Plan Review Details - Permit 17030255
Plan Review Stops For Permit 17030255
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-22 Cont ID  
Sent By rmcdouga Date 2017-03-22 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2017-03-22 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By rmcdouga Date 2017-03-13 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2017-03-13 Time 07:20 Sent To  
Notes
2017-03-13 09:37:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 2) ADDRESS THE HISTORIC PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-20 Cont ID  
Sent By vperez Date 2017-03-20 Time 09:19 Rev Time 0.00
Received By vperez Date 2017-03-20 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-10 Cont ID  
Sent By destabro Date 2017-03-15 Time 09:24 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 09:46 Sent To B
Notes
2017-03-10 09:53:21PLEASE SHOW AT METER LOCATION THAT THERE IS A 200MCB,
  
 ALSO SHOW ON PANEL SCHEDULE A, THE LOAD CALCULATION FOR
 PANEL B. THE 16,400WATT LOAD SHOWN AT PANEL B IS NOT
 ACCOUNTED FOR AT PANEL A CALCULATION.
  
 150A 2POLE SHOWN AT PANEL A BUT 100AMP FEDDERS AT
 #3THWN GOOD FOR 100AMPS ONLY. CORRECT TYPO TO REFLECT
 100A 2 POLE BREAKER. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-03-15 Cont ID  
Sent By destabro Date 2017-03-09 Time 15:39 Rev Time 0.00
Received By destabro Date 2017-03-15 Time 09:22 Sent To B
Notes
2017-03-09 15:41:143/15/2017 - APPLICANT AGREED TO NOT USE BOTTOM/TOP
 TRACKS TO MOUNT STORM SHUTTERS. PERMIT THEN MEETS
 CONDITIONS OF HISTORIC REVIEW. DLE
  
 3/9/2017 - PER HISTORIC DISTRICT GUIDELINES, ALUMINUM
 STORM PANELS MUST BE DEMOUNTABLE AND APPLIED WITHOUT
 THE USE OF HEADERS OR TRACKS. PLEASE REVISE PRODUCT
 APPROVALS TO REFLECT THIS CHANGE. QUESTIONS MAY BE
 DIRECTED TO DESIREE ESTABROOK, HISTORIC PRESERVATION
 PLANNER, 561.822.1428.
2017-03-09 14:08:16ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-22 Cont ID  
Sent By rmcdouga Date 2017-03-22 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2017-03-16 Time 09:29 Sent To  
Notes
2017-03-17 09:29:33RESUB OF REVISION ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-13 Cont ID  
Sent By rmcdouga Date 2017-03-13 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2017-03-07 Time 13:55 Sent To  
Notes
2017-03-08 13:55:21REVISION ROUTED TO HISTORIC VIA ZONING INBOX