Plan Review Details - Permit 17021171
Plan Review Stops For Permit 17021171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-24 Cont ID  
Sent By jgomez Date 2017-03-24 Time 09:40 Rev Time 0.00
Received By jgomez Date 2017-03-24 Time 09:39 Sent To  
Notes
2017-03-24 09:45:40RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISED FLOOR PLAN SHOWS A NEW WINDOW ADJACENT TO
 THE SLIDING GLASS DOORS #104. PROVIDE SPECIFICATIONS
 FOR THE SIZE AND TYPE OF WINDOW. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: CONTRACTOR'S E-MAIL RESPONSE STATED THAT
 THERE IS NO ADDITIONAL WINDOW. REVISED SHEET S101
 CLEARLY SHOWS FRAMING PLAN #2 WITH CLOUDED #3 REVISION
 WHERE THE ADDITIONAL WINDOW IS SHOWN. IT ALSO SHOWS
 THAT DOOR #102 WAS REVISED FROM FRENCH DOORS TO SLIDING
 GLASS DOORS. PLEASE REVISE ALL PLANS INCLUDING
 ELECTRICAL AND MECHANICAL TO REFLECT THE ACTUAL
 PROPOSED CONDITIONS.
  
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW WINDOW TO THE THE
 SLIDING GLASS DOORS. SPECIFY ALL FRAMING MEMBERS SIZES
 AND ATTACHMENTS. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 RESPONSE: SEE RESPONSE TO COMMENT #1 ABOVE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW WINDOW ADJACENT TO SLIDING GLASS DOORS #104 AS
 SHOWN ON PLANS. COORDINATE SIZE AND TYPE WITH ITEM #1
 ABOVE.
 RESPONSE: SEE RESPONSE TO COMMENT #1 ABOVE.
  
 B) MULLION IF SPECIFIED BY THE ENGINEER OF RECORD ON
 ITEM #1 ABOVE. CLEARLY SPECIFY SIZE OF MULLION AND
 FASTENERS.
 RESPONSE: SEE RESPONSE TO COMMENT #1 ABOVE.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: SEE RESPONSE TO COMMENT #1 ABOVE.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-10 Cont ID  
Sent By jgomez Date 2017-03-10 Time 11:34 Rev Time 0.00
Received By jgomez Date 2017-03-10 Time 17:29 Sent To  
Notes
2017-03-10 17:33:55RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISED FLOOR PLAN SHOWS A NEW WINDOW ADJACENT TO
 THE SLIDING GLASS DOORS #104. PROVIDE SPECIFICATIONS
 FOR THE SIZE AND TYPE OF WINDOW. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW WINDOW TO THE THE
 SLIDING GLASS DOORS. SPECIFY ALL FRAMING MEMBERS SIZES
 AND ATTACHMENTS. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW WINDOW ADJACENT TO SLIDING GLASS DOORS #104 AS
 SHOWN ON PLANS. COORDINATE SIZE AND TYPE WITH ITEM #1
 ABOVE.
  
 B) MULLION IF SPECIFIED BY THE ENGINEER OF RECORD ON
 ITEM #1 ABOVE. CLEARLY SPECIFY SIZE OF MULLION AND
 FASTENERS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-16 Cont ID  
Sent By vperez Date 2017-03-16 Time 15:00 Rev Time 0.00
Received By rlecky Date 2017-03-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By fmittner Date 2017-03-14 Time 09:09 Rev Time 0.00
Received By fmittner Date 2017-03-14 Time 09:09 Sent To  
Notes
2017-03-10 17:08:02REVISED PLANS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-24 Cont ID  
Sent By jgomez Date 2017-03-24 Time 11:05 Rev Time 0.00
Received By jgomez Date 2017-03-24 Time 09:32 Sent To  
Notes
2017-03-24 09:33:39RECEIVED E-MAIL FROM PETER ADLER (CONTRACTOR).

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-16 Cont ID  
Sent By rlecky Date 2017-03-16 Time 15:00 Rev Time 0.00
Received By rlecky Date 2017-02-27 Time 11:25 Sent To  
Notes
2017-02-28 11:25:45R17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-24 Cont ID  
Sent By jgomez Date 2017-03-24 Time 09:51 Rev Time 0.00
Received By jgomez Date 2017-03-24 Time 09:51 Sent To  
Notes
2017-03-24 10:04:4103/24/17 TALKED TO TONY (A/C CONTRACTOR).
 NEED THE EQUIPMENT SIZING CALCULATIONS FOR THE REVISED
 EQUIPMENT AND THE RETURN AIR GRILL NEEDS TO BE AWAY
 FROM THE KITCHEN AREA.
  
  
  
  
 RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SIZE OF EQUIPMENT SHOWN ON SHEET M101 WAS CHANGED.
 PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC.
 M1401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- RETURN AIR GRILL CAN NOT BE LOCATED IN THE KITCHEN.
 SEC. M1602.2(4) FBC-RESIDENTIAL. REVISE PLAN ON SHEET
 M101.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-10 Cont ID  
Sent By jvalido Date 2017-03-10 Time 18:35 Rev Time 0.00
Received By jgomez Date 2017-03-10 Time 18:35 Sent To  
Notes
2017-03-10 18:37:25RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SIZE OF EQUIPMENT SHOWN ON SHEET M101 WAS CHANGED.
 PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC.
 M1401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- RETURN AIR GRILL CAN NOT BE LOCATED IN THE KITCHEN.
 SEC. M1602.2(4) FBC-RESIDENTIAL. REVISE PLAN ON SHEET
 M101.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-15 Cont ID  
Sent By gjohnson Date 2017-03-15 Time 12:43 Rev Time 0.00
Received By gjohnson Date 2017-03-15 Time 11:41 Sent To  
Notes
***NONE***