Plan Review Details - Permit 17030449
Plan Review Stops For Permit 17030449
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 06:47 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 06:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-18 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2017-05-12 Time   Sent To  
Notes
2017-05-12 07:51:59BLDG. # 3. PLANS WILL NOT BE STAMPED UNTIL ALL 3
 BUILDINGS CAN MEET CODE COMPLIANCE.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-18 Cont ID  
Sent By jwitmer Date 2017-03-18 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2017-03-18 Time 11:55 Sent To  
Notes
2017-03-18 11:56:49BLDG. # 3. PLANS WILL NOT BE STAMPED UNTIL ALL 3
 BUILDINGS CAN MEET CODE COMPLIANCE.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 09:33 Rev Time 0.00
Received By jpearson Date 2017-05-31 Time 09:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By vperez Date 2017-03-14 Time 13:27 Rev Time 0.00
Received By rlecky Date 2017-03-14 Time 13:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By wjolin Date 2017-06-06 Time 11:11 Rev Time 0.00
Received By wjolin Date 2017-06-06 Time 10:53 Sent To  
Notes
2017-06-06 11:10:491851 DIVISION AVENUE
 TRACKING #17030449
 PERMIT #15050262
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 06/14/17 UPDATE: PROJECT TEAM HAS AGREED (PER PHONE
 CONVERSATION) TO SUBMIT ALL APPROPRIATE DECORATIVE GAS
 FIREPLACE LISTING AND INSTALLATION INFORMATION FOR FIRE
 DEPARTMENT APPROVAL PRIOR TO INSTALLATION.
  
  
 PREVIOUS REVIEW COMMENTS NOT ADDRESSED:
 REPEAT COMMENT - SUBMIT EQUIPMENT SPECIFICATIONS,
 LISTING INFORMATIN AND INSTALLATION INFORMATION FOR THE
 FIREPLACE APPLIANCE.
  
 REPEAT COMMENT - INDICATE IF THE FIREPLACE IS A
 CATEGORY I, II, III OR IV VENTED APPLIANCE IN
 ACCORDANCE WITH NFPA 54.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-22 Cont ID  
Sent By wjolin Date 2017-03-22 Time 16:11 Rev Time 0.00
Received By wjolin Date 2017-03-22 Time 15:13 Sent To  
Notes
2017-03-22 16:11:491851 DIVISION AVENUE
 TRACKING #17030449
 PERMIT #15050262
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMIT EQUIPMENT SPECIFICATIONS, LISTING INFORMATIN AND
 INSTALLATION INFORMATION FOR THE FIREPLACE APPLIANCE.
  
 INDICATE IF THE FIREPLACE IS A CATEGORY I, II, III OR
 IV VENTED APPLIANCE IN ACCORDANCE WITH NFPA 54.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 10:19 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 10:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By gjohnson Date 2017-04-12 Time 14:45 Rev Time 0.00
Received By gjohnson Date 2017-04-12 Time 14:23 Sent To  
Notes
2017-04-12 14:44:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR FIRE
 PLACE. PER FBC FG 304
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT MANUFACTURE INSTILLATION GUIDE FOR THE FIRE
 PLACE VENT. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P-4.05 THE TOTAL BTU LOAD IS LISTED AS
 4,650,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 33 @ 150,00 = 4,950,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. P-4.06 THE TOTAL BTU LOAD IS LISTED AS
 4,850,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 35 @ 150,00 = 5,250,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-06 Cont ID  
Sent By jroach Date 2017-06-06 Time 16:04 Rev Time 0.00
Received By jroach Date 2017-05-22 Time 14:59 Sent To  
Notes
2017-05-23 14:59:16C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-23 Cont ID  
Sent By lmarchan Date 2017-05-23 Time 14:59 Rev Time 0.00
Received By lmarchan Date 2017-05-02 Time 12:11 Sent To  
Notes
2017-05-02 12:11:20C34 FEES NEED TO BE PAID.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By gjohnson Date 2017-04-12 Time 14:46 Rev Time 0.00
Received By gjohnson Date 2017-03-10 Time 08:05 Sent To  
Notes
2017-03-13 08:06:07C03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-30 Cont ID  
Sent By ccole Date 2017-05-30 Time 11:52 Rev Time 0.00
Received By ccole Date 2017-05-30 Time 11:52 Sent To  
Notes
2017-05-30 11:52:29MECHANICAL PROVISOS
 5/30/17
  
 1) CLOTHES DRYER EXHAUST DUCTS SHALL NOT EXTEND INTO OR
 THROUGH DUCTS OR PLENUMS- SECTION 504.4 FBC-14
 MECHANICAL.
  
 2) GAS WATER HEATERS AND VENTS:
 503.3.5 AIR DUCTS AND FURNACE PLENUMS.
 VENTING SYSTEMS SHALL NOT EXTEND INTO OR PASS THROUGH
 ANY FABRICATED AIR DUCT OR FURNACE PLENUM.
  
 503.3.6 ABOVE-CEILING AIR-HANDLING SPACES.
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NONDUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1. THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
  
 2. THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
  
 3. THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT
 OR ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR
 OF THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE.
  
 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE GAS FIREPLACE AND VENTING IN THE
 CLUBROOM SHALL BE ONSITE AT TIME OF INSPECTION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 15:25 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 15:25 Sent To  
Notes
2017-05-08 15:25:271ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030449
 5/8/17
  
 RESULT: DENIED
  
 1) THE REQUESTED MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW GAS FIREPLACE AND VENTING SYSTEM WERE NOT
 SUBMITTED- PLEASE COMPLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By ccole Date 2017-03-20 Time 09:54 Rev Time 0.00
Received By ccole Date 2017-03-20 Time 09:54 Sent To  
Notes
2017-03-20 09:54:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030449
 3/20/17
  
 1) SHEET M-100B: A NEW AC SYSTEM- AC-4A IS SHOWN.
 PLEASE ADD THE SYSTEM TO THE AC EQUIPMENT SCHEDULE ON
 SHEET M-300.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2017-06-06 Time 08:45 Sent To  
Notes
2017-06-06 08:46:29 
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By tklarge Date 2017-04-12 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2017-04-12 Time 09:52 Sent To  
Notes
2017-04-12 14:22:171ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IT IS UNCLEAR WHAT PLUMBING IS BEING REVISED PLEASE
 CLOUD ALL REVISIONS ON THE PLAN AND PROVIDE A NARRATIVE
 THAT LIST THE PAGE NUMBERS AND REVISION NUMBER AND WHAT
 IS BE REVISED. PER WPB AMEND. TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By jroach Date 2017-06-06 Time 16:03 Rev Time 0.00
Received By jroach Date 2017-06-06 Time 16:03 Sent To  
Notes
2017-06-06 16:04:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2017
 PERMIT NO.: 15050261, 15050262, AND 15050263
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 2. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-29 Cont ID  
Sent By jroach Date 2017-03-29 Time 15:08 Rev Time 0.00
Received By jroach Date 2017-03-29 Time 15:04 Sent To  
Notes
2017-03-29 15:09:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.29.2017
 PERMIT NO.: 15050261, 15050262, AND 15050263
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 2. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  