Plan Review Details - Permit 17030466
Plan Review Stops For Permit 17030466
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 14:22 Rev Time 0.00
Received By tklarge Date 2017-07-20 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By tklarge Date 2017-05-04 Time 10:50 Rev Time 0.00
Received By tklarge Date 2017-05-04 Time 10:50 Sent To  
Notes
2017-05-04 10:50:521) THE ICC LEGACY REPORT THAT HAS BEEN SUBMITTED IS
 UNACCEPTABLE. THE REPORT IS BASED ON THE 1997 UBC WHICH
 IS NOT RECCOGNIZED BY THE FBC AS A REFERENCED STANDARD.
 NOTE: THE SUBMITTED UL ASSEMBLY DESIGN IS ACCEPTABLE AS
 IT IS FOR A 2 HOUR ASSEMBLY IF THAT IS THE INTENT.
 2) THE HORIZONTAL SHAFT ENCAPSULATING THE DRAIN LINES
 SHALLL BE 2 HOUR RATED. DRAWINGS 13A-A & 13A-B SHOW THE
 SHAFT AS 1 HOUR RATED. CLARIFY.
 3) THE SUBMITTED NARRATIVE STATES THAT SHAFT ENCLOSURES
 CONNECTING LESS THAN 4 STORIES REQUIRE A 1 HOUR RATING
 WHICH IS CORRECT BUT THIS STRUCTURE IS 8 STORIES.
 PLEASE CLARIFY THIS RESPONSE.
 4) THE NARRATIVE ALSO REFERS TO FBC SEC. 406.3.5 FOR
 ALLOWING A 1 HOUR ROOF RATING. THIS SECTION IS FOR AREA
 & HEIGHT IN THE 2010 FBC AND DOES NOT REFER TO ANY
 HOURLY RATING. CLARIFY.
 5) THE NARRATIVE ALSO REFERS TO SEC. 713.4.2.1 OF THE
 FBC - THIS SECTION IN THE 2010 FBC REFERS TO
 NONCOMBUSTIBLE PENETRATING ITEMS THAT CONNECT NOT MORE
 THAN THREE STORIES ARE PERMITTED. THIS SECTION APPLIES
 TO NONFIRE - RESISTANCE RATED ASSEMBLIES. CLARIFY HOW
 THIS APPLIES TO THIS ISSUE WHEN THE STAIR ENCLOSURE IS
 A 2 HOUR RATED ENCLOSURE.
 6) THE NARRATIVE ALSO REFERS TO FBC SEC.708.4 WHICH
 REFERS TO THE FIRE RATING OF SHAFT ENCLOSURES. THIS
 STRUCTURE IS 8 STORIES AND REQUIRES A 2 HOUR RATING FOR
 THE THE HORIZONTAL SHAFT ENCLOSURE.
 AT THIS POINT DUE TO THE DISCRPANCIES IN THE SUBMITTED
 DOCUMENTS I HAVE NO IDEA IF YOUR DESIGN IS GOING TO BE
 2 HOUR RATED OR IF YOU ARE STILL ATTEMPTING TO GET A 1
 HOUR RATING APPROVED WHICH DOES NOT MEET CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By shill Date 2017-03-14 Time 12:17 Rev Time 0.00
Received By tklarge Date 2017-03-14 Time 12:16 Sent To  
Notes
2017-03-14 12:17:181) INDICATE THE REQUIRED FIRE RATING OF THE STAIRWAY ON
 THE DRAWINGS.FROM THE ORIGINAL DRAWINGS THIS IS A 2
 HOUR RATED STAIRWAY.
 2) INDICATE THE FIRE RATING OF THE ENCLOSURE FOR THE
 PIPING ON THE DRAWINGS. THE DRAWINGS NOTE 2 LAYERS OF
 5/8 INCH TYPE X DRYWALL ON METAL STUD FRAMING WHICH
 WOULD PROVIDE AN 80 MINUTE FIRE RATING WHICH IS LESS
 THAN THE 2 HOUR RATING OF THE ENCLOSURE.THIS PIPING
 ENCLOSURE SHALL BE THE SAME RATING AS THE ENCLOSURE IN
 WHICH IT IS LOCATED.FBC 713..4, 713.5.
 3) INDICATE THE GAUGE OF THE METAL STUDS BEING USED.
  
 TIM LARGE
 561-805-6692
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-18 Cont ID  
Sent By jleahy Date 2017-07-18 Time 17:04 Rev Time 0.00
Received By jleahy Date 2017-07-18 Time 17:04 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-19 Cont ID  
Sent By vperez Date 2017-04-19 Time 10:28 Rev Time 0.00
Received By vperez Date 2017-04-19 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By vperez Date 2017-03-13 Time 14:58 Rev Time 0.00
Received By vperez Date 2017-03-13 Time 14:58 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 14:22 Rev Time 0.00
Received By tklarge Date 2017-07-17 Time 14:35 Sent To  
Notes
2017-07-18 14:35:44RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By tklarge Date 2017-05-04 Time 10:51 Rev Time 0.00
Received By tklarge Date 2017-04-17 Time 12:51 Sent To  
Notes
2017-04-18 12:51:47RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-14 Cont ID  
Sent By tklarge Date 2017-03-14 Time 12:18 Rev Time 0.00
Received By tklarge Date 2017-03-13 Time 13:48 Sent To  
Notes
2017-03-13 13:49:10VPEREZ'S DESK

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 14:21 Rev Time 0.00
Received By tklarge Date 2017-07-20 Time 14:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By tklarge Date 2017-05-04 Time 10:50 Rev Time 0.00
Received By tklarge Date 2017-05-04 Time 06:21 Sent To  
Notes
2017-05-04 08:56:251) THE ICC LEGACY REPORT THAT HAS BEEN SUBMITTED IS
 UNACCEPTABLE. THE REPORT IS BASED ON THE 1997 UBC WHICH
 IS NOT RECCOGNIZED BY THE FBC AS A REFERENCED STANDARD.
 NOTE: THE SUBMITTED UL ASSEMBLY DESIGN IS ACCEPTABLE AS
 IT IS FOR A 2 HOUR ASSEMBLY IF THAT IS THE INTENT.
 2) THE HORIZONTAL SHAFT ENCAPSULATING THE DRAIN LINES
 SHALLL BE 2 HOUR RATED. DRAWINGS 13A-A & 13A-B SHOW THE
 SHAFT AS 1 HOUR RATED. CLARIFY.
 3) THE SUBMITTED NARRATIVE STATES THAT SHAFT ENCLOSURES
 CONNECTING LESS THAN 4 STORIES REQUIRE A 1 HOUR RATING
 WHICH IS CORRECT BUT THIS STRUCTURE IS 8 STORIES.
 PLEASE CLARIFY THIS RESPONSE.
 4) THE NARRATIVE ALSO REFERS TO FBC SEC. 406.3.5 FOR
 ALLOWING A 1 HOUR ROOF RATING. THIS SECTION IS FOR AREA
 & HEIGHT IN THE 2010 FBC AND DOES NOT REFER TO ANY
 HOURLY RATING. CLARIFY.
 5) THE NARRATIVE ALSO REFERS TO SEC. 713.4.2.1 OF THE
 FBC - THIS SECTION IN THE 2010 FBC REFERS TO
 NONCOMBUSTIBLE PENETRATING ITEMS THAT CONNECT NOT MORE
 THAN THREE STORIES ARE PERMITTED. THIS SECTION APPLIES
 TO NONFIRE - RESISTANCE RATED ASSEMBLIES. CLARIFY HOW
 THIS APPLIES TO THIS ISSUE WHEN THE STAIR ENCLOSURE IS
 A 2 HOUR RATED ENCLOSURE.
 6) THE NARRATIVE ALSO REFERS TO FBC SEC.708.4 WHICH
 REFERS TO THE FIRE RATING OF SHAFT ENCLOSURES. THIS
 STRUCTURE IS 8 STORIES AND REQUIRES A 2 HOUR RATING FOR
 THE THE HORIZONTAL SHAFT ENCLOSURE.
 AT THIS POINT DUE TO THE DISCRPANCIES IN THE SUBMITTED
 DOCUMENTS I HAVE NO IDEA IF YOUR DESIGN IS GOING TO BE
 2 HOUR RATED OR IF YOU ARE STILL ATTEMPTING TO GET A 1
 HOUR RATING APPROVED WHICH DOES NOT MEET CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By tklarge Date 2017-03-14 Time 12:17 Rev Time 0.00
Received By tklarge Date 2017-03-14 Time 11:41 Sent To  
Notes
2017-03-14 12:00:581) INDICATE THE REQUIRED FIRE RATING OF THE STAIRWAY ON
 THE DRAWINGS.FROM THE ORIGINAL DRAWINGS THIS IS A 2
 HOUR RATED STAIRWAY.
 2) INDICATE THE FIRE RATING OF THE ENCLOSURE FOR THE
 PIPING ON THE DRAWINGS. THE DRAWINGS NOTE 2 LAYERS OF
 5/8 INCH TYPE X DRYWALL ON METAL STUD FRAMING WHICH
 WOULD PROVIDE AN 80 MINUTE FIRE RATING WHICH IS LESS
 THAN THE 2 HOUR RATING OF THE ENCLOSURE.THIS PIPING
 ENCLOSURE SHALL BE THE SAME RATING AS THE ENCLOSURE IN
 WHICH IT IS LOCATED.FBC 713..4, 713.5.
 3) INDICATE THE GAUGE OF THE METAL STUDS BEING USED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  