Plan Review Details - Permit 17021168
Plan Review Stops For Permit 17021168
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-08 Cont ID  
Sent By wjolin Date 2017-03-08 Time 16:48 Rev Time 0.00
Received By wjolin Date 2017-03-07 Time 17:25 Sent To M
Notes
2017-03-07 17:44:552210 NORTH AUSTRALIAN AVENUE
 PERMIT 17021168
 FIRE DEPT PLAN REVIEW COMMENTS
  
 *****PROVISO - SUBMIT REVISION*****
  
 FIRST FLOOR RESIDENTIAL IS NOT DIVIDED INTO TWO SMOKE
 COMPARTMENTS WITH SEPARATE FLOW SWITCHES.
  
 ARE EXISTING SPRINKLERS PROTECTING THE ELEVATOR PITS?
  
 NO SPRINKLERS PROTECTING SMALL CLOSESTS IN NEW
 RESIDENTIAL BOARD AND CARE OCCUPANCY. PER NFPA 13
 SECTION 8.15.8.2 CLOSETS AND PANTRIES. SPRINKLERS ARE
 NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND
 PANTRIES WITHIN DWELLING UNITS IN HOTELS AND MOTELS
 WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQUARE
 FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND
 THE WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIALS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 07:15 Rev Time 0.00
Received By ccole Date 2017-02-27 Time 11:09 Sent To  
Notes
2017-02-28 11:10:00ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 07:15 Rev Time 0.00
Received By ccole Date 2017-03-14 Time 07:15 Sent To  
Notes
***NONE***