Plan Review Details - Permit 17021026
Plan Review Stops For Permit 17021026
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-14 Cont ID  
Sent By cthroop Date 2017-04-14 Time 09:55 Rev Time 0.00
Received By cthroop Date 2017-04-14 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By cthroop Date 2017-03-23 Time 08:40 Rev Time 0.00
Received By cthroop Date 2017-03-22 Time 11:40 Sent To  
Notes
2017-03-23 08:46:34BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN PEOFESSIONAL REQUIRED TO REVIEW AND APPROVE
 PLANS. ENGINEER SIGNATURE AND SEAL ON STRUCTURAL PLANS
 ONLY.
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE
 PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481.
 2. PRODUCT APPROVALS.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-07 Cont ID  
Sent By jleahy Date 2017-04-07 Time 16:20 Rev Time 0.00
Received By jleahy Date 2017-04-07 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-07 Cont ID  
Sent By jleahy Date 2017-03-07 Time 15:49 Rev Time 0.00
Received By jleahy Date 2017-03-07 Time 15:00 Sent To  
Notes
2017-03-07 16:20:2417021026
  
 1) RISER DIGRAM NEEDED 215.5
  
 2) LOAD CALCULATION FBC RESIDENTIA E 3602.2
  
 3) PANEL SCHEDULE(S) FBC RESIDENTIAL E 3706.2
  
 4) FIRST FLOOR SA SHOULD BE CO2 AND WITHIN 10' OF
 BEDROOM DOOR R-315.1
  
 5) SAME AT TOP OF THE STAIRS R-315.1
  
 6) LIGHT FIXTURE LAMPS TO BE 75% HIGH EFFICINCY FBC EC
 R 404.1
  
 7) NEED TO SHOW SERVICE LOCATION AND PANEL LOCATION
  
 8) FRONT/REAR OUTLETS MISSING FBC RESIDENTIAL E3901.7
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 WEST PALM BEACH, FL
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-04-14 Cont ID  
Sent By skennedy Date 2017-04-14 Time 09:48 Rev Time 0.00
Received By skennedy Date 2017-04-14 Time 09:48 Sent To  
Notes
2017-04-14 09:48:29A SEPARATE GAS SUBMITTAL IS REQQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By cthroop Date 2017-04-14 Time 09:55 Rev Time 0.00
Received By cthroop Date 2017-04-04 Time 16:05 Sent To  
Notes
2017-04-05 11:55:22R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By cthroop Date 2017-03-23 Time 08:40 Rev Time 0.00
Received By cthroop Date 2017-02-23 Time 14:12 Sent To  
Notes
2017-02-24 14:12:13R04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-11 Cont ID  
Sent By skennedy Date 2017-05-11 Time 10:52 Rev Time 0.00
Received By skennedy Date 2017-05-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By skennedy Date 2017-04-14 Time 09:41 Rev Time 0.00
Received By skennedy Date 2017-04-14 Time 09:29 Sent To  
Notes
2017-04-14 09:44:38THE APPLICANT HAS AGREED TO SUBMIT A REVISION TO
 INCLUDE A COMPLETE ENERGY AND EQUIPMENT SIZING
 CALCULATION. THERE WILL ALSO BE A SEPARATE GAS
 SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-22 Cont ID  
Sent By skennedy Date 2017-03-22 Time 11:27 Rev Time 0.00
Received By skennedy Date 2017-03-22 Time 11:27 Sent To  
Notes
2017-03-22 11:40:221ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 EQUIPMENT SCHEDDULE, SUPPLY DUCTS PER FBC-R M16 & BATH
 EXHAUST PER FBC-R M15.
  
 ADVISIORY
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT BEDROOMS.
  
 ADVISORY IT APPEARS APPLICABLE THAT AN ENERGY SUBMITTAL
 IS REQUIRED AS FOLLOWS:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 OR
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 AND
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-14 Cont ID  
Sent By gjohnson Date 2017-04-14 Time 09:24 Rev Time 0.00
Received By gjohnson Date 2017-04-14 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By gjohnson Date 2017-03-13 Time 15:00 Rev Time 0.00
Received By gjohnson Date 2017-03-09 Time 14:49 Sent To  
Notes
2017-03-09 17:04:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 2. SHOW LOCATION OF NEW WATER HEATER. PER WPB AMEND TO
 FBC 197.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. PER WPB
 AMEND TO FBC 107.3.5.3(11)
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  