Plan Review Details - Permit 17030604
Plan Review Stops For Permit 17030604
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time 09:36 Sent To  
Notes
2017-04-06 10:46:03BUILDING PLAN REVIEW
 W. P. B. REVISION: 17030604
 W. P. B. PERMIT: 15100707
 ADD: 831 BELVEDERE RD.
 CONT: AJS BUILDING & RENOVATIONS, INC.
 TEL: (407)298-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 06/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THE SHEET A3 AND M1 DO NOT MATCH THE
 FLOOR LAYOUT, SEE THE DOOR OPENING TO THE MECHANICAL
 CLOSET, DISCREPANCY IN THE PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2A) ON SHEETS A4 AND A6 THERE IS HAND WRITTEN INK ON
 THE PLANS. ONLY THE DESIGNER OF RECORD CAN MAKE CHANGES
 TO THE PLANS. 61G15-23.002(2) FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER.
  
 2B) SHEET A4 THE HAND WRITTEN NOTE INDICATES FOR THE
 WINDOW INFILL ENGINEERING IS ATTACHED. PLEASE NOTE
 THERE ARE ENGINEERING SHEETS BUT NONE OF THE
 ENGINEEERING SHEETS SHOW THIS DETAIL. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 2C) THE PLANS ARE DESIGNED BY JOHN P STOPPI JR. P. E.
 THE 81/2 X 14 INCH ENGINEERING SKETCHES SUBMITED ARE BY
 RIZA ALTAN A DELEGATE ENGINEER THE ENGINEERING SKETCHES
 NEED TO BE REVIEWED BY THE ENGINEER OF RECORD AND A
 SHOP DRAWING STAMP OF APPROVAL APPLIED.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PLEASE REVIEW THE PRODUCT APPROVAL FOR THE FRONT
 DOOR, NOA 15-0612.09 PLEASE REVIEW THE TECHNICAL SHEET
 3 OF 11. THIS DOOR IS ONLY GOOD FOR 20 PSF WITH THE
 REQUIRED 1/2 INCH ADA SILL. 2014 FBC-B 1609.1.5 &
 1609.1.2.3.1.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-06 Cont ID  
Sent By vperez Date 2017-04-06 Time 08:40 Rev Time 0.00
Received By vperez Date 2017-04-06 Time 08:40 Sent To  
Notes
2017-04-06 08:41:20ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL APPROVAL.
 FBC 107.3.5
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By pleduc Date 2017-04-10 Time   Rev Time 0.00
Received By pleduc Date 2017-04-10 Time 13:18 Sent To  
Notes
2017-04-10 13:37:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 GENERAL COMMNET - THERE ARE NO REVISION CLOUDS OR OTHER
 INDICATIONS SHOWING WHAT OR WHERE CHANGES WERE MADE.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE SPECIFIC INDICATORS FOR EACH AREA OF
 REVISION ON EACH PLAN SHEET AS APPLICABLE.
  
  
  
  
 2)
 SHEET A 3 - THE FIRE WALL IS INDICATED AS CALL=OUT WT2.
 WT2 DOES NOT HAVE A FIRE WALL LISTING.
  
 PLEASE PROVIDE THE APPLICABLE FIRE WALL LISTING
 REFERENCE.
  
  
  
 3) ADDRESS OTHER CITY DEPARTMENT'S COMMENTS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-11 Cont ID  
Sent By tklarge Date 2017-04-11 Time 10:46 Rev Time 0.00
Received By tklarge Date 2017-03-15 Time 12:54 Sent To  
Notes
2017-04-05 12:55:03C09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 18:07 Rev Time 0.00
Received By ccole Date 2017-04-05 Time 17:54 Sent To  
Notes
2017-04-05 18:12:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030604
 4/5/17
  
 1) THE LOCATION OF THE AHU CLOSET DOOR AS SHOWN ON THE
 REVISED M-1 PLAN DOES NOT MATCH THE LOCATION ON THE
 ARCHITECTURAL AND PLUMBING PLAN SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-04-11 Cont ID  
Sent By tklarge Date 2017-04-11 Time 10:45 Rev Time 0.00
Received By tklarge Date 2017-04-11 Time 10:09 Sent To  
Notes
***NONE***