Plan Review Details - Permit 17030233
Plan Review Stops For Permit 17030233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-09 Cont ID  
Sent By shill Date 2017-05-09 Time 17:30 Rev Time 0.00
Received By shill Date 2017-05-09 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-24 Cont ID  
Sent By shill Date 2017-03-24 Time 07:58 Rev Time 0.00
Received By shill Date 2017-03-24 Time 07:46 Sent To ENG
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-20 Cont ID  
Sent By vperez Date 2017-03-20 Time 13:08 Rev Time 0.00
Received By vperez Date 2017-03-20 Time 13:08 Sent To  
Notes
2017-03-20 13:12:35PASSED WITH PROVISO:
  
 PROVIDE REVISED AVAILABLE FAULT CURRENT CALCULATION FOR
 THE NEW SERVICE SHOWN AND LABEL SERVICE UPON FINAL
 INSPECTION WITH AIC. NEC 110.24A
  
 SITE LIGHT, YARD LIGHTS TO BE UNDER SEPERATE PERMIT.
 ANY LOW VOLTAGE AS WELL. FBC 107.3.5
  
 A SECOND MEANS OF GROUNDING REQUIRED TO SUPPLEMENT THE
 ONE GROUND ROD SHOWN. PROVIDE TWO RODS.
  
 V. PEREZ
 *6717

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-05-04 Cont ID  
Sent By mgonzale Date 2017-05-04 Time   Rev Time 1.00
Received By mgonzale Date 2017-05-04 Time   Sent To I
Notes
2017-05-04 15:08:09PASSED WITH PROVISO:
  
 #1 PLEASE NOTE THERE ARE TWO VERTICAL DATUMS LISTED.
 CO-2 AND SO-1
  
 #2 CONTRACTOR SHALL OBTAIN PERTINENT PERMITS SUCH AS
 SFWMD ERP PERMIT, SFWMD WATER USE.
  
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-09 Cont ID  
Sent By shill Date 2017-05-09 Time 17:31 Rev Time 0.00
Received By shill Date 2017-05-04 Time 16:00 Sent To  
Notes
2017-05-04 16:00:12RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-04 Cont ID  
Sent By lmarchan Date 2017-05-04 Time 15:59 Rev Time 0.00
Received By lmarchan Date 2017-03-06 Time 11:06 Sent To  
Notes
2017-03-24 07:59:21REMOVED FROM C10 AND ROUTED TO ENGINEERING BOX
  
  
2017-03-08 11:06:56C10

Review Stop Z ZONING
Rev No 1 Status N Date 2017-03-10 Cont ID  
Sent By ajones Date 2017-03-10 Time 10:47 Rev Time 0.00
Received By ajones Date 2017-03-10 Time 10:47 Sent To  
Notes
***NONE***