2017-03-22 12:01:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030451
 3/22/17
  
 1) SITE SPECIFIC ENGINEERING IS REQUIRED FOR TIE-DOWN
 OF THE RTU'S AND CURBS- SECTION 301.15 FBC-14
 MECHANICAL, AND 1609 FBC-14 BUILDING.
  
 2) COMMISSIONING OF THE NEW AC SYSTEMS IS REQUIRED IN
 COMPLIANCE WITH SECTION 408.2 FBC-14 ENERGY COMPLIANCE.
 PLEASE SUBMIT A COMMISSIONING PLAN AS OUTLINED IN
 SECTION C408.2.1.
  