Plan Review Details - Permit 17021076
Plan Review Stops For Permit 17021076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-01 Cont ID  
Sent By rmcdouga Date 2017-03-01 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2017-03-01 Time 18:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 07:57 Sent To  
Notes
2017-02-28 09:13:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROFLEX 90 MSC UNDERLAYMENT WAS TESTED FOR AIR
 BORNE AND STRUCTURAL SOUND TRANSMISSIONS WITH TILE ON
 AN 8" CONCRETE SLAB WITH A SUSPENDED GYPSUM BOARD
 CEILING. THIS IS NOT THE FLOOR CEILING ASSEMBLY FOR
 YOUR PROPOSED INSTALLATION. SUBMIT TWO COPIES OF THE
 PRODUCT TESTING FOR A 6" SLAB WITH NO SUSPENDED CEILING
 WHICH HAS SOUND TRANSMISSION RATINGS (STC AND II2) OF
 NOT LESS THAN 50. ALSO, SUBMIT TWO COPIES OF THE FLAME
 SPREAD AND SMOKE DEVELOPED TEST REPORTS ON THE PRODUCT.
 THE FLAME SPREAD INDEX MUST BE NO MORE THAN 25 AND
 SMOKE DEVELOPED INDEX CAN BE NO MORE THAN 450. FBC
 1207.2, 1207.3 & 720.2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-01 Cont ID  
Sent By rmcdouga Date 2017-03-01 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 14:27 Sent To  
Notes
2017-03-01 14:28:03RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2017-02-24 Time 11:08 Sent To  
Notes
2017-02-27 11:09:05BLDG <5K