| Plan Review Stops For Permit 17021129 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2017-03-07 11:45:04 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- GARAGE DOOR STRUCTURAL BUCK: PROVIDE COMPLETE DETAIL | | | AND SPECIFICATIONS FOR THE ATTACHMENT OF THE STRUCTURAL | | | BUCK TO THE SUPPORTING STRUCTURE. SPECIFY BUCK SIZE, | | | FASTENER TYPE, SIZE AND SPACING. DETAIL #11 ON SHEET | | | 12ABCD DOESN'T PROVIDE THIS INFORMATION. | | | 2- ARROW ORIENTATION SHOWN ON SHEET 2 OF 2 OF SURVEY | | | SUBMITED IS INCORRECT. REVISE AS REQUIRED. | | | 3- TRUSS PACKAGE SUBMITTED: THERE IS NO NEED TO SUBMIT | | | TRUSS PACKAGE FOR SINGLE FAMILY RESIDENCES (R3). THE | | | TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED IN | | | WRITING BY THE ARCHITECT OF RECORD. THEN, DELIVER THE | | | TRUSS PACKAGE TO THE BUILDING INSPECTOR AT TIME OF | | | FRAMING INSPECTION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-03-10 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-03-10 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-03-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-15 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-15 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-10 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-10 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2017-03-10 10:20:36 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR WATER | | | HEATER AND DRYER. PER THE FBC-2014 FUEL GAS CODE SEC. | | | 304 | | | | | | 2.THE FIRST SECTION OF CSST UPSTREAM OF THE DRYER | | | SHOULD BE EHD OF 37 OR 11/4 CSST . PER FBC FUEL GAS | | | TABLE 402.4(15) | | | | | | 3. THE SECOND SECTION OF CSST BETWEEN DRYER AND COOK | | | TOP SHOULD BE EHD OF 31 OR 1" CSST . PER FBC FUEL GAS | | | TABLE 402.4(15) | | | | | | 4.THE NOTE ON THE PLAN UNDER NAT. GAS @ 12-14" WC | | | STATES TOTAL BTU 568M THE RISER AND APPLIANCE SCHEDULE | | | SHOWS TOTAL BTU LOAD AT 168M PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 5. PLEASE PROVIDE SIZING TABLES USED TO SIZE SYSTEM. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-10 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-27 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2017-03-07 16:05:00 | $10,003.08 PAID. MU-2017-005174. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2017-03-07 12:21:21 | PROVIDE COPY OF PAID IMPACT FEES RECEIPT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2017-03-07 12:00:54 | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | 1- DEN ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-10 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-10 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2017-03-07 12:38:29 | A) ROOF TILE NOA 16-0314.08 | | | B) ROOF TILE UNDERLAYMENT NOA 15-0410.04. | | | C) ROOF VENTS FL16588-R1 AND NOA 13-0122.07 | | | D) ROOF TILE ADHESIVE FL6332-R5. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-03-03 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-03-03 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-03-03 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2017-03-03 12:08:25 | 3/3/17- PASSED | | | | | | IBIS RESIDENTIAL PLANNED DEVELOPMENT ZERO LOT LINE | | | LANDSCAPE PLAN APPROVED | | | ONE KITCHEN ONE UNIT | | | BUILDING HEIGHT 14FT. 8IN. MEETS HEIGHT LIMITS | | | ZERO SIDE SETBACK IS 8FT. MEETING 0FT. REQUIREMENT | | | SIDE SETBACK IS 15.69FT. MEETING 8FT. REQUIREMENT | | | A/C UNIT DOESN'T PROJECT INTO A REQUIRED SETBACK | | | FRONT SETBACK IS 45.47FT. MEETING 10FT. REQUIREMENT | | | REAR SETBACK IS 45.07FT. MEETING 10FT. REQUIREMENT | | | DRIVEWAY IS 18FT. WIDE MEETING 20FT. LIMIT | | | 5FT. 2IN SIDE SETBACK MEETS 3FT. REQUIREMENT | | | REQUIRED PERVIOUS SURFACE IN THE FRONT SETBACK IS | | | 577.5SQFT. | | | PROPOSED 590SQFT. | | | SCREEN ENCLOSURE HAS A 15.69SQFT. SIDE SETBACK MEETING | | | 3FT. REQUIREMENT | | | REAR SETBACK FOR A SCREEN ENCLOSURE IS 38.85FT. MEETING | | | 3FT. REQUIREMENT | | | | | | | | | PLEASE CONTACT | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING | | | DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL 33402 | | | OFFICE HOURS: M-F 8AM - 5PM | | | (561)822-1442 | | | [email protected] | | | |
|
|