Plan Review Details - Permit 17030212
Plan Review Stops For Permit 17030212
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-10 Cont ID  
Sent By jwitmer Date 2017-04-10 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2017-04-10 Time 13:48 Sent To  
Notes
2017-04-10 14:28:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030212
 ADD: 846 SOUTHERN BLVD.
 CONT: HOOKS CONSTRUCTION
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MONDAY APRIL10/2017
 ACTION: BUILDING PROVISO
  
 1) SHOWING COMPLIANCE WITH 2014 FBC-ACCESS. CODE 904
 CHECK-OUT AND SALES COUNTERS
 FOR HEIGHT AND APPROACH.
  
 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 904.4.1 PARALLEL APPROACH. A PORTION OF THE COUNTER
 SURFACE THAT IS 36 INCHES LONG MINIMUM AND 36 INCHES
 HIGH MAXIMUM ABOVE THE FINISH FLOOR SHALL BE PROVIDED.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 SHALL BE POSITIONED FOR A PARALLEL APPROACH ADJACENT TO
 THE 36 INCH MINIMUM LENGTH OF COUNTER.
  
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES LONG, THE ENTIRE COUNTER SURFACE
 SHALL BE 36 INCHES HIGH MAXIMUM ABOVE THE FINISH FLOOR.
  
 904.4.2 FORWARD APPROACH. A PORTION OF THE COUNTER
 SURFACE THAT IS 30 INCHES LONG MINIMUM AND 36 INCHES
 HIGH MAXIMUM SHALL BE PROVIDED. KNEE AND TOE SPACE
 COMPLYING WITH 306 SHALL BE PROVIDED UNDER THE COUNTER.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE POSITIONED FOR A FORWARD APPROACH TO THE COUNTER.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By jwitmer Date 2017-03-20 Time 07:24 Rev Time  
Received By jwitmer Date 2017-03-20 Time 06:45 Sent To  
Notes
2017-03-20 07:24:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030212
 ADD: 846 SOUTHERN BLVD.
 CONT: HOOKS CONSTRUCTION
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MARCH 20/2017
 ACTION: DENIED
  
 1) THE COVERSHEET A100 INDICATES THE MERCANTILE
 OCCUPANCY OF 1593 SQ. FT./ 60 = 27 OCCUPANTS. PLEASE
 REVIEW THE 2014 FBC-B TABLE 1004.1.2 FOR THE GRADE
 FLOOR THE OCCUPANT LOAD IS TAKEN AT 30 SQ. FT./
 OCCUPANT. 1593/30= 54 OCCUPANTS.
  
 2) PLEASE PROVIDE WHAT THE SPACE IS BEHIND THE STORAGE
 ROOM THIS SPACE IS NOT LABELED TO USAGE IF PART OF THE
 TENANCY OR IF COMMON AREA? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) WITH THE OCCUPANT LOAD GREATER THAN 50 2 EXITS ARE
 REQUIRED. FOR THE SECANDARY EXIT YOU HAVE TO TTRAVEL
 THROUGH THE STORAGE ROOM. TO USE THE STORAGE ROOM AS
 THE SECONDARY EXIT SHOW COMPLIANCE WITH 2014 FBC-B
 1014.2 EGRESS THROUGH INTERVENING SPACES. EGRESS
 THROUGH INTERVENING SPACES SHALL COMPLY WITH THIS
 SECTION. 4. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND
 LEAD DIRECTLY FROM THE RETAIL AREA TO THE EXIT WITHOUT
 OBSTRUCTIONS.
  
 4) THE PLANS DO NOT SHOW ANY DETAILS SHOWING COMPLIANCE
 WITH 2014 FBC-ACCESS. CODE 904 CHECK-OUT AND SALES
 COUNTERS FOR HEIGHT OR APPROACH.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-06 Cont ID  
Sent By vperez Date 2017-04-06 Time 11:25 Rev Time 0.00
Received By vperez Date 2017-04-06 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By vperez Date 2017-03-14 Time 09:23 Rev Time 0.00
Received By vperez Date 2017-03-14 Time 09:23 Sent To  
Notes
2017-03-14 09:24:09INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION FOR ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO CCTV, PHONE AND
 DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 FOR FEEDERS AND BRANCH CIRCUITS AND COMPLETIONS
 DOCUMENTS.
 3. PLEASE PROVIDE INTERIOR LIGHTING LEVELS AS REQUIRED
 BY FBC EC 405.
 4. SHOW GFCI BREAKER AT PANEL BOARD FOR DRINKING
 FOUNTAIN, AS GFCI WILL NEED TO BE READILY ACCESSIBLE
 PER NEC 210.8B.
 5. COULD NOT LOCATE SIGN RECEPTACLE AND LOAD AT PANEL
 SCHEDULE AS REQUIRED PER NEC 600.5A
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-18 Cont ID  
Sent By wjolin Date 2017-04-18 Time 16:18 Rev Time 0.00
Received By wjolin Date 2017-04-18 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-09 Cont ID  
Sent By wjolin Date 2017-03-09 Time 15:44 Rev Time 0.00
Received By wjolin Date 2017-03-09 Time 15:28 Sent To  
Notes
2017-03-09 15:44:40846 SOUTHERN BOULEVARD
 PERMIT #17030212
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS OR SUITE NUMBER PROVIDED ON THE PLANS.
  
 PLANS STATE THE BUILDING IS PROTECTED BY AUTOMATIC
 SPRINKLERS; HOWEVER, NO SPRINKLER RENOVATION SCOPE IS
 SHOWN ON THE PLANS.
  
 PROVIDE A STORAGE ROOM LAYOUT TO ENSURE DEDICATED
 EGRESS ROUTES CAN AND WILL BE MAINTAINED.
  
 NO ROOM NAME OR OCCUPANCY LISTED ADJACENT TO THE
 RESTROOM. WHY IS A DOOR FROM AN ADJACENT TENANT SPACE
 LOCATED IN THIS WALL?
  
 NO EXIT SIGN PROVIDED ON EMPLOYEE SIDE OF NEW DOOR
 SEPARATING SUPPLY ROOM FROM SALES AREA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-18 Cont ID  
Sent By wjolin Date 2017-04-18 Time 16:18 Rev Time 0.00
Received By wjolin Date 2017-03-30 Time 11:00 Sent To  
Notes
2017-04-04 11:01:07B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By jwitmer Date 2017-03-20 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2017-03-06 Time 16:05 Sent To  
Notes
2017-03-07 16:05:49B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By jwitmer Date 2017-03-20 Time 07:24 Rev Time  
Received By jwitmer Date 2017-03-20 Time 06:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-06 Cont ID  
Sent By ccole Date 2017-04-06 Time 07:29 Rev Time 0.00
Received By ccole Date 2017-04-05 Time 18:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-09 Cont ID  
Sent By ccole Date 2017-03-09 Time 09:35 Rev Time 0.00
Received By ccole Date 2017-03-09 Time 09:35 Sent To  
Notes
2017-03-09 09:46:561ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING
 PERMIT #17030212
 3/9/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET M-2: PROVIDE THE CFMS AT EACH SUPPLY DIFFUSER
 AND RETURN GRILL- SECTION C403.2.7.5 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THAT TESTING BALANCING IS
 REQUIRED PER SECTION C408.2.2.
  
 3) M-2. KEY NOTE #13: IT APPEARS THAT AIR IS BEING
 TRANSFERRRED INTO THE EGRESS CORRIDOR WHICH IS NOT
 PERMITTED PER SECTION 601.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-11 Cont ID  
Sent By gjohnson Date 2017-04-11 Time 16:20 Rev Time 0.00
Received By gjohnson Date 2017-04-11 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-15 Cont ID  
Sent By gjohnson Date 2017-03-15 Time 11:51 Rev Time 0.00
Received By gjohnson Date 2017-03-15 Time 11:42 Sent To  
Notes
2017-03-15 11:55:571ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS OF ADA BATHROOM. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. A501 DETAIL A CLEAR FLOOR SPACE PROVIDE NOTE
 FOR FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  