Plan Review Details - Permit 17030227
Plan Review Stops For Permit 17030227
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 10:44 Rev Time 0.00
Received By cthroop Date 2017-06-21 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-06-16 Cont ID  
Sent By cthroop Date 2017-06-16 Time 09:15 Rev Time 0.00
Received By cthroop Date 2017-06-16 Time 07:34 Sent To  
Notes
2017-06-16 09:46:49BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 4TH REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING ITEMS HAVE NOT BEEN CORRECTED FROM LAST
 REVIEW.
  
 1. SEE COMMENT #1 - DIMENSION FROM THE NOSING TO THE
 TOP OF THE HANDRAIL IS SPECIFIED AS 30" (SEE PLAN PAGE
 S-303). DIMENSION TO BE NOT LESS THAN 34" NOR MORE THAN
 38" PER FBC-R311.7.8.1.
 R311.7.8.1 HEIGHT.
 HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED
 PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF
 RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM)
 AND NOT MORE THAN 38 INCHES (965 MM).
  
 2. SEE COMMENT #3 - NOTE #15 ON PLAN SHEET S-102 STATES
 DRAFTSTOPPING SHALL NOT EXCEED 100 SF. FBC -R302.12
 STATES AREA NOT TO EXCEED 1000 SF.
 R302.12 DRAFTSTOPPING.
 IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
 WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE
 ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL
 BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE
 FOLLOWING CIRCUMSTANCES:
  
 3. SEE COMMENT #5 - PRODUCT APPROVALS TO BE REVIEWED
 AND APPROVED BY DESIGNER OF RECORD PER FBC-R107.3.4.
 SUBMITTED NOA 16-0629.16 FOR FRENCH DOORS IS NOT ON
 APPROVED PRODUCT APPROVAL LIST (SEE PLAN SHEET S-000).
 FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4. SEE COMMENT #6 - MANUFACTURERS INSTALLATION
 INSTRUCTIONS SUBMITTED FOR OUTDOOR BBQ. SAFE OPERATING
 PRACTICES PROHIBIT OPERATION UNDER OVERHEAD COMBUSTIBLE
 CONSTRUCTION. SUMMER KITCHEN CEILING IS T&G. PLEASE
 MCLARIFY.
  
 5. SEE COMMENT #7 - NOA 16-0629.14 FOR ARCH TOP ENTRY
 DOORS (FIXED WINDOW) SUBMITTED FOR REVIEW IS NOT ON
 APPROVED PRODUCT APPROVAL LIST (SEE PLAN PAGE S-000).
 FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-30 Cont ID  
Sent By rmcdouga Date 2017-05-30 Time 17:33 Rev Time 0.00
Received By rmcdouga Date 2017-05-25 Time 19:12 Sent To  
Notes
2017-05-30 13:57:05PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET S-303, THE DIMENSION FROM THE NOSING TO THE
 TOP OF THE HANDRAIL IS SPECIFIED AS 30" ON THE DETAIL.
 FBC-R 311.7.8.1 REQUIRES THIS DIMENSION TO BE NOT LESS
 THAN 34" NOR MORE THAN 38".
  
 2) THE LANDSCAPE AND DRAINAGE PLAN THAT WAS SUBMITTED
 DOES NOT SHOW COMPLIANCE WITH FBC-R 401.3 FOR SURFACE
 WATER DRAINAGE. SUBMIT TWO SETS OF SURFACE WATER
 DRAINAGE PLANS THAT SHOW COMPLIANCE WITH THE FOLLOWING:
 R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED TO
 A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 3) NOTE #15 ON SHEET S-102, FOR DRAFTSTOPPING THE
 CONCEALED SPACES OF THE FLOOR/CEILING ASSEMBLY
 INCORRECTLY STATES THAT THE AREAS SHALL NOT EXCEED 100
 SF AND SECTION R 302.12 CODE STATES 1000 SF. PLEASE
 CORRECT.
  
 4) ON SHEET S-102, SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE FLOOR TRUSSES TO THE LEDGERS IN
 ORDER TO RESIST LATERAL FORCES ON THE STRUCTURE. FBC
 107.2.1
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD OF
 THE STRUCTURE. FBC 107.3.4
  
 6) THE INFORMATION THAT WAS SUBMITTED FOR THE BUILT-IN
 OUTDOOR BBQ DOES NOT HAVE THE LISTING INFORMATION OR
 INSTALLATION REQUIREMENTS, SUCH AS, CLEARANCES TO
 COMBUSTIBLES. SUBMIT ADDITION INFORMATION. FBC-R
 107.2.1
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCH
 TOP ENTRY DOORS AS REQUIRED BY FBC 107.3.4.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-21 Cont ID  
Sent By rmcdouga Date 2017-04-21 Time 17:02 Rev Time 0.00
Received By rmcdouga Date 2017-04-21 Time 19:12 Sent To  
Notes
2017-04-21 17:02:42DUE TO COMPUTER SYSTEM FAILURE, THIS IS ACTUALLY THE
 FIRST BUILDING PLAN REVIEW.
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MEAN ROOF HEIGHT (MRH) IS INCORRECTLY SPECIFIED
 AS 15' ON SHEET S-000. THIS IS A TWO STORY STRUCTURE
 AND THE MEAN ROOF HEIGHT APPEARS TO BE APPROXIMATELY
 25'. FBC-R301.2.1
  
 2) PROVIDE COMPONENT AND CLADDING PRESSURES FOR ROOF
 ZONES 1, 2 & 3 AND WALL ZONES 4 & 5 ON THE PLANS. FBC
 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND COMPONENT AND
 CLADDING DESIGN PRESSURES PURSUANT TO FBC-R301.2.
  
 3) SHOW COMPLIANCE WITH FBC-R 311.7 FOR STAIR
 REQUIREMENTS ON THE PLANS. STAIR DETAIL #10 ON S-300 IS
 FOR POURED CONCRETE STAIRS AND THE CODE REQUIREMENT
 INFORMATION IS NOT PROVIDED.
  
 4) SHOW COMPLIANCE WITH FBC-R 311.7.8 FOR HANDRAIL
 REQUIREMENTS ON THE PLANS.
  
 5) SHOW COMPLIANCE WITH FBC-R 312.1 FOR THE GUARDS
 REQUIRED AT THE BALCONY AND THE STAIRS ON THE PLANS.
  
 6) PROVIDE TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBC-R 401.3.
  
 7) THE SECOND FLOOR GAME ROOM HAS CLOSETS AND COULD BE
 USED AS A SLEEPING ROOM NOW OR IN THE FUTURE.
 THEREFORE, THE WINDOWS MUST COMPLY WITH FBC-R 310 FOR
 EMERGENCY ESCAPE AND RESCUE.
  
 8) SHOW COMPLIANCE WITH FBC-R 302.12 FOR DRAFTSTOPPING
 OF THE CONCEALED SPACE OF THE FLOOR / CEILING ASSEMBLY
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET.
  
 9) SHOW THE TRUSS TO LEDGER CONNECTORS ON SHEET S-102
 AND THE ROOF TO WALL CONNECTORS ON SHEET S-103. THERE
 ARE NO ID MARKS ON THE FLOOR AND ROOF FRAMING PLANS TO
 SHOW THE LOCATIONS OF THE CONNECTORS THAT ARE LISTED IN
 THE ANCHOR SCHEDULE ON SHEET S-400.
  
 10) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS. TWO DIFFERENT ENERGY FORMS AND EQUIPMENT
 SIZING CALCULATIONS WERE SUBMITTED. PLEASE REMOVE THE
 OLD ONE AND SUBMIT AN ADDITIONAL COPY OF THE CORRECT
 ONE.
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ARCH TOP ENTRY
 DOORS.
  
 12) PRODUCT APPROVALS WERE SUBMITTED FOR STRUCTURAL
 MULLIONS, HOWEVER, THE PLANS DO NOT APPEAR TO SHOW ANY
 MULLIONS. PLEASE CLARIFY. FBC 107.2.1
  
 13) SUBMIT TWO SETS OF THE EVALUATION REPORTS FOR THE
 ICYNENE SPRAY FOAM INSULATION. FBC-R 316
  
 14) SUBMIT TWO SETS OF THE MANUFACTURER?S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE BUILT-IN
 OUTDOOR BBQ GRILL AND HOOD (IF ONE IS REQUIRED).
 FBC-R107.2.1
  
 15) SPECIFY THE MATERIAL THAT WILL BE INSTALLED ON THE
 CEILING OF THE SUMMER KITCHEN, LANAI AND COVERED ENTRY
 AREAS.
  
 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By rmcdouga Date   Time   Rev Time 0.00
Received By rmcdouga Date 2017-04-19 Time 07:49 Sent To  
Notes
2017-04-20 15:22:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MEAN ROOF HEIGHT (MRH) IS INCORRECTLY SPECIFIED
 AS 15' ON SHEET S-000. THIS IS A TWO STORY STRUCTURE
 AND THE MEAN ROOF HEIGHT APPEARS TO BE APPROXIMATELY
 25'. FBC-R301.2.1
  
 2) PROVIDE COMPONENT AND CLADDING PRESSURES FOR ROOF
 ZONES 1, 2 & 3 AND WALL AREAS 4 & 5 ON THE PLANS.
 FBC-R301.2.1
  
 3) SHOW COMPLIANCE WITH FBC-R 311.7 FOR STAIR
 REQUIREMENTS ON THE PLANS. STAIR DETAIL #10 ON S-300
 ARE FOR POURED CONCRETE STAIRS AND ARE MISSING
 INFORMATION.
  
 4) SHOW COMPLIANCE WITH FBC-R 311.7.8 FOR HANDRAIL
 REQUIREMENTS ON THE PLANS.
  
 5) SHOW COMPLIANCE WITH FBC-R 312.1 FOR GUARDS
 REQUIREMENTS AT THE BALCONY AND STAIR ON THE PLANS.
  
 6) PROVIDE TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBC-R401.3.
  
 7) THE SECOND FLOOR GAME ROOM HAS CLOSETS AND COULD BE
 USED AS A SLEEPING ROOM NOW OR IN THE FUTURE. THE
 WINDOWS NEED TO COMPLY WITH FBC-R310 FOR EMERGENCY
 ESCAPE ANE RESCUE.
  
 8) **********************REVIEW NOT COMPLETE AT THIS
 TIME********************
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-23 Cont ID  
Sent By jleahy Date 2017-03-23 Time 11:35 Rev Time 0.00
Received By jleahy Date 2017-03-23 Time 11:11 Sent To  
Notes
2017-03-23 11:37:59PROVISO!
  
 NEED TO SUBMIT PANEL SCHEDULES PRIOR TO THE FINAL
 INSPECTION.
 E3706.2 FBC RESIDENTIAL
  
 JLEAHY
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 10:44 Rev Time 0.00
Received By cthroop Date 2017-06-07 Time 16:09 Sent To  
Notes
2017-06-08 16:09:28R30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-30 Cont ID  
Sent By rmcdouga Date 2017-05-30 Time 17:34 Rev Time 0.00
Received By rmcdouga Date 2017-05-11 Time 13:20 Sent To  
Notes
2017-05-12 13:20:26R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By rmcdouga Date 2017-04-21 Time 17:03 Rev Time 0.00
Received By rmcdouga Date 2017-03-06 Time 11:09 Sent To  
Notes
2017-03-07 11:09:08R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By cthroop Date 2017-06-16 Time 09:15 Rev Time 0.00
Received By cthroop Date 2017-06-14 Time 08:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-04-19 Cont ID  
Sent By rmcdouga Date 2017-04-19 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2017-04-19 Time 07:49 Sent To  
Notes
2017-04-19 07:50:04BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-04-18 Cont ID  
Sent By hmoser Date 2017-04-18 Time 13:58 Rev Time 0.00
Received By hmoser Date 2017-04-18 Time 13:48 Sent To  
Notes
2017-04-18 13:58:46PASS PROVISO
 1) REFER TO SECTION M1301.3 PROVIDE MANUFACTURE
 INSTALLATION INSTRUCTIONS
 FOR RANGE HOOD AT FIRST INSPECTION. 2014 FBC(R)
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 REVISION REQUIRED
 PROVIDE RETURN AIR FOR GAME ROOM 2014 FBC(R)
 3) PROVIDE A ENGINEER DETAIL ON THE CONDENSER TIE DOWN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 FAX 561-805-6676
 OFFICE 561-805-6732
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 10:34 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 10:34 Sent To  
Notes
2017-05-24 11:07:512ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-503 SANITARY RISER DIAGRAM.
 A. THE WATER CLOSET AND BIDET IN THE MASTER BATHROOM
 ARE NOT VENTED PROPERLY. PER FBC RES P3101.2.1
 B. THE SHOWER IN MASTER BATHROOM ARE NOT VENTED
 PROPERLY. PER FBC RES P3101.2.1
 C. THE TWO BATHROOMS ON THE SECOND FLOOR RISER ARE NOT
 LABELED CORRECTLY BATH#5 IS LABELED AS LAUNDRY BATH #3
 IS LABELED AS MASTERBATH PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
 D. BATHROOM #4 IS MISSING ON THE SECOND FLOOR RISER
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 E. THE VENT ON THE WATER CLOSET IN THE BATHROOM #5 IS
 NOT A REQUIRED VENTAND CAN NOT CONNECT TO-THE TOP OF
 THE WATER CLOSET RISER PLEASE REMOVE. PER WPB AMEND TO
 FBC 107.2.1
  
 2. 2ND REQUEST A CLEAN OUT IS REQUIRED AT THE BASE OF
 ALL SOIL STACKS. PER FBC RES P3005.2.6
  
 3. PLEASE INCLUDE HOT WATER SYSTEM ON WATER RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 I SUGGEST TO EXPEDITE AN APPROVAL FOR PLUMBING THAT A
 MEETING BE SCHEDULED TO GO OVER THE COMMENTS ON THE
 RISER DIAGRAM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 12:47 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 11:07 Sent To  
Notes
2017-03-17 12:56:511ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ON THE RISER THE WC IN MASTER BATHROOM IS NOT
 VENTED. PER FBC PL P3101.2.1
  
 2. ON THE RISER THE LT IS NOT VENTED. PER FBC PL
 P3101.2.1
  
 3. THE MASTER SH IS NOT SHOWN ON RISER PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. THE SOIL STACK FOR THE SECOND FLOOR IS NO SHOWN ON
 THE GROUND FLOOR RISER PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. PLEASE PROVIDE A WATER RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.3.5.3(11)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-04-19 Cont ID  
Sent By rmcdouga Date 2017-04-19 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2017-04-19 Time 16:48 Sent To  
Notes
2017-04-19 16:55:15SAXONY 900 CONCRETE ROOF TILE - NOA NO. 16-0711.05
 BORAL TILE SEAL - NOA NO. 12-1219.01
 ICP ADHESIVES POLYSET AH-160

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-06-20 Time   Rev Time 0.00
Received By   Date 2017-06-20 Time   Sent To  
Notes
2017-06-20 14:19:43********************ZONING
 PROVISO*****************************************
  
 DO NOT APPROVE FINAL WITHOUT CONFIRMING THAT LANDSCAPE
 PERMIT HAS BEEN ISSUED AND INSPECTION OF LANDSCAPE
 INTALLLATION HAS BEEN APPROVED. PLEASE CONTACT ME WITH
 ANY QUESTIONS.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-05-23 Time   Rev Time 0.00
Received By   Date 2017-05-23 Time   Sent To  
Notes
2017-05-23 15:56:16******************ZONING
 REVIEW*************************
  
 THE HEIGHT OF BUILDING AND OVERHANGS ARE FINE. THE
 LANDSCAPE AND IRRIGATION PLAN SHOULD BE SUBMITTED AS A
 SEPARATE PERMIT. PLEASE LET ME KNOW IF YOU HAVE ANY
 QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By awooten Date 2017-03-14 Time 10:42 Rev Time 0.00
Received By awooten Date 2017-03-13 Time 14:48 Sent To  
Notes
2017-03-14 10:40:28MAXIMUM HEIGHT IN THIS DISTRICT IS 30 FEET.
  
 SEC. 94-306. - HEIGHT EXCEPTIONS.
  
 (A) EXEMPTIONS TO HEIGHT LIMITS. HEATING, VENTILATION,
 AND AIR CONDITIONING EQUIPMENT; CHURCH STEEPLES, BELL
 TOWERS, FLAG POLES, CHIMNEYS, PARAPETS, STAIR
 ENCLOSURES, TANKS, DECORATIVE FEATURES, ELEVATOR
 HOISTWAYS OR EQUIPMENT, TELEVISION OR RADIO ANTENNAS,
 AND RELATED MECHANICAL OR FUNCTIONAL FEATURES MAY
 EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN PERCENT.
  
 OVERHANG FOR BALCONIES CANNOT ENCROACH MORE THAN 3 FEET
 INTO SETBACKS. PLEASE PROVIDE BALCONY ENCROACHMENT.
  
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK.
  
 PLEASE SUBMIT LANDSCAPE AND IRRIGATION PLAN AS A
 SEPARATE PERMIT.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  