Plan Review Details - Permit 17030253
Plan Review Stops For Permit 17030253
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-11 Cont ID  
Sent By tklarge Date 2017-03-11 Time 04:24 Rev Time 0.00
Received By tklarge Date 2017-03-07 Time 13:22 Sent To  
Notes
2017-03-08 13:22:33PLUMB <5K

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-11 Cont ID  
Sent By tklarge Date 2017-03-11 Time 04:24 Rev Time 0.00
Received By tklarge Date 2017-03-11 Time 03:57 Sent To  
Notes
2017-03-11 04:22:201) AS DRAWN, THE SANITARY RISER DOES NOT CCOMPLY WITH
 2014 FBC-RES. SEC.P3108.2.2, (VERTICAL WET VENTING),
 AND SEC. P3109.2 ( WASTE STACK VENTING ) IF THAT IS THE
 INTENT. REVISE THE DESIGN OF THE SANITARY SYSTEM AND
 CLARIFY WHAT SECTION OF THE PLUMBING CODE THAT YOU ARE
 BASING YOUR DESIGN UPON.
 2) SIZE THE DRY VENT ON THE PLAN. COMPLY WITH 2014
 FBC-RES. SEC.P3108.
 3) WHERE IS THE SANITARY LINE /STACK FOR A WASHING
 MACHINE?
 4) PLACE A NOTE ON THE PLANS THAT THE INSTALLATION
 SHALL COMPLY WITH 2014 FBC - RESIDENTIAL. THE PLANS
 REFER TO THE 2004 FBC.
 5) CLEANOUTS ARE REQUIRED IN THE BASE OF BOTH STACKS.
 2014 FBC-RES. SEC. P3005.2.6.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  