS ARE MISLABELED AS SUPPLY
 DIFFUSERS AND ARE UNDERSIZED- 50 SQ. INCHES PER 100
 CFMS REQUIRED. ONE BEDROOM TRANSFER IN UNIT 201 IS NOT
 LABELED.
  
 C) INDICATE WHICH TYPE OF BI-FOLD DOORS ARE ENCLOSING
 THE AHU CLOSETS.
  
 7) PROVIDE KITCHEN AND BATH EXHAUST SYSTEMS IN
 ACCORDANCE WITH TABLE M1507.4 FBC-14 RESIDENTIAL. SEE
 ALSO SECTION R303.3 FOR BATHROOM VENTILATION IF USING
 AN OPERABLE WINDOW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-12 Cont ID  
Sent By gjohnson Date 2017-05-12 Time 11:01 Rev Time 0.00
Received By gjohnson Date 2017-05-12 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-29 Cont ID  
Sent By gjohnson Date 2017-03-29 Time 15:03 Rev Time 0.00
Received By gjohnson Date 2017-03-29 Time 13:31 Sent To  
Notes
2017-03-29 15:39:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 2. PROVIDE MANUFACTURE SPECIFICATION FOR TANKLESS WATER
 HEATER. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE EXISTING PLUMBING LAYOUT FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  