| Plan Review Stops For Permit 17021032 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-02-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-20 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-20 |
Time |
07:41 |
Sent To |
Z |
|
| Notes |
| 2018-02-20 10:40:37 | SENT TO ZONING (LL). CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-10-05 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-10-03 |
Time |
08:24 |
Sent To |
P |
|
| Notes |
| 2017-10-05 16:17:31 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. IT IS RECOMMENDED THAT A SEPERATE PERMIT BE ISSUED | | | FOR THE GUEST HOUSE. THIS IS NOT MANDATORY BUT MAY | | | ASSIST IN OBTAINING A CERTIFICATE OF OCCUPANCY FOR THE | | | PRIMARY RESIDENCE. | | | 2. OWNER/AGENT TO SIGN ENERGY SUBMITTALS. | | | 3. PROVIDE FOUNDATION PLAN FOR GENERATOR, INCLUDE AN | | | ATTACHMENT DETAIL. ALSO PROVIDE THE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS FOR THE SPECIFIC GENERATOR TO | | | BE INSTALLED. | | | 4. PROVIDE ICC-ES REPORT FOR THE ICYNENE INSULATION. | | | IDENTIFY WHICH PRODUCT WILL BE INSTALLED. MANUFACTURERS | | | INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE AT TIME OF | | | INSTALLATION. | | | 5. PROVISOS FOR PRODUCT APPROVALS ARE ALLOWED. PLEASE | | | PROVIDE A LIST, REVIEWED AND APPROVED BY DESIGN | | | PROFESSIONAL OF ALL PRODUCTS TO BE DEFFERRED. THESE | | | DOCUMENTS SHALL BE REVIEWED AND APPROVED PRIOR TO | | | INSTALLATION. ALL OTHER SUBMITTAL DOCUMENTS SHALL BE | | | INCLUDED AT TIME OF PERMIT. | | | 6. PROVIDE ELEVATION CERTIFICATE. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD. | | | | | | AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-04-17 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-04-17 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-04-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-04-17 07:53:57 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | 2. NFIP - PROJECT IS LOCATED IN FLOOD ZONE A5. | | | 3. PROVIDE SITE PLAN WITH SITE DRAINAGE. | | | 4. ROOFING - SEPERATE PERMIT REQUIRED. | | | 5. PROVIDE SHORING PLAN FOR C.I.P. 2ND FLOOR AND ROOF. | | | 6. PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING: | | | SKYLIGHTS, ROOFTOP GLASS RAILING, OVERHEAD DOORS. | | | 7. PROVIDE SHOP DRAWINGS/ SPECIFICATIONS AND/OR | | | MANUFACTURERS INSTALLATION INSTRUCTIONS FOR THE | | | FOLLOWING: | | | SPIRAL STAIRCASE, FIREPLACES, ALUMINUM EYBROWS, | | | ELEVATOR, SOLAR PV PANELS, SOLAR WATER HEATER, 2ND | | | FLOOR LIFT, FIRE PITS, GLASS STAIR RAILS/GUARDS, BBQ | | | GRILL, WATER PROOF MEMBRANE FOR ELEVATOR PIT AND CAR | | | LIFTS. | | | 8. PLAN SHEET A-5.6 INDICATES A 4 CAR GARAGE, PLAN | | | SHEET A-2.1 INDICATES A 3 CAR GARAGE. PLEASE CLARIFY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS | | | A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. 6 INCHES. | | | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE) | | | REQUIRES AN ADDITIONAL 6 INCHES OF FREEBOARD REQUIRING | | | THE DESIGN FLOOD ELEVATION (DFE) TO BE 8. 0 FEET. | | | PLEASE INSERT THIS INFORMATION ON YOUR PLANS. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, | | | WINDOW, AND DOOR SUBMITTALS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-10-03 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-10-03 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-03-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-03-09 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-03-09 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-29 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-29 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2017-11-29 08:58:49 | OK PER EMAIL FROM VINCE NOEL DATED 11/29/17 | | | CREATED PDF OF EMAIL CHAIN AND SENT TO FILENET | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2017-11-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-28 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-28 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2017-11-28 06:34:52 | FAILED PENDING RESPONSE FROM ENGINEERING RE: UNITY OF | | | TITLE, CONSTRUCTION IN UTILITY EASEMENT | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-01 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-01 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-06 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-06 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-14 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-14 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2017-03-14 10:59:46 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. SHOW DISTANCE FROM REG. TO APPLIANCE. PER FBC 2014 | | | FUEL GAS CODE SEC. 402.4.1. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-01 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-01 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-02-15 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2018-02-16 09:50:13 | RESUB ROUTED TO CTHROOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-28 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-07 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-04-17 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-04-17 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-02-23 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2017-04-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-04-14 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-04-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-04-14 07:36:26 | FEES PAID 1/20/17 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-11-16 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-11-16 |
Time |
17:39 |
Sent To |
I |
|
| Notes |
| 2017-11-16 19:06:25 | PROVIDE ROOF STAND PRODUCT APPROVALS TO THE INSPECTOR | | | IN THE FIELD. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-04-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-04-12 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-04-11 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2017-04-12 15:52:23 | PLAN DENIED | | | 1) AHU # 2 REFER TO SECTION M1602.2 PROHIBITED | | | SOURCES # 1 RETURN AIR IN KITCHEN MUST BE 10 FT. | | | FROM ANY APPLIANCE.2014 FRC | | | 2) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS | | | ON THE KITCHEN HOOD AT FIRST INSPECTION. | | | 3) AHU # 3 PROVIDE SIZE OF GRILL IN FOYER ON THE PLAN. | | | 4) SHOW LOCATION OF ALL 6 CONDENSERS ON THE PLAN | | | SECTION 107-FBC. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2018-02-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-02-20 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-02-20 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2021-03-27 11:08:47 | NFIP REVIEW COMMENTS: | | | PROVIDE BUILDING UNDER CONSTRUCTION ELEVATION | | | CERTIFICATE AT PLACEMENT OF 1ST FLOOR. | | | PROVIDE FINISHED CONSTRUCTION ELEVATION CERTIFICATE | | | PRIOR TO C/O. | | | CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-10-05 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-10-03 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2017-10-05 15:55:30 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ELEVATION CERTIFICATE REQUIRED PRIOR TO ISSUANCE OF | | | PERMIT. | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS | | | A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7 FEET NGVD 29. | | | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. | | | 4658-16 (EFF. DATE 9-12-2016), REQUIRES AN ADDITIONAL 2 | | | FEET OF FREEBOARD REQUIRING THE DESIGN FLOOD ELEVATION | | | (DFE) TO BE 9.0 FEET NGVD 29. PLEASE NOTE THIS | | | INFORMATION ON YOUR PLANS. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD 29. | | | | | | AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2017-04-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-04-14 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-04-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-04-14 09:52:13 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS | | | A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7 FEET, NGVD | | | 29. THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. | | | 4658-16, (EFF. DATE 9-12-2016), REQUIRES AN ADDITIONAL | | | 2 FEET OF FREEBOARD REQUIRING THE DESIGN FLOOD | | | ELEVATION (DFE) TO BE 9. 0 FEET NGVD 29. PLEASE INSERT | | | THIS INFORMATION ON YOUR PLANS. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD. | | | | | | AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | 1612.1 GENERAL. | | | WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION | | | 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES | | | AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING | | | SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL | | | DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED | | | AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS | | | AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE | | | THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED | | | WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL | | | APPLY. | | | | | | 1612.4 DESIGN AND CONSTRUCTION. | | | THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES | | | LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH | | | HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF | | | ASCE 7 AND WITH ASCE 24. | | | | | | FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & | | | R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND | | | STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS | | | COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED | | | TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD | | | DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE | | | FLOOD ELEVATION CERTIFICATE. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-01 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-01 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-06 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-05 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-14 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-13 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2017-03-14 10:54:57 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE A WATER RISER DIAGRAM. PER WPB AMEND | | | TO FBC 107.3.5.3(11) | | | | | | 2. THE DRAIN FOR THE JACUZZI ON ROOF NOT SHOWN PLEASE | | | CLARIFY. WPB AMEND TO FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-10-05 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-10-05 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-04-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-04-14 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-04-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-04-14 13:30:10 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | 2. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM | | | COMPONENTS. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-02-22 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-02-21 |
Time |
|
Sent To |
P |
|
| Notes |
| 2018-02-22 15:24:14 | SEPERATE PERMITS REQUIRED FOR: LANDSCAPING, SWIMMING | | | POOL, DRIVEWAY AND WALKWAYS/PAVERS. | | | | | | NOTES: | | | | | | - SEE ATTACHMENTS FOR SUPPORTING EMAILS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-10-23 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-10-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-10-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-23 13:03:51 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SURVEY PROVIDED SHOWS THAT THERE ARE UTILITY | | | EASEMENTS RUNNING THROUGH THE PROPERTY. STRUCTURES | | | CANNOT BE BUILT OVER ANY UTILITY EASEMENTS. | | | | | | 2.) THE SURVEY SHOWS THAT THERE ARE TWO (2) PARCELS | | | ASSOCIATED WITH THE PROPERTY. A UNITY OF TITLE MAY BE | | | REQUIRED. A STOP HAS BEEN ADDED FOR THE ENGINEERING | | | SERVICES DEPARTMENT TO REVIEW THE PLANS. | | | | | | 3.) THE PLANS SHOW A KITCHEN IN THE GUEST BEDROOM ON | | | THE SECOND FLOOR. NO MORE THAN ONE (1) KITCHEN FACILITY | | | SHALL BE PROVIDED FOR THE OVERALL PROJECT. ALL PLANS | | | SHOULD BE CORRECTED FOR CONSISTENCY. | | | | | | 4.) PROVIDE ADDITIONAL INFORMATION ON THE ARCHITECTURAL | | | FEATURES THAT ARE LOCATED ABOVE THE MAXIMUM ALLOWABLE | | | HEIGHT IN THE DISTRICT. THE ARCHITECTURAL FEATURES SEEM | | | TO BE ENCLOSED SPACES, WHICH DOES NOT QUALIFY AS AN | | | ARCHITECTURAL FEATURES. | | | | | | 5.) DETAILS AND DIMENSIONS OF THE PROPOSED MOTORIZED | | | GATE ALONG FOREST HILL BOULEVARD NOT PROVIDED WITH THE | | | RESUBMITTAL. PLEASE PROVIDE. | | | | | | | | | NOTES: | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENT. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | * SURVEY SUBMITTED WITH RESUBMITTAL #2. ENGINEERING | | | REVIEW STOP ADDED FOR ENGINEERING DEPT. TO REVIEW | | | SURVEY AND PROPOSED DEVELOPMENT. | | | | | | * NO KITCHEN FACILITY SHALL BE PERMITTED IN THE GUEST | | | ROOM LOCATED ON THE SECOND FLOOR. THIS SHALL BE | | | CORRECTED ON ALL PLAN SHEETS FOR CONSISTENCY. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-03-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-03-02 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2017-03-03 13:27:00 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) A SURVEY OF THE PROPERTY IS REQUIRED. | | | | | | 2.) SITE PLAN SHOULD CLEARLY ILLUSTRATE/PROVIDE THE | | | FOLLOWING INFORMATION: | | | - NORTH ARROW. | | | - DATA TABLE SUPPLING THE FOLLOWING INFORMATION: ZONING | | | OF THE PROPERTY; TOTAL ACRES OF THE PROJECT; TOTAL | | | GROSS BUILDING SQUARE FOOTAGE; AMOUNT OF OPEN SPACE, | | | LANDSCAPING, BUILDING COVERAGE AND IMPERMEABLE SURFACE | | | IN PERCENTAGES AND IN SQUARE FEET; PARKING COMPUTATIONS | | | (PARKING REQUIRED, PROVIDED, ETC.) | | | - LOT DIMENSIONS AS PROVIDED IN THE SURVEY OF THE | | | PROPERTY. | | | - DIMENSIONS OF ALL DRIVEWAYS | | | - SETBACK DIMENSION FROM ALL PROPOSED STRUCTURES TO THE | | | PROPERTY LINE. | | | | | | 3.) THE PROPOSED RESIDENTIAL STRUCTURE SEEMS TO BE | | | ENCROACHING INTO THE 5 FT. SIDE SETBACK ALONG THE NORTH | | | PROPERTY LINE. PLEASE ADDRESS. [ZLDR S.94-72(A)(2)] | | | | | | 4.) THE MAXIMUM HEIGHT OF THE PROPOSED RESIDENTIAL | | | STRUCTURE FROM THE GROUND TO THE TOP OF THE STRUCTURE | | | IS 30 FT. THE ELEVATIONS INDICATE THAT THE HEIGHT OF | | | THE STRUCTURE EXCEEDS THE MAXIMUM ALLOWABLE HEIGHT (>33 | | | FT.). PLEASE ADDRESS. [ZLDR S.94-72(A)(3)] | | | | | | 5.) THE PLAN SHOWS MULTIPLE KITCHENS PROPOSED ON | | | DIFFERENT LEVELS OF THE RESIDENTIAL STRUCTURE; HOWEVER, | | | THE SF7 ZONING DISTRICT ALLOWS ONLY ONE (1) KITCHEN IN | | | THE PROPOSED RESIDENTIAL STRUCTURE. | | | | | | 6.) PROVIDE DETAILS AND DIMENSIONS OF THE PROPOSED | | | MOTORIZED GATE ALONG FOREST HILL BOULEVARD. | | | | | | 7.) MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO | | | THE POOL EQUIPMENT AND GENERATOR, MAY NOT PROJECT MORE | | | THAN 4 FT. INTO A SETBACK. [ZLDR S.94-305(A)(4)] | | | | | | 8.) PROVIDE VISIBILITY TRIANGLES IN ACCORDANCE WITH | | | ZLDR S.94-305(E) TO ENSURE THAT INTERSECTION VISIBLE IS | | | NOT OBSCURED BY THE PROPOSED WALL. | | | | | | 9.)THE SITE PLAN (SHEET A1.1) SHOWS TWO DRIVEWAYS ON | | | FOREST HILL BOULEVARD. THIS IS NOT PERMITTED. ONLY ONE | | | (1) DRIVEWAY WITH A WIDTH OF NO GREATER THAN 20 FT. AT | | | THE PROPERTY LINE SHALL BE PROVIDED ON FOREST HILL | | | BOULEVARD. ALTERNATIVELY, ONE (1) 10 FT. WIDE DRIVEWAY | | | ON FOREST HILL BOULEVARD AND ONE (1) 10 FT. WIDE | | | DRIVEWAY ON FLAGLER DRIVE CAN BE PROVIDED. [ZLDR | | | S.94-313(1)C.] | | | | | | 10.) A SEPARATE PERMIT FOR LANDSCAPING IS REQUIRED AND | | | SHALL BE SUBMITTED CONCURRENTLY WITH THIS PERMIT. | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. |
|
|