Plan Review Details - Permit 17030383
Plan Review Stops For Permit 17030383
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-13 Cont ID  
Sent By hmoser Date 2017-04-13 Time 14:37 Rev Time 0.00
Received By hmoser Date 2017-04-11 Time 11:14 Sent To  
Notes
2017-04-12 11:14:51RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By hmoser Date 2017-03-23 Time 13:53 Rev Time 0.00
Received By hmoser Date 2017-03-09 Time 14:54 Sent To  
Notes
2017-03-09 14:54:09MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-13 Cont ID  
Sent By hmoser Date 2017-04-13 Time 14:36 Rev Time 0.00
Received By hmoser Date 2017-04-13 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By hmoser Date 2017-03-23 Time 13:53 Rev Time 0.00
Received By hmoser Date 2017-03-23 Time 13:33 Sent To  
Notes
2017-03-23 13:53:42PLAN DENIED
 1) PROVIDE GRILL SIZE AND CFM AT EACH SUPPLY GRILL.
 SECTION 107
 CITY AMENDMENTS 2010
 2) PROVIDE A SIGNATURE ON THE PLAN FROM WHO EVER DREW
 THE PLAN
 AND LICENSE NUMBER. SECTION 107.2.1 CITY AMENDMENTS
 2010
 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR. 2014
 FBC RESIDENTIAL CODE
 4) PROVIDE EQUIPMENT SCHEDULE ON THE PLAN.
 5) TWO COPY'S OF LOT SERVE SHOWING THE DISTANCE FROM
 PROPERTY
 LINE TO CONDENSER
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 651-805-6676