Plan Review Details - Permit 17030460
Plan Review Stops For Permit 17030460
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-28 Cont ID  
Sent By jwitmer Date 2017-07-28 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2017-07-28 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By jwitmer Date 2017-03-17 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-03-17 Time 06:49 Sent To  
Notes
2017-03-17 07:15:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030460
 ADD: 105 S. NARCUSSUS ST. SUITE # 130
 CONT: TBD
 TEL: 786-260-8944
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 17/ 2017
 ACTION: DENIED
  
 1) THE VALUE OF $1,000 DOLLARS IS LOW FOR THE WORK
 SHOWN. THE SHEET D-1 IS THE ONLY ARCHITECTURAL SHEET IN
 THE SET OF PLANS. W P B ADMINISTRATIVE CODE 108.2
 SCHEDULE OF PERMIT FEES. ON BUILDINGS, STRUCTURES,
 ELECTRICAL, GAS, MECHANICAL AND PLUMBING SYSTEMS OR
 ALTERATIONS REQUIRING A PERMIT, A FEE FOR EACH PERMIT
 SHALL BE PAID AS REQUIRED, IN ACCORDANCE WITH THE
 SCHEDULE ESTABLISHED BY THE APPLICABLE GOVERNING
 AUTHORITY. 108.3* BUILDING PERMIT VALUATION.
  
 2) SHEET D-1 DOES NOT SHOW COMPLIANCE WITH 2014
 FBC-ACCESS. CODE 904.3.2 COUNTER.THE COUNTER SURFACE
 HEIGHT SHALL BE 38 INCHES (965 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. THE TOP OF THE COUNTER EDGE
 PROTECTION SHALL BE 2 INCHES (51 MM) MAXIMUM ABOVE THE
 TOP OF THE COUNTER SURFACE ON THE AISLE SIDE OF THE
 CHECK-OUT COUNTER.
  
 3) SHEET D-1 DOES NOT SHOW COMPLIANCE WITH 2014
 FBC-ACCESS. CODE 226.1. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 4) SHEET D-1 DOES NOT SHOW COMPLIANCE WITH 2014
 FBC-ACCESS. CODE 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 4A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By jpearson Date 2017-07-27 Time 11:41 Rev Time 0.00
Received By jpearson Date 2017-07-27 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By vperez Date 2017-03-20 Time 10:06 Rev Time 0.00
Received By vperez Date 2017-03-20 Time 10:06 Sent To  
Notes
2017-03-20 10:07:54PLEASE ADDRESS FIRE, BUILDING AND MECHANICAL COMMENTS
 FOR A COMPLETE ELECTRICAL APPOVAL. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-28 Cont ID  
Sent By pleduc Date 2017-07-28 Time   Rev Time 0.00
Received By pleduc Date 2017-07-28 Time 10:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By pleduc Date 2017-03-14 Time   Rev Time 0.00
Received By pleduc Date 2017-03-13 Time 16:10 Sent To  
Notes
2017-03-14 10:59:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1)
 SHEET EQ 1 - A NOTE INDICATING A PIZZA OVEN, A HOOD AND
 NEW EQUIPMENT IS TO BE INSTALLED.
  
 THE PIZZA HOOD SHALL BE INSTALLED UNDER SEPARATE SHOP
 DRAWINGS.
  
  
  
 2)
 SHEET EQ 1 - THERE IS NO INDICATIONS OF ANY EXISTING
 FIRE SPRINKLER AND/OR FIRE ALARM DEVICES OR EQUIPMENT.
  
 ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 15:34 Sent To  
Notes
2017-07-27 15:34:19GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-25 Time 12:41 Sent To  
Notes
2017-07-26 12:41:36B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By vperez Date 2017-03-20 Time 10:08 Rev Time 0.00
Received By vperez Date 2017-03-20 Time 10:08 Sent To  
Notes
2017-03-13 11:13:37B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-07-28 Cont ID  
Sent By ccole Date 2017-07-28 Time 17:29 Rev Time 0.00
Received By ccole Date 2017-07-28 Time 17:29 Sent To  
Notes
2017-07-28 17:38:57MECHANICAL PROVISO:
  
 SEPARATE PERMITS REQUIRED FOR GAS, GAS COOKING
 APPLIANCES, PIZZA OVEN, EXHAUST HOOD AND DUCT, FIRE
 SUPPRESSION AND ANY OTHER MECHANICAL ALTERATIONS.
  
 CCOLE- 7/28/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 16:08 Rev Time 0.00
Received By ccole Date 2017-03-14 Time 16:03 Sent To  
Notes
2017-03-14 16:24:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030460
 3/14/17
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PIZZA
 OVEN- SECTION 623.1 FBC-14 FUEL GAS.
  
 2) INDICATE HOW COMBUSTION AIR IS TO BE SUPPLIED TO THE
 PIZZA OVEN AND PROVIDE A CALCULATION- SECTION 304
 FBC-14 FUEL GAS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE OVEN HOOD AND
 FIRE SUPPRESSION SYSTEM IF REQUIRED. PLEASE PLACE A
 NOTE ON THE PLAN.
  
 4) PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, AND EQUIPMENT. THE $1000.00 VALUE ON THE
 APPLICATION APPEARS TO BE UNDERVALUED FOR THE SCOPE OF
 THE PROJECT. PLEASE PROVIDE AN ACCURATE VALUE THAT
 REFLECTS THE FULL SCOPE OF THE PROJECT INCLUDING THE
 NEW FOOD SERVICE EQUIPMENT AND THEIR INSTALLATIONS-
 SECTION 109.3 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 15:32 Sent To  
Notes
2017-07-27 15:33:01FIXTURES ONLY NO ROUGH PLUMBING/GPJ

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-15 Cont ID  
Sent By gjohnson Date 2017-03-15 Time 13:04 Rev Time 0.00
Received By gjohnson Date 2017-03-15 Time 11:40 Sent To  
Notes
***NONE***