Plan Review Details - Permit 17030121
Plan Review Stops For Permit 17030121
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-16 Cont ID  
Sent By jwitmer Date 2017-05-16 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2017-05-16 Time 14:44 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-17 Cont ID  
Sent By jwitmer Date 2017-03-17 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2017-03-16 Time 16:34 Sent To  
Notes
2017-03-17 09:32:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030121
 ADD: 1309 N. FLAGLER DR. X-RAY ROOM : T3177
 CONT: PM WRIGHT
 TEL: 561-309-6162
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 17/ 2017
 ACTION: BUILDING PROVISO
  
 1) DEFERRED SUBMITTAL 107.3.4.2. SHEET A1.0 SPECIFIC
 FLOOR PLAN NOTE # 4, INDICATES THE INSTALLATION OF NEW
 5/8 INCH LEAD LINED DRYWALL WITH 1/8TH INCH THICK LEAD
 LINING OVER THE EXISTING WALLS AS REQUIRED OR DIRECTED
 BY THE RADIATION CONSULTANT / PHYSICIST. 2014 FBC-B
 465.5.1 SHIELDING. 465.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED. 465.5.1.3. PRIOR TO CONSTRUCTION, THE FLOOR
 PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
 SHOP DRAWING REVIEW AND APPROVAL BY THE DESIGNER OF
 RECORD BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2) DEFERRED SUBMITTAL 107.3.4.2. SHEET S1 & S2 DRAWINGS
 BY GE HEALTHCARE. SHOW THE USE OF UNISTRUT SUPPORT AND
 EQUIPMENT TO BE HUNG FROM THE CEILING. SUBMIT SHOP
 DRAWINGS TO THE DESIGNER OF RECORD SHOWING THE
 ALLOWABLE AMOUNT OF LBS. TO BE HUNG FROM THE ASSEMBLY.
 SHOW THE ATTACHMENT TO THE STRUCTURAL STEEL OR THROUGH
 BOLT THROUGH CONCRETE FLOOR SHOULD BE FAVORED. DO NOT
 USE ANCHORS IN DIRECT TENSION. NOTE IF THE SHOP
 DRAWINGS WERE PREPARED BY AN ENGINEER, THEY WILL NEED
 TO BE SIGNED AND SEALED. FL ADMIN CODE 61G15-23.002
 ENGINEERS. SINCE THE GE HEALTHCARE DRAWINGS ARE NOT
 SIGNED AND SEALED THE SHOP DRAWINGS BEING SUBMITTED
 WILL NEED TO BE REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By rlecky Date 2017-04-27 Time 15:26 Rev Time 0.00
Received By rlecky Date 2017-04-27 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 13:05 Rev Time 0.00
Received By rlecky Date 2017-03-28 Time 12:02 Sent To  
Notes
2017-03-28 13:06:50PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE PANEL SCHEDULES AND RISER PLANS DO NOT SEEM TO
 CORRESPOND. THE SPECIFICATIONS AND LOADS FOR THE NEW
 EQUIPMENT HAVE NOT BEEN ADEQUATELY IDENTIFIED. NEC
 215.5
  
 VERIFY THE NEW RADIOLOGY EQUIPMENT HAS BEEN LISTED FOR
 USE AND IS IN CONFORMITY WITH THE REQUIREMENTS OF THE
 NATIONAL ELECTRICAL CODE. NEC 110.3
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By pleduc Date 2017-03-14 Time   Rev Time 0.00
Received By pleduc Date 2017-03-14 Time 12:12 Sent To  
Notes
2017-03-14 17:01:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET E 0.00 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT.
  
 PLEASE PROVIDE AN APPLICABLE NOTE INDICATING:
  
 THE FIRE ALARM SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY, EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
  
  
 2)
 SHEET P 3.01 - THERE ARE INDICATIONS OF FIRE SPRINKLER
 WORK.
  
 PLEASE PROVIDE AN APPLICABLE NOTE INDICATING:
  
 THE FIRE SPRINKLER SYSTEM SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM EXCEEDS 4
 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED
 UNTIL FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
 3)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 4)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-22 Cont ID  
Sent By tklarge Date 2017-05-22 Time 12:51 Rev Time 0.00
Received By tklarge Date 2017-04-27 Time 14:42 Sent To  
Notes
2017-04-27 15:32:36B36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 13:07 Rev Time 0.00
Received By rlecky Date 2017-03-02 Time 13:16 Sent To  
Notes
2017-03-06 13:16:53B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-03-16 Cont ID  
Sent By jwitmer Date 2017-03-16 Time   Rev Time  
Received By jwitmer Date 2017-03-16 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By ccole Date 2017-05-03 Time 07:49 Rev Time 0.00
Received By ccole Date 2017-05-02 Time 17:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-10 Cont ID  
Sent By ccole Date 2017-03-10 Time 15:11 Rev Time 0.00
Received By ccole Date 2017-03-10 Time 15:11 Sent To  
Notes
2017-03-10 15:39:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030121
 3/10/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE A VENTILATION CALCULATION FOR THE NEW
 RECONFIGURED RADIOLOGY ROOM PER TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) REFER TO TABLE 7-1 ASHRAE 170 AND PROVIDE THE DESIGN
 PARAMETERS FOR THE RADIOLOGY ROOM.
  
 3) M2.03: PROVIDE FIRE DAMPERS FOR THE DUCTS
 PENETRATING THE FIRE-RATED RADIOLOGY/CORRIDOR WALL.
  
 4) M0.00: PROVIDE THE CORRECT PROJECT DESIGN CRITERIA
 FOR WEST PALM BEACH FL. THE CRITERIA ON THE PLAN IS FOR
 MIAMI.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-22 Cont ID  
Sent By tklarge Date 2017-05-22 Time 12:51 Rev Time 0.00
Received By tklarge Date 2017-05-22 Time 12:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By tklarge Date 2017-03-20 Time 14:22 Rev Time 0.00
Received By tklarge Date 2017-03-20 Time 13:39 Sent To  
Notes
2017-03-20 14:22:29SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE ADDED
 SINK. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  