Plan Review Details - Permit 17030448
Plan Review Stops For Permit 17030448
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 06:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2017-05-12 Time 07:15 Sent To  
Notes
2017-05-12 07:48:40BUILDING PLAN REVIEW
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2/ 2010 TYPE I-B
 W. P. B. REVISION: 17030448
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK CONSTRUCTION
 CONTACT: CHARLES ROBERSON
 TEL: 305-665-1146
 E-MAIL: ??????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. MAY 12/2017
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2A) 2ND REQUEST. SHEET A-3.00 NOTES 6 & 10 INDICATE THE
 USE OF PRE-FABRICATED DECORATIVE FOAM OUTLOOKERS AT
 ELEVATION 46FOOT ? 8INCHES. IT HAS RECENTLY BROUGHT TO
 MY ATTENTION THAT FOR FOAM (EFIS) THE CODE SECTION
 1406.2 EXCEPTION: PLASTIC COMPLYING WITH CHAPTER 26. IN
 CHAPTER 26 EFIS. THE EFIS TRIM WILL NEED TO SHOW
 COMPLIANCE WITH 2603.5. EXTERIOR WALLS OF BUILDINGS OF
 TYPE I, II, III OR IV CONSTRUCTION OF ANY HEIGHT SHALL
 COMPLY WITH SECTIONS 2603.5.1 THROUGH 2603.5.7.
 SATISFYING THIS COMMENT ELIMINATES COMMENTS 2B-2E.
  
 COMMENTS FROM 1ST REVIEW. PLEASE REVIEW IN THE 2010
 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE. IN THE 2009 IBC-B COMMENTARY
 IT STATES: ALL EXTERIOR TRIM AND VENEERS ON BUILDINGS
 OF TYPE I, II III AND IV CONSTRUCTION THAT ARE MORE
 THAN 40 FEET ABOVE THE GRADE ARE REQUIRED TO BE
 NON-COMBUSTIBLE.
  
  
 2B) PLEASE IDENTIFY WHERE THE USE OF THE SMOOTH FOAM
 BRACKETS ARE TO BE LOCATED ON THE BUILDING SEE NOTE
 NUMBER 10. THE 2010 FBC-B SECTION 1406.2.1 (2) 2.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 2C) SHEET A-3.00 NOTE 17 STATES PRE-FABRICATED
 DECORATIVE BRACKETS BUT THE PLANS DO NOT SPECIFY THE
 TYPE OF MATERIALS. ELEVATION A DOES SHOW THE USE OF
 DECORATIVE BRACKET TYPE 17 ABOVE 40 FEET ABOVE GRADE.
 2010 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR
 WALL COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE.
  
  
 2D) SHEET A-3.04 DETAIL 10 FOAM BRACKET AT ROOF LINE
 THE DIMENSIONS INDICATED AND THE SCALE 1 INCH = 1 FOOT
 DOES NOT MATCH UP? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 2E) SHEET A-4.2 DETAILS 2 & 3 BOTH SHOW THE USE OF FOAM
 BRACKETS ABOVE THE 40 FOOT FROM GRADE LEVEL. 2010 FBC-B
 SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-18 Cont ID  
Sent By jwitmer Date 2017-03-18 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2017-03-18 Time 10:09 Sent To  
Notes
2017-03-18 11:49:11 
 BUILDING PLAN REVIEW
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2/ 2010 TYPE I-B
 W. P. B. REVISION: 17030448
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK CONSTRUCTION
 CONTACT: CHARLES ROBERSON
 TEL: 305-665-1146
 E-MAIL: ??????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. MARCH 18/2017
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 1) PLEASE PROVIDE YOUR E-MAIL ADDRESS; WE USE YOUR
 E-MAIL ADDRESS FOR CORRESPONDENCE IN THE FORM OF A
 WRITTEN RECORD. 107.2.1.4 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 RECORD RETENTION PROGRAM.
  
 2A) SHEET A-3.00 NOTES 6 & 10 INDICATE THE USE OF
 PRE-FABRICATED DECORATIVE FOAM OUTLOOKERS AT ELEVATION
 46?-8?. PLEASE REVIEW IN THE 2010 FBC-B SECTION
 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL COVERINGS
 SHALL BE LIMITED TO 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE. IN THE 2009 IBC-B COMMENTARY IT STATES:
 ALL EXTERIOR TRIM AND VENEERS ON BUILDINGS OF TYPE I,
 II III AND IV CONSTRUCTION THAT ARE MORE THAN 40 FEET
 ABOVE THE GRADE ARE REQUIRED TO BE NON-COMBUSTIBLE.
  
 2B) PLEASE IDENTIFY WHERE THE USE OF THE SMOOTH FOAM
 BRACKETS ARE TO BE LOCATED ON THE BUILDING SEE NOTE
 NUMBER 10. THE 2010 FBC-B SECTION 1406.2.1 (2) 2.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 2C) SHEET A-3.00 NOTE 17 STATES PRE-FABRICATED
 DECORATIVE BRACKETS BUT THE PLANS DO NOT SPECIFY THE
 TYPE OF MATERIALS. ELEVATION A DOES SHOW THE USE OF
 DECORATIVE BRACKET TYPE 17 ABOVE 40 FEET ABOVE GRADE.
 2010 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR
 WALL COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE.
  
  
 2D) SHEET A-3.04 DETAIL 10 FOAM BRACKET AT ROOF LINE
 THE DIMENSIONS INDICATED AND THE SCALE 1 INCH = 1 FOOT
 DOES NOT MATCH UP? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 2E) SHEET A-4.2 DETAILS 2 & 3 BOTH SHOW THE USE OF FOAM
 BRACKETS ABOVE THE 40 FOOT FROM GRADE LEVEL. 2010 FBC-B
 SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 09:30 Rev Time 0.00
Received By jpearson Date 2017-05-31 Time 09:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By rlecky Date 2017-03-14 Time 12:48 Rev Time 0.00
Received By rlecky Date 2017-03-14 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-14 Cont ID  
Sent By wjolin Date 2017-06-06 Time 11:12 Rev Time 0.00
Received By wjolin Date 2017-06-06 Time 10:52 Sent To  
Notes
2017-06-06 11:12:49838 ADAMS STREET
 TRACKING #17030448
 PERMIT #15050261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 06/14/17 UPDATE: PROJECT TEAM HAS AGREED (PER PHONE
 CONVERSATION) TO SUBMIT ALL APPROPRIATE DECORATIVE GAS
 FIREPLACE LISTING AND INSTALLATION INFORMATION FOR FIRE
 DEPARTMENT APPROVAL PRIOR TO INSTALLATION.
  
  
 PREVIOUS REVIEW COMMENTS NOT ADDRESSED:
 REPEAT COMMENT - SUBMIT EQUIPMENT SPECIFICATIONS,
 LISTING INFORMATIN AND INSTALLATION INFORMATION FOR THE
 FIREPLACE APPLIANCE.
  
 REPEAT COMMENT - INDICATE IF THE FIREPLACE IS A
 CATEGORY I, II, III OR IV VENTED APPLIANCE IN
 ACCORDANCE WITH NFPA 54.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-06-05 Cont ID  
Sent By gjohnson Date 2017-06-05 Time 17:22 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 17:22 Sent To  
Notes
2017-06-05 17:24:39GAS PROVISO :
  
 1. MANUFACTURE SPECS AND INSTALLATION GUIDE SHALL BE ON
 JOBSITE FOR INSPECTION.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 09:35 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 09:35 Sent To  
Notes
2017-05-11 09:38:502ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 PREVIOUS COMMENTS HAVE NOT BEEN COMPLIED WITH.THE
 RESPONSE LETTER STATES THEY WERE ATTACHED I COULD NOT
 LOCATE THEM.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT MANUFACTURE INSTILLATION GUIDE FOR THE FIRE
 PLACE VENT. PER WPB AMEND TO FBC 107.2.1
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By gjohnson Date 2017-04-12 Time 14:55 Rev Time 0.00
Received By gjohnson Date 2017-04-12 Time 14:55 Sent To  
Notes
2017-04-12 14:56:271ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GASCOMMENTS:
  
 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR FIRE
 PLACE. PER FBC FG 304
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT MANUFACTURE INSTILLATION GUIDE FOR THE FIRE
 PLACE VENT. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P-4.05 THE TOTAL BTU LOAD IS LISTED AS
 4,650,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 33 @ 150,00 = 4,950,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. P-4.06 THE TOTAL BTU LOAD IS LISTED AS
 4,850,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 35 @ 150,00 = 5,250,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-06 Cont ID  
Sent By jroach Date 2017-06-06 Time 16:03 Rev Time 0.00
Received By jroach Date 2017-05-22 Time 14:53 Sent To  
Notes
2017-05-23 14:53:50C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2017-05-02 Time 12:07 Sent To  
Notes
2017-05-02 12:10:18C34 FEES NEED TO BE PAID.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By gjohnson Date 2017-04-12 Time 14:56 Rev Time 0.00
Received By gjohnson Date 2017-03-10 Time 17:30 Sent To  
Notes
2017-03-10 17:31:31C03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-30 Cont ID  
Sent By ccole Date 2017-05-30 Time 11:50 Rev Time 0.00
Received By ccole Date 2017-05-30 Time 10:31 Sent To  
Notes
2017-05-30 11:51:55MECHANICAL PROVISOS
 5/30/17
  
 1) CLOTHES DRYER EXHAUST DUCTS SHALL NOT EXTEND INTO OR
 THROUGH DUCTS OR PLENUMS- SECTION 504.4 FBC-14
 MECHANICAL.
  
 2) GAS WATER HEATERS AND VENTS:
 503.3.5 AIR DUCTS AND FURNACE PLENUMS.
 VENTING SYSTEMS SHALL NOT EXTEND INTO OR PASS THROUGH
 ANY FABRICATED AIR DUCT OR FURNACE PLENUM.
  
 503.3.6 ABOVE-CEILING AIR-HANDLING SPACES.
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NONDUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1. THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
  
 2. THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
  
 3. THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT
 OR ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR
 OF THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE.
  
 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE GAS FIREPLACE AND VENTING IN THE
 CLUBROOM SHALL BE ONSITE AT TIME OF INSPECTION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 15:24 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 15:24 Sent To  
Notes
2017-05-08 15:24:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030448
 5/8/17
  
 RESULT: DENIED
  
 1) THE REQUESTED MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW GAS FIREPLACE AND VENTING SYSTEM WERE NOT
 SUBMITTED- PLEASE COMPLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By ccole Date 2017-03-20 Time 09:05 Rev Time 0.00
Received By ccole Date 2017-03-20 Time 07:27 Sent To  
Notes
2017-03-20 09:53:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030448
 3/20/17
  
 1) SHEET M-100B: A NEW AC SYSTEM- AC-4A IS SHOWN.
 PLEASE ADD THE SYSTEM TO THE AC EQUIPMENT SCHEDULE ON
 SHEET M-300.
  
 2) M-2.02: SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE
 GAS FIREPLACE AND VENT SYSTEM, AND INDICATE HOW
 CIOMBUSTION AIR IS BEING PROVIDED PER SECTION 304 FUEL
 GAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-05 Time 17:21 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 17:21 Sent To  
Notes
2017-06-05 17:22:42 
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 09:18 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 09:18 Sent To  
Notes
2017-05-11 09:35:161ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHTS. P- 2.00, 2.01, 2.02, 2.03, 2.04, 2.05 ARE
 DRAWN TO SMALL I HAD TO USE A MAGNIFYING GLASS TO READ
 COMBUSTION AIR CALCULATIONS ALL DRAWING SHALL BE A MIN
 OF 1/8" PER FT. WPB AMEND TO FBC 107.2.1.4 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By tklarge Date 2017-04-12 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2017-04-12 Time 14:53 Sent To  
Notes
2017-04-12 14:53:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IT IS UNCLEAR WHAT PLUMBING IS BEING REVISED PLEASE
 CLOUD ALL REVISIONS ON THE PLAN AND PROVIDE A NARRATIVE
 THAT LIST THE PAGE NUMBERS AND REVISION NUMBER AND WHAT
 IS BE REVISED. PER WPB AMEND. TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By jroach Date 2017-06-06 Time 16:02 Rev Time 0.00
Received By jroach Date 2017-06-06 Time 16:02 Sent To  
Notes
2017-06-06 16:03:14ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2017
 PERMIT NO.: 15050261, 15050262, AND 15050263
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 2. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-29 Cont ID  
Sent By jroach Date 2017-03-29 Time 15:10 Rev Time 0.00
Received By jroach Date 2017-03-29 Time 15:03 Sent To  
Notes
2017-03-29 15:10:46ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.29.2017
 PERMIT NO.: 15050261, 15050262, AND 15050263
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 2. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved