Plan Review Details - Permit 17030415
| Plan Review Stops For Permit 17030415 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-03-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-23 |
Time |
05:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-23 |
Time |
05:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-03-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-11 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-11 |
Time |
05:04 |
Sent To |
|
|
| Notes |
| 2017-03-11 07:38:14 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR.COMPLY WITH | | | 2014 FBC-FUEL GAS SEC.304.1. | | | 2) A CSA INTERNATIONAL DESIGN CERTIFIED DOWN DRAFT | | | DIVERTER MUST BE INSTALLED AT THE FLUE OUTLET OF THE | | | OVEN AND CONNECTED TO THE OUTSIDE FLUE PER THE | | | MANUFACTURER'S INSTALLATION MANUAL, PAGE 6 OF 44. | | | 3) PAGE 6 OF THE MANUFACTURER'S MANUAL STATES THAT | | | ELECTRICITY IS REQUIRED. A SEPARATE PERMIT WILL BE | | | REQUIRED FOR THE ELECTRIC. WPB AMEND. TO FBC SEC,105.1. | | | 4) TYPE "B" VENTS SHALL BE LISTED AND LABELED AND | | | TESTED IN ACCORDANCE WITH UL 441. | | | 5) SUBMIT A DETAIL AS TO HOW THE WALL PENETRATION FOR | | | THE VENT WILL BE MADE WATERTIGHT.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 6) SUBMIT AN ANCHORING DETAIL FOR THE GAS VENT. 2014 | | | FBC-FUEL GAS SEC. 502.6. | | | 7) THE VENT TERMINUS SHALL BE EQUIPPED WITH A LISTED | | | CAP/ LISTED ROOF ASSEMBLY. 2014 FBC-FUEL GAS | | | SEC.503.6.6. | | | 8) INDICATE THE VENTED APPLIANCE CATEGORY FOR THIS | | | APPLIANCE. THIS INFORMATION SHOULD BE OBTAINABLE FROM | | | THE MANUFACTURER.THIS INFO WILL BE BENEFICIAL FOR THE | | | REVIEW.WPB AMEND. TO FBC SEC.107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-23 |
Time |
05:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-21 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2017-03-22 10:04:42 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-11 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-10 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2017-03-10 16:27:29 | PLUMB -$5000 |
|
|
|