| Plan Review Stops For Permit 17030253 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-11 |
Time |
04:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-07 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2017-03-08 13:22:33 | PLUMB <5K |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-03-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-11 |
Time |
04:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-11 |
Time |
03:57 |
Sent To |
|
|
| Notes |
| 2017-03-11 04:22:20 | 1) AS DRAWN, THE SANITARY RISER DOES NOT CCOMPLY WITH | | | 2014 FBC-RES. SEC.P3108.2.2, (VERTICAL WET VENTING), | | | AND SEC. P3109.2 ( WASTE STACK VENTING ) IF THAT IS THE | | | INTENT. REVISE THE DESIGN OF THE SANITARY SYSTEM AND | | | CLARIFY WHAT SECTION OF THE PLUMBING CODE THAT YOU ARE | | | BASING YOUR DESIGN UPON. | | | 2) SIZE THE DRY VENT ON THE PLAN. COMPLY WITH 2014 | | | FBC-RES. SEC.P3108. | | | 3) WHERE IS THE SANITARY LINE /STACK FOR A WASHING | | | MACHINE? | | | 4) PLACE A NOTE ON THE PLANS THAT THE INSTALLATION | | | SHALL COMPLY WITH 2014 FBC - RESIDENTIAL. THE PLANS | | | REFER TO THE 2004 FBC. | | | 5) CLEANOUTS ARE REQUIRED IN THE BASE OF BOTH STACKS. | | | 2014 FBC-RES. SEC. P3005.2.6. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
|