| 2017-03-22 11:31:19 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030455 | | | 3/22/17 | | | | | | 1) THE NEW CONDENSER UNIT MUST MATCH WITH THE EXISTING | | | AIR HANDLER AND THE MATCH MUST BE VERIFIED BY | | | SUBMITTING AN AHRI CERTIFICATE, OR MANUFACTURER'S | | | LETTER- SEE SECTION C101.4.7 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR | | | TIE-DOWN OF THE NEW ROOFTOP CONDENSER PER SECTION | | | 301.15 FBC-14 MECHANICAL AND SECTION 1609 FBC-14 | | | BUILDING. THE SUBMITTED PRODUCT APPROVAL FOR THE BMP | | | CLIP IS INCOMPLETE- PLEASE PROVIDE THE COVER SHEETS, | | | AND MARK ALL APPLICABLE NOTES, DETAILS, DESIGN | | | PRESSURES, AND CLIP SIZES ON THE INSTALLATION | | | INSTRUCTIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|