Plan Review Details - Permit 17030329
Plan Review Stops For Permit 17030329
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By shill Date 2017-03-27 Time 14:41 Rev Time 0.00
Received By shill Date 2017-03-27 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By jwitmer Date 2017-03-13 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2017-03-13 Time 11:52 Sent To  
Notes
2017-03-13 13:58:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030329
 ADD: 1401 FORUM WAY SUITE # 501
 CONT: CLAY KOHLMEYER
 TEL: 561-694-1214
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 13, 2017
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. THE COVERSHEET CS-1 INDICATES THE
 CONSTRUCTION TYPE TO BE IIB- UNPROTECTED SPRINKLERED
 WHEREAS THE LIFE SAFETY SHEET LS-1 INDICATES THE
 BUILDING TYPE OF CONSTRUCTION TO BE A IB. IB TYPE OF
 CONSTRUCTION IS PROTECTED SEE FBC-B TABLE 601 AND IS
 FIRE SPRINKLERED.
  
 2) THE PLAN A-1.0 INDICATES A PARTITION TYPE LEGEND.
 THE PARTITION TYPE IDENTIFIED ?C? IS TO BE USED WITH A
 X-RAY ROOM. NEITHER THE LIFE SAFETY SHEET NOR A-1.0
 SHOW THE USE OF AN X-RAY ROOM. IS THERE ANY ROOMS THAT
 WILL REQUIRE SHIELDING AS FOUND IN SECTION 465.1 FOR
 X-RAY ROOMS OR IS THIS A GENERIC NOTE THAT HAS NOTHING
 TO DO WITH THIS TENANT SPACE. IF X-RAY EQUIPMENT IS TO
 BE INSTALLED IN THIS TENANT SPACE PLEASE INDICATE THE
 TYPE OF USAGE, THE MACHINES CAPACITY OF STRENGTH IN
 KEV. FBC-B 465.1.3. A THOROUGH REVIEW CANNOT BE MADE AT
 THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 3) THE PLAN A-1.0 INDICATES A DOOR SCHEDULE WITH THE
 DESIGNATION OF R FOR DOORS TO BE RELOCATED. THESE DOORS
 ARE IN A NEW WALL LOCATION. 2014 EXISTING BUILDING CODE
 LEVEL II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING. PLEASE PROVIDE THE SIZE OF THE DOOR IN THE
 DOOR SCHEDULE AND COMPLIANCE WITH 2014 FBC-B 1008.1.1
 SIZE OF DOOR.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By vperez Date 2017-03-27 Time 07:06 Rev Time 0.00
Received By vperez Date 2017-03-27 Time 07:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By vperez Date 2017-03-13 Time 10:59 Rev Time 0.00
Received By vperez Date 2017-03-13 Time 10:59 Sent To  
Notes
2017-03-13 11:05:55INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 PLEASE SHOW ON MEP SHEET THE EMERGENCY FIXTURES AS
 SHOWN ON LIFE SAFETY SHEET. ELECTRICAL SCOPE TO
 COORELATE. FBC 107.3.5
  
 CLARIFY IF INTERIOR LIGHTING CONTROLS ARE ON OCCUPANCY
 SENSORS TO AUTOMATICALLY CONTROL THE LIGHTING. FBC EC
 405
  
 PROVIDE THE PANEL SCHEDULE ASSOCIATED WITH THIS OFFICE
 SUITE. FBC 107.3.5
  
 ANY LOW VOLTAGE SYSTEM ALTERATION WILL REQUIRE SEPERATE
 PERMIT. GENERAL NOTE WILL SUFFICE.
  
 VAL PEREZ
 ELECTRICAL PLANS EXAMINER
 *6717
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By pleduc Date 2017-03-28 Time   Rev Time 0.00
Received By pleduc Date 2017-03-28 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-15 Cont ID  
Sent By pleduc Date 2017-03-15 Time   Rev Time 0.00
Received By pleduc Date 2017-03-14 Time 12:11 Sent To  
Notes
2017-03-15 11:39:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) PLEASE PROVIDE A LIGHTWEIGHT ROOF TRUSS SIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-28 Cont ID  
Sent By pleduc Date 2017-03-28 Time   Rev Time 0.00
Received By pleduc Date 2017-03-23 Time 09:53 Sent To  
Notes
2017-03-24 09:53:43B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 15:29 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 10:30 Sent To  
Notes
2017-03-09 10:31:32B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-03-13 Cont ID  
Sent By jwitmer Date 2017-03-13 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2017-03-13 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By ccole Date 2017-03-28 Time 07:13 Rev Time 0.00
Received By ccole Date 2017-03-27 Time 17:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 15:23 Rev Time 0.00
Received By ccole Date 2017-03-17 Time 15:22 Sent To  
Notes
2017-03-17 15:26:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030329
 3/17/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-03-13 Cont ID  
Sent By gjohnson Date 2017-03-13 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2017-03-13 Time 15:34 Sent To  
Notes
2017-03-13 15:44:213/13/17 NO PLUMBING WORK BEING INDICATED ON PLANS/GPJ