Plan Review Details - Permit 17030679
Plan Review Stops For Permit 17030679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-30 Cont ID  
Sent By shill Date 2017-06-30 Time 15:46 Rev Time 0.00
Received By shill Date 2017-06-30 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By shill Date 2017-03-27 Time 15:38 Rev Time 0.00
Received By shill Date 2017-03-27 Time 15:32 Sent To  
Notes
2017-03-27 15:48:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A0.0 STATES THIS IS A LEVEL 1 ALTERATION. SEE FBC EB
 504, THIS IS A LEVEL II ALTERATION, REVISE PLAN.
  
 2. REVISE PLAN TO CLARIFY LOCATION OF SMOKE BARRIERS,
 IF ANY, FBC 107. IF THIS BUILDING DOES NOT HAVE SMOKE
 BARRIERS, REVISE PLAN WITH A NOTE.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By jleahy Date 2017-06-29 Time 12:34 Rev Time 0.00
Received By jleahy Date 2017-06-29 Time 12:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 14:04 Rev Time 0.00
Received By rlecky Date 2017-03-28 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By shill Date 2017-06-30 Time 15:47 Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 15:10 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By pleduc Date 2017-03-20 Time   Rev Time 0.00
Received By pleduc Date 2017-03-20 Time 10:39 Sent To  
Notes
2017-03-20 17:01:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET A 0.0 - THERE IS A NEW DOOR PROPOSED IN THE
 CORRIDOR. IT APPEARS THAT THIS SECTION OF THE HOSPITAL
 MAY BE WITHIN AN EXISITNG SMOKE BARRIER. DOES THIS
 PROSED DOOR CONFLICT WITH THE ORIGINAL SMOKE BARRIER
 REQUIREMENTS AND/OR AFFECT ANY SMIOKE REMOVAL
 CALCULATION AIR REQUIRERMENETS.
  
 DOES THIS DOOR NEED ANY SPECIAL SEALING AND OR
 HARDWARE?
  
 PLEASE PROVIDE A REVEIW AND/ OR CHANGE..
  
  
  
 2)
 SHEET A 1.0 - DOOR # 2 DOES NOT SHOW ANY HARDWARE OR
 LOCKING EQUIPMENT. THIS DOOR IS PROPOSED IN AN EXIT
 CORRIDOR. WHAT OCCUPANY NUMBER DOES IT SERVE? IS EXIT
 OR PANIC HARDWARE REQUIRED? DOES IT LOCK OR LATCH? DOES
 IT HAVE A KEY OR THUMB LOCKING BOLT?
  
 PLEASE PROVIDE APPLICABLE EXIT EQUIPMENT.
  
  
  
 3)
 SHEET A 1.0 - DOOR # 1 DOES NOT SHOW ANY HARDWARE OR
 LOCKING EQUIPMENT. WILL THIS DOOR BE LOCKABLE? THE LOCK
 MUST MEET THE REQUIREMENTS OF NFPA 101, CHAPTER 7,
 MENAS OF EGRESS AND CAN NOT BE LOCK IN THE PATH OF
 EGRESS UNLESS MEETING THOSE REQUIREMENTS.
  
 PLEASE PROVIDE A REVIEW AND/OR CHANGE
  
  
  
 4)
 SHEET A 1.0 & E 0.1 - THE PROPOSED DOOR IN THE CORRIDOR
 IS NOT SHOWN WITH AN EXIT LIGHT LEADING TO THE EXIT.
  
 PLEASE REIVEW AND PROVIDE FOR THE APPLICABLE EXIT
 SIGNAGE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-30 Cont ID  
Sent By shill Date 2017-06-30 Time 15:47 Rev Time 0.00
Received By shill Date 2017-06-02 Time 11:20 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 14:04 Rev Time 0.00
Received By rlecky Date 2017-03-16 Time 13:42 Sent To  
Notes
2017-03-17 13:42:33B20