Plan Review Details - Permit 17030346
Plan Review Stops For Permit 17030346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-17 Cont ID  
Sent By cthroop Date 2017-07-17 Time 16:22 Rev Time 0.00
Received By cthroop Date 2017-07-17 Time 16:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By cthroop Date 2017-06-29 Time 16:14 Rev Time 0.00
Received By cthroop Date 2017-06-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By cthroop Date 2017-04-18 Time 12:11 Rev Time 0.00
Received By cthroop Date 2017-04-18 Time 07:12 Sent To M
Notes
2017-04-18 13:12:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOTE - DEMO PERMIT 17031167.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE LANDINGS AT EXTERIOR DOORS.
 4. PROVIDE LOT DRAINAGE INFO ON SITE PLAN.
 5. DESIGN USES A CLOSED ATTIC SYSTEM - PROVIDE AN
 ICC-ES REPORT (ESR-1826) FOR THE ICYNENE INSULATION
 SYSTEM. IDENTIFY PROPOSED ICYNENE PRODUCT TO BE
 INSTALLED. PROVIDE PRODUCT APPROVALS, REVIEWED AND
 APPROVED BY DESIGNER FOR PROPOSED PRODUCT.
 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 MODULAR FIREPLACE AND GAS GRILL.
 7. PALM BEACH COUNTY IMPACT FEES REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 R311.3.1 FLOOR ELEVATIONS AT THE REQUIRED EGRESS DOORS.
 LANDINGS OR FINISHED FLOORS AT THE REQUIRED EGRESS DOOR
 SHALL NOT BE MORE THAN 11/2 INCHES (38 MM) LOWER THAN
 THE TOP OF THE THRESHOLD. EXCEPTION: THE LANDING OR
 FLOOR ON THE EXTERIOR SIDE SHALL NOT BE MORE THAN 73/4
 INCHES (196 MM) BELOW THE TOP OF THE THRESHOLD
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-17 Cont ID  
Sent By jleahy Date 2017-07-17 Time 16:16 Rev Time 0.00
Received By jleahy Date 2017-07-17 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 07:06 Rev Time 0.00
Received By jleahy Date 2017-06-26 Time 07:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-24 Cont ID  
Sent By jleahy Date 2017-03-24 Time 07:16 Rev Time 0.00
Received By jleahy Date 2017-03-23 Time 15:50 Sent To  
Notes
2017-03-24 07:17:57PROVISO FOR PLANS 3/24/17
  
 1) SUBMIT A PANEL SCHEDULE SHOWING OCP FOR EACH
 CIRCUIT.
 2) SMOKE ALARMS ADDED TO MSTR BDROOM
 3) OUTLETS ADDED TO SLIDING GLASS DOORS.
  
 JAKE LEAHY
 561-805-6713

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 15:28 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-06-20 Cont ID  
Sent By gjohnson Date 2017-06-20 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 14:59 Sent To  
Notes
2017-06-20 15:06:22GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-17 Cont ID  
Sent By cthroop Date 2017-07-17 Time 16:21 Rev Time 0.00
Received By cthroop Date 2017-06-30 Time 15:32 Sent To  
Notes
2017-06-30 15:43:23R29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-29 Cont ID  
Sent By skennedy Date 2017-06-29 Time 16:45 Rev Time 0.00
Received By skennedy Date 2017-06-07 Time 15:53 Sent To  
Notes
2017-06-08 15:53:57R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-18 Cont ID  
Sent By hmoser Date 2017-04-18 Time 14:36 Rev Time 0.00
Received By hmoser Date 2017-03-08 Time 11:00 Sent To  
Notes
2017-03-09 11:01:00R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-07-19 Cont ID  
Sent By cthroop Date 2017-07-19 Time 17:02 Rev Time 0.00
Received By cthroop Date 2017-07-19 Time 17:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By cthroop Date 2017-04-18 Time 09:32 Rev Time 0.00
Received By cthroop Date 2017-04-18 Time 07:12 Sent To  
Notes
2017-04-18 09:33:21BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By skennedy Date 2017-06-29 Time 16:45 Rev Time 0.00
Received By skennedy Date 2017-06-29 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By hmoser Date 2017-04-18 Time 14:36 Rev Time 0.00
Received By hmoser Date 2017-04-18 Time 14:26 Sent To  
Notes
2017-04-18 14:36:42PLAN DENIED
 1) PLEASE SUBMIT A LARGER PLAN WITH EQUIPMENT SCHEDULE
 SHOW LOCATION OF RETURN AIR . PLAN TO SMALL TO READ.PER
 SECTION
 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 17:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By gjohnson Date 2017-06-20 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 13:06 Sent To  
Notes
2017-06-20 14:52:021ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. MISSING BAR SINK ON RISER DIAGRAM IT APPEARS THAT
 THE BAR SINK WAS CHANGED TO THE KITCHEN SINK. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE RISER DIAGRAM SHOWS BATH 2 WITH A TUB THE FLOOR
 PLAN SHOWS A SHOWER PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 2ND REQUEST LAVS IN MASTER AND POWDER ROOM NEED TO BE
 VENTED WASHING MACHINE AND LAUNDRY SINK NEEDS A VENT.
 PER FBC RES P3101.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 14:09 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 11:08 Sent To  
Notes
2017-03-17 14:43:551ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ALL THE LAVS NEED TO BE VENTED WASHING MACHINE AND
 LAUNDRY SINK NEEDS A VENT. PER FBC RES P3101.2.1
  
 2. THE KITCHEN IS NOT SHOWN ON RISER DIAGRAM PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE BRANCH DRAIN CONNECTING THE LAVS AND SHOWER AND
 TUB IN MASTER BATHROOM IS UNDER SIZED NO MORE THAN TWO
 FIXTURES CAN BE CONNECT TO 11/2" . PER FBC RES TABLE
 P3005.4.2 NOTE A
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By cthroop Date 2017-06-29 Time 16:02 Rev Time 0.00
Received By cthroop Date 2017-06-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By cthroop Date 2017-04-18 Time 09:33 Rev Time 0.00
Received By cthroop Date 2017-04-18 Time 07:25 Sent To  
Notes
2017-04-18 09:34:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By awooten Date 2017-06-14 Time 13:26 Rev Time 0.00
Received By awooten Date 2017-06-13 Time 11:45 Sent To  
Notes
2017-06-14 13:26:26***************ZONING REVIEW PASSED*******************
  
 LANDSCAPE PLAN SUBMITTED AND APPROVED.
  
 DRIVEWAY PERMIT SHALL BE SUBMITTED SEPARATELY.
  
 MAKE SURE THE SETBACKS ON APPROVED SITE PLAN WITH
 DRAINAGE ARE THE SAME AS THE SURVEY OF PROPOSED
 RESIDENCE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 [email protected]
 561-822-1449

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-15 Cont ID  
Sent By awooten Date 2017-03-15 Time 09:42 Rev Time 0.00
Received By awooten Date 2017-03-13 Time 14:49 Sent To  
Notes
2017-03-15 09:41:49THE DRIVEWAY WILL BE UNDER A SEPARATE PERMIT.
  
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPING ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PLAN SHOWING
 COMPLIANCE WITH LANDSCAPE CODE:
  
 SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 ALANA WOOTEN, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1449
 E-MAIL: [email protected]
  
  