Plan Review Details - Permit 17030654
Plan Review Stops For Permit 17030654
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 08:34 Rev Time 0.00
Received By cthroop Date 2017-06-27 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By cthroop Date 2017-06-02 Time 09:56 Rev Time 0.00
Received By cthroop Date 2017-06-02 Time 07:12 Sent To  
Notes
2017-06-02 10:24:25BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUB-SURFACE INVISTEGATION BY SOILPROBE ENGINEERING &
 TESTING, INC. SPECIFIES THE INSTALLATION OF PIN PILES
 AND HELICAL-PIERS WITH A SPACING OF NOT GREATER THAN 8
 FEET ON CENTER. ( SEE PAGES 3 & 4 OF REPORT AND PLAN
 PAGE S1.0) PLEASE CLARIFY.
 2. PLAN PAGE A-002 SPECIFIES THE REMOVAL OF AN INTERIOR
 LOAD BEARING WALL. PLAN PAGE S2.0 SPECIFIES THIS WALL
 TO REMAIN. IF BEARING WALL IS TO BE REMOVED, PROVIDE
 SHORING DETAIL. PLEASE CLARIFY.
 3. PROVIDE LINTEL/BEAM SCHEDULE.
 4. PROVIDE WINDOW AND DOOR SCHEDULE WITH ROUGH OPENINGS
 AND DESIGN WIND LOADS.
 5. DETAIL 2, PAGE S0.1 IS NOT APPLICABLE TO THIS
 PROJECT. NEW ROOF CONSISTS OF 2X10 P.T 16 INCHES ON
 CENTER.
 6. PROVIDE DETAIL OF VERTICAL RE-INFORCING FOR 8" CMU
 IN-FILL.
 7. PROVIDE DETAIL FOR THE REMOVAL OF FRENCH DOORS AND
 INSTALLATION OF DOUBLE WINDOWS.
 8. NO MECHANICAL PLAN SUBMITTED. CANNOT VERIFY IF THERE
 WILL BE ADDITIONAL CONDITIONED SPACE.
 9. PLAN PAGE A-007 TO BE SIGNED AND SEALED BY DESIGNER
 OF RECORD.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-20 Cont ID  
Sent By rlecky Date 2017-06-20 Time 14:30 Rev Time 0.00
Received By rlecky Date 2017-06-20 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-01 Cont ID  
Sent By rlecky Date 2017-06-01 Time 14:38 Rev Time 0.00
Received By rlecky Date 2017-06-01 Time 11:48 Sent To  
Notes
2017-06-01 14:40:07 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS AS WELL.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC
 E4004.8
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
 THE PLANS DO NOT INDICATE THE SIZE OR WIRING METHOD FOR
 THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR THE
 COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20
 AMPERE BRANCH CIRCUITS. FBC E3901.3, E3901.4
  
 INCLUDE A PANEL SCHEDULE SHOWING THE NEW CIRCUITS WITH
 APPROPRIATE OVERCURRENT PROTECTION. NEC 110.26, FBC R
 E3405.1, E3706.2
  
 ALL NEW CIRCUITS MUST BE PROTECTED WITH ARC FAULT
 CIRCUIT BREAKERS. FBC E3902.12, NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.2;
 FBC R E4002.14
  
 AN INTERSYSTEM BONDING SYSTEM IS REQUIRED AT THE
 SERVICE GROUNDING SYSTEM. FBC E3609.3
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE FRONT
 AND REAR ELEVATIONS. FBC E3902,NEC 210.8
  
 RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER
 REQUIRE GFCI PROTECTION. FBC E3902 NEC 210.8
  
 PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA.
 RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE
 FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE
 OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC
 210.52, FBC E3901.3
  
 NOTE: THE PLANS ON SHEET A-OO2 INDICATE THE REMOVAL OF
 APPLIANCES IN THE GARAGE. THESE APPLIANCES ARE STILL
 SHOWN IN THE GARAGE ON THE ELECTRICAL PLANS. PLEASE
 CLARIFY.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By rlecky Date 2017-03-23 Time 11:04 Rev Time 0.00
Received By rlecky Date 2017-03-23 Time 10:21 Sent To  
Notes
2017-03-23 11:05:26PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA.
 FBC E3901.3
  
 VERIFY THAT THE EXISTING BEDROOMS HAVE THE REQUIRED
 SMOKE AND CARBON MONOXIDE DETECTORS. REMODELING OF AN
 EXISTING STRUCTURE IS REQUIRED TO INCLUDE
 INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND OUTSIDE
 EACH SLEEPING AREA. IF THE BUILDING HAS GAS APPLIANCES,
 AN ATTACHED GARAGE OR A FIREPLACE, A CARBON MONOXIDE
 DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED
 FOR SLEEPING. 2014 FBC R314, 315
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC
 E4004.8
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 08:33 Rev Time 0.00
Received By cthroop Date 2017-06-16 Time 13:21 Sent To  
Notes
2017-06-19 13:21:44R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-07 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-11 Time 13:10 Sent To  
Notes
2017-05-12 13:10:24R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-04 Cont ID  
Sent By skennedy Date 2017-04-04 Time 14:02 Rev Time 0.00
Received By skennedy Date 2017-03-16 Time 09:19 Sent To  
Notes
2017-04-04 14:02:594/4/17 PLACED IN DENIED H. IT IS ANTICIPATED THE
 APPLICANT WILL REDUCE THE SCOPE OF THE APPLICATION, THE
 ATTACHED CANCEL REQUEST ALSO INDICATES A SCOPE
 REDUCTION. AN AMENDED LETTER IS FORTHCOMING. REVIEW IS
 SUSPENDED UNTIL RE-SUBMITTAL. RE-SUBMITTAL MAY BE
 ACCEPTED IF PRIOR TO 9/16/2017. SAK
2017-03-17 09:19:33R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 07:39 Rev Time 0.00
Received By cthroop Date 2017-06-27 Time 07:39 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By cthroop Date 2017-06-02 Time 09:51 Rev Time 0.00
Received By cthroop Date 2017-06-02 Time 07:12 Sent To  
Notes
2017-06-02 09:52:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NO MECHANICAL PLAN SUBMITTED. CANNOT VERIFY
 ADDITIONAL CONDITIONED SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-06-26 Cont ID  
Sent By skennedy Date 2017-06-26 Time 15:40 Rev Time 0.00
Received By skennedy Date 2017-06-26 Time 15:40 Sent To  
Notes
2017-06-26 15:40:25NO MECHANICAL WORK PROPOSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By skennedy Date 2017-06-02 Time 11:21 Rev Time 0.00
Received By skennedy Date 2017-06-02 Time 11:21 Sent To  
Notes
2017-06-02 11:33:451ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 THE PLAN DOES NOT SHOW MECHANICAL IMPROVEMENTS HOWEVER
 THE EXPANSION OF SPACE INDICATES MECHANICAL ALTERATIONS
 MAY BE INDICATED. EITHER SUPPLY A PLAN PER THE SECTION
 BELOW OR INDICATE NO MECHANICAL IS TO BE DONE UNDER THE
 PROJECT OR WILL BE DONE BY SEPARATE PERMIT.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 &
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-05-24 Time   Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 17:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 08:33 Rev Time 0.00
Received By cthroop Date 2017-06-27 Time 07:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By cthroop Date 2017-06-02 Time 09:52 Rev Time 0.00
Received By cthroop Date 2017-06-02 Time 07:58 Sent To  
Notes
2017-06-02 09:56:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW FLAT ROOF SYSTEM
 COMPONENETS.
 2. PLANS SPECIFY "S" TYPE CLAY TILE TO BE USED FOR
 REPLACEMENT OF MAIN HOUSE ROOFING. NOA SUBMITTED IS FOR
 FLAT CONCRETE TILE. PLEASE CLARIFY.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pcreigh Date 2017-06-07 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-07 Time 09:30 Sent To  
Notes
2017-06-07 09:47:44PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved