Plan Review Details - Permit 17030344
Plan Review Stops For Permit 17030344
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 15:57 Rev Time 0.00
Received By shill Date 2017-04-25 Time 15:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-16 Cont ID  
Sent By jwitmer Date 2017-03-16 Time 14:30 Rev Time  
Received By jwitmer Date 2017-03-16 Time 11:55 Sent To  
Notes
2017-03-16 14:30:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030344
 ADD: 1500 FLORIDA MANGO ROAD SUITES 9A & 10
 CONT: MALASKY HOMES
 TEL: 561-471-8600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 16/ 2017
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET INDICATES THIS IS A S2
 OCCUPANCY AND THE OFFICE BEING AN ACCESSORY OCCUPANCY.
 WITH THE S2 OCCUPANCY DECLARED AS 5760 SQ. FT. AND THE
 BUSINESS/ OFFICE 1,419 SQ. FT. THE BUSINESS OCCUPANCY
 IS OVER 10 % OF THE FLOOR AREA, CLOSER TO 25% MAKING
 THIS A MIXED USE OCCUPANCY. SEE 2014 FBC-B 508.2.1 AREA
 LIMITATIONS. AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT
 OCCUPY MORE THAN 10 PERCENT OF THE BUILDING AREA.
  
 2) THE LIFE SAFETY PLAN INDICATES THE STORAGE OCCUPANCY
 TO BE AN S2. PLEASE LIST THE TYPES OF ARTICLES TO BE
 STORED IN THIS FACILITY CLASSIFYING IT AN S2 TYPE OF
 OCCUPANCY. FBC-B 311.3 LOW-HAZARD STORAGE- GROUP S-2.
  
 3) THE LIFE SAFETY SHEET SHOWS WHAT APPEARS TO BE A NEW
 OPENING BETWEEN THE 2 TENANT SPACES IDENTIFIED 9B AND
 UNIT 10. THIS IS AN OCCUPANCY SEPARATION WALL WHICH
 WOULD REQUIRE FIRE RATING FOUND IN FBC-B TABLE 508.4
 FOR FIRE SPRINKLERED BUILDINGS A 1 HOUR, SEE OPENING
 PROTECTIVES TABLE 716.5.
  
 4) SHEET A-1 DETAIL # 1 INDICATES THE ENCLOSING OF A 12
 FOOT HIGH 10 FOOT WIDE OVERHEAD DOOR OPENING. THIS SAME
 DETAIL HAS SECTION 1A & 2. THIS DETAIL IS NOT CLEAR AS
 TO THE METAL STUD HEADER. THE PLANS ARE SILENT TO THE
 SIZE OF THE STUDS, GAUGE OF METAL, YIELD STRENGTH, HOW
 THE BOXED HEADER WILL ATTACH TO THE (COLUMNS) MAIN WIND
 FORCE RESISTING SYSTEM? THE PLANS ALSO DO NOT PROVIDE
 THE SIZE OF THE EXTERIOR BEARING WALL STEEL STUD
 INFILL. 2014 FBC-B 2211.4 WALL STUD DESIGN.
  
 5) SHEET A-1 DETAIL # 1 PLEASE PROVIDE THE WIND DESIGN
 CRITERIA PER 2014 FBC-B 1603.1.4. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) THE MIAMI-DADE NOA 15-0618.01 3000 RESISTOR
 STOREFRONT WINDOW WALL SYSTEM WAS SUBMITTED. THIS IS
 FOR THE SIDELIGHTS ONLY!!! FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) SHEET MEP DETAILS 1, 2 & 3 ALL SHOW INSULATION LAID
 IN ON THE DROP CEILING, WHAT IS THIS INSULATION TO BE
 USED FOR? 2014 FBC-ENERGY C402.2.1 INSULATION INSTALLED
 ON A SUSPENDED CEILING WITH REMOVALABLE CEILING TILES
 SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL
 RESISTANCE OF THE ROOF INSULATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 15:20 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-24 Cont ID  
Sent By jleahy Date 2017-04-24 Time 15:22 Rev Time 0.00
Received By jleahy Date 2017-04-24 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By jleahy Date 2017-03-27 Time 16:23 Rev Time 0.00
Received By jleahy Date 2017-03-27 Time 13:12 Sent To  
Notes
2017-03-27 16:23:07JAKE LEAHY
 ELECTRICAL INSPECTOR II
 561-805-6713
 [email protected]
  
 FBCE C405.5.2.INTERIOR LIGHTING POWER. THE TOTAL
 INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS DETERMINED
 ACCORDING TO TABLE C405.5.2(1) USING THE BUILDING AREA
 METHOD, OR TABLE C405.5.2(2) USING THE SPACE-BY-SPACE
 METHOD, FOR ALL AREAS OF THE BUILDING COVERED IN THIS
 PERMIT.
  
 2011 NEC 210.5 (C)(3) CIRCXUIT NUMBERS ON PLANS
  
 2011 NEC 215.5 RISER DIAGRAM
  
 2011 NEC 422.52 DRINKING FOUNTAINS TO BE GFCI
 PROTECTED.
  
 PLAN SHOWS WAREHOUSE PLEASE INCLUDE FLOOR PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-26 Cont ID  
Sent By pleduc Date 2017-04-26 Time   Rev Time 0.00
Received By pleduc Date 2017-04-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By pleduc Date 2017-03-14 Time   Rev Time 0.00
Received By pleduc Date 2017-03-13 Time 16:09 Sent To  
Notes
2017-03-14 09:48:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET LS 1 - THERE IS NO INDICATION OF THE
 CLASSIFICATION OF OCCUPANY; MIXED OR SEPARATED;
  
 PER NFPA 101, 5TH ED
  
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 PLEASE INDICATE THE INTENT OF THE OCCUANCY
 CLASSIFICATION AND ENSURE THE MOST RESTRICTIVE
 REQUIRMENTS ARE MET.
  
  
 2)
 SHEET LS 1 - THERE ARE NO INDICATIONS OF THE
 DESCRIPTION OF THE HAZARD CLASSIFICATION
  
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED DESIGN PROFESSIONAL (RDP) OR OWNER AND
 SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR
 REVIEW AND APPROVAL ON THE BASIS OF THE CHARACTER OF
 THE CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED
 IN THE BUILDING OR STRUCTURE.
  
 PLEASE PROVIDE A DETAILED THE PROPOSED CONTECT OF THE
 STORAGE, INCLUDING BUT NOT LIMITED TO, PRODUCT,
 PALLETS, PACKAGING, RACKS, RACK HEIGHTS, ETC.
  
  
  
 3)
 SHEET LS 1 - THERE AR NO INDICATIONS OF THE DOORS LOCKS
 ON THE EXIT DOORS EITHER AT THE DOUBLE FRONT DOOR AR
 BOTH WAREHOUSE DOORS. ALL HARDWARE SHALL COMPLY WITH
 NFPA 101, CHAPTER 7, MEANS OF EGRESS AND/OR THE MOST
 RESTRICTIVE OCCUPANY AS DETERMINED BY # 1 ABOVE.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3,
 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
 PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS.
  
  
  
 4)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 5)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 07:42 Rev Time 0.00
Received By gjohnson Date 2017-04-18 Time 13:07 Sent To  
Notes
2017-04-19 13:07:11B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-31 Cont ID  
Sent By gjohnson Date 2017-03-31 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2017-03-08 Time 13:07 Sent To  
Notes
2017-03-09 13:07:27B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-24 Cont ID  
Sent By ccole Date 2017-04-21 Time 17:03 Rev Time 0.00
Received By ccole Date 2017-04-21 Time 17:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By ccole Date 2017-03-20 Time 12:37 Rev Time 0.00
Received By ccole Date 2017-03-20 Time 12:37 Sent To  
Notes
2017-03-20 14:01:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030344
 3/20/17
  
 1) THE INPUT DATA REPORT ATTACHED TO THE ENERGYGAUGE
 COMPLIANCE SUBMITTAL DOES NOT PROVIDE DATA FOR THE
 FRONT ENTRY DOOR, THE 6X7" OPENING INTO THE WAREHOUSE,
 AND THE 48X48" WINDOW BETWEEN THE OFFICE AND THE
 WAREHOUSE.
  
 2) PLEASE ATTACH THE MECHANICAL PLAN SHEETS INTO THE
 MAIN PLAN SETS- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 07:42 Rev Time 0.00
Received By gjohnson Date 2017-04-28 Time 07:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-31 Cont ID  
Sent By gjohnson Date 2017-03-31 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2017-03-31 Time 14:34 Sent To  
Notes
2017-03-31 15:23:531ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT, MEP LAVATORY IN BATHROOM #2 IS SHOWN TO CLOSE
 TO WC IT SHALL BE SHOWN TO PROVIDE A 60" CLEAR FLOOR
 SPACE FROM SIDE WALL PER FBC ACC 604.3.1
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  